ICFDV40 Fireplace Insert
CLEARANCES
12” (305 mm)
Maximum Depth
14”
(355 mm)
Side Wall
Combustible Mantel
Side Facing
10” (254 mm)
Minimum
10” (254 mm)
Minimum
11”
(279 mm)
INSERT CLEARANCES
No combustibles (ie: drapes, doors) may be within, or
swing within 36" of the front of the insert.
MANTEL CLEARANCES
NOTE: The combustible area above the facing must
not protrude more than 3/4" from the facing. If it does,
it is considered a mantel and must meet the mantel
requirements listed in this manual.
FP2992
Figure 3 -
Mantel Clearances
NOTE:
Side clearance to com-
bustibles is 10" (254 mm) from
opening whether it is side wall
or mantel legs.
14"
(355 mm)
12" (305 mm)
Finish Wall
FP2993
Figure 4 -
Mantel Clearances
Fireplace Insert
Opening
Noncombustible
Material Required up
to 9" Above Fireplace
Opening
HEARTH REQUIREMENTS
The insert must be installed on a noncombustible hearth
extending a minimum of 10" (254 mm) from the
fi
replace
opening (local codes may require a larger hearth). The
hearth must also extend to both sides of the face.