13
ODSR Series "A" Outdoor Woodburning Fireplace
20006811
FP593
SR/C
11/20/97
Fig. 19
Installing firestop spacer.
FP593
Attic Installation
Ceiling Installation
Nails (4)
Firestop
Spacer
Joist
Joist
Firestop Spacer
Nails (4)
FP263
Fig. 20
Attic shield installlation (Canadian requirement).
FP263
MBUF
5/9/96
Attic
Insulation
Shield
Nails
(4 required)
Attic Joist
Ceiling
Base
Flanges
Chimney Supports
If chimney supports are required, they are installed the
same as elbows. Nail chimney support straps to adjacent
structural framing, as shown on, Page 9, Figure 10. Bend
straps as necessary and make sure they are secure so
they will support the weight of the chimney. A chimney
support is 2
¹⁄₂
" (64 mm) long when installed. Consider this
dimension when determining how many straight chimney
sections are needed.
NOTE:
Chimney supports are generally used in long runs
in a chase installation.
Additional Ceilings
If you encounter additional ceilings, repeat same steps
required for first ceiling installation. Refer to firestop il-
lustration on Figure 19.
Penetrating the Roof
Run pipe to roofline. Since chimney system must be vented
to the out-of-doors, you
must
use an approved Vermont
Castings Group termination.
If a chase is used, refer to the installation manual provided
with the termination cap.
Locate Chimney Centerpoint On Roof
Use same procedure detailed in locating centerpoint of
the flue system.
Drive a nail up through roof at the center point. This will
determine center point on outside of the roof.
Cut and Frame Roof hole
Size of roof hole varies with the type of chimney termina-
tion installed. Refer to installation instructions provided
with Vermont Castings Group chimney termination to find
correct size of roof hole.
There must be a 1
¹⁄₂
(38 mm) air space between outermost
portion of chimney sections and any adjacent combustible
surfaces. (Combustible surfaces include burnable materi-
als such as: ceiling members, joists, flooring, combustible
insulation and roof structures.)
WARNINg: DO NOT PACK REQUIRED AIR SPACES
WITh INSULATION OR OThER MATERIALS.
Mark an outline of the roof hole around the center of the
point nail.
NOTE:
Hole dimensions given in the chimney
top installation instructions are
horizontal
dimensions;
therefore, the hole size must be marked on the roof ac-
cordingly.
Cover the opening of the installed chimney so debris can-
not get into the system.
Install the attic insulation shield with the flanges on its base
extending down into the framing hole. Nail each corner of
attic insulation shield to the framing members of the ceil-
ing hole using 8d nails. Attic shields are not required at
the roof.
Continue Installing Pipe to Complete Run
Continue attaching pipe sections to complete system
to next level always being careful that the pipe is firmly
snapped locked in place before proceeding to next pipe
section.