Dutchwest Natural Vent Gas Heater

30002008

Passing Through a 

Combustible Wall or Ceiling

An approved pass-through device is always required 
when a vent passes through a combustible wall or ceil-
ing. Check with the maker of the vent system for the 
correct listed devices that are available. A listed pass-
through device is required whether or not the installa-
tion includes decorative pipe around the Type B venting 
system.  

NOTE:

 It is essential to seal between the ceil-

ing support (sometimes called a ‘firestop spacer’) and 
the decorative pipe, if installed, with a high-temperature 
silicone sealant. (Fig. 6)
Complete the venting system installation according to 
the manufacturer’s instructions. 

Fig. 7

  Vent termination window.

Venting Requirements

FP567
NVBR/NVBC VENTING RUNS
11/12/97

Venting Runs 

A: 

Vertical installations up to 36 feet (12m) in 

     height. Up to an 18 ft. horizontal vent run can be

     installed within the vent system using a 

     maximum of two 90-degree elbows or four 

     45-degree elbows.

B: 

Vertical installations up to 36 feet (12m) in 

     height. Up to a 24 ft. horizontal vent run can be

     installed within the vent system using a 

     maximum of two 45-degree elbows. 

     (Ratio = 2/3, Hor./Vert.)

= Acceptable venting configuration
= Unacceptable venting configuration

NOTE: When venting staight vertical, without an

elbow, a minimum of 8 ft. vertical is required

off the top of the stove.

Horizontal Run (in feet)

Vertical Run (in feet)

(Measured from top of the unit before any elbow

)

36
34
32
30
28
26
24
22
20
18
16
14
12
10

8
6
4
2

1   2   4     6    8    10  12 14  16  18   20  22  24

A

B

FP567b

ST361

Ceiling pass thru

5/11/00   djt

Joists

Ceiling 

Support

Trim Col-

lar

Air Space

Listed 4” 

(102mm) 

B-Vent

Decorative 

6” Pipe

High-Tempera-

ture Silicone 

Sealant

Air Space as Re-

quired by Code

ST361

Fig. 6

  A ceiling pass-through, with decorative pipe around the 

vent.

High-Tem-

perature 

Silicone 

Sealant

Содержание Dutchwest 2467

Страница 1: ...om your neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the re department DO NOT STORE OR USE GASO LINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE...

Страница 2: ...rements 6 Vent Layout and Height Requirements 6 Passing Through a Combustible Wall or Ceiling 7 Venting Requirements 7 Install the Optional Fan 8 Venting System Assembly 9 Connect the Gas Supply Line...

Страница 3: ...venting system WARNING Operation of this heater when not con nected to a properly installed and maintained venting system or tampering with the vent safety shutoff system can result in carbon monoxid...

Страница 4: ...lve Inlet C L Valve Inlet 2008 Dutchwest NV dimensions 6 23 03 17 419 mm 23 584 mm 28 721 mm 4 111 mm 6 172 mm 12 318 mm 24 622 mm See Page 5 for Flue Collar Centerline Dimensions Fig 1 Dutchwest dime...

Страница 5: ...m clearance to combustible materials Maintain a 6 152 mm clearance when using single wall pipe The gas appliance and vent system must be vented directly to the outside of the building and never be att...

Страница 6: ...at a Type B vent system rising on the outside of the home be enclosed in a chase Check your local codes for requirements The minimum vent system height for the Dutchwest Natural Vent Stove is 8 2 43 m...

Страница 7: ...o 36 feet 12m in height Up to an 18 ft horizontal vent run can be installed within the vent system using a maximum of two 90 degree elbows or four 45 degree elbows B Vertical installations up to 36 fe...

Страница 8: ...snapstat bracket Use needle nose pliers to remove the black plastic grommet from the bracket Discard the bracket Connect the two wires to the two snapstat extension leads pro vided with the parts bag...

Страница 9: ...e rebox Use a B vent adapter from the same maker as the rest of the B vent components to join the rst section of venting to the draft hood The stove includes a spill switch Operating this stove when n...

Страница 10: ...f 10 0 and a mini mum inlet supply pressure of 11 0 w c In the U S Gas connection should be made in ac cordance with current National Fuel Gas Code ANSI Z223 1 NFPA 54 Since some municipalities have a...

Страница 11: ...ig 19 Attach switch assembly to rear shroud PILOT ADJ TP TH TPTH ST228 attach switch wires to valve 12 99 ST228 Fig 20 Attach switch wires to valve Install the Log Set 1 Remove the logs from their pac...

Страница 12: ...engage with the corresponding ribs at the bottom When properly installed the bottom of the stove front cannot be pulled away from the sides without also lifting it ST773 handle assy 6 6 03 3 8 Lock in...

Страница 13: ...iate the condition Pilot and Burner Inspection Each time you light your heater check that the pilot ame and burner ame patterns are as shown in Fig ures 26 and 27 If ame patterns are incorrect turn th...

Страница 14: ...ING smell all around the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF YOU SMELL GAS Do not try to light any replac...

Страница 15: ...burner lights wires are faulty or connections are bad B Thermopile may not gen 1 Be sure wire connecitons from thermopile at gas ate suf cient voltage valve terminals are tight and thermopile is full...

Страница 16: ...il the operation of the converted appliance is checked as speci ed in the manufacturer s instructions supplied with the kit CAUTION The gas supply shall be shut off prior to disconnecting the electric...

Страница 17: ...l s Starting at 5251 ST718 Fig 33 Natural gas air shutter setting ST726 SNV air shutter lp gas position 8 23 02 djt 1 8 3 8 Air Shutter LP Position Air Shutter LP Position Con guration for Stove with...

Страница 18: ...Rear Part Minimum Maximum Setting 000 5022 69 029 30000513 54 055 20000130 21 500 28 000 3 8 Open Conversion to Natural Gas Input BTU h Air Shutter Kit Front Part Rear Part Minimum Maximum Setting 00...

Страница 19: ...ture stove paints available through your local dealer to touch up areas as needed Clean areas to be painted with a wire brush and be sure to cover the logs burner and valve assembly glass and frame as...

Страница 20: ...upply before inspecting the system Both the inner exhaust pipe and the outer combustion supply pipe must be checked to con rm that they are unblocked and in good condition Check the Gas Flame Regularl...

Страница 21: ...Rheostat Chassis Ground RHEOSTAT SNAPSTAT BOX Snapstat BLK B L K BLK BLK BLK WHT ST153 rdv connections diag 10 99 Fig 42 Fan circuit MOTOR SNAPSTAT ON OFF RHEOSTAT WHT WHT BLK BLK BLK GRN BLK ST236 F...

Страница 22: ...s 30002005 4 Grille NV DW Gas 30002044 5 Front DW Gas 30001928 6 Door DW Gas 30001929 7 Leg DW Gas 30001930 1a 1b 1c PILO T ON OFF PILOT ADJ L O H I 15a b 16 17 18 21 20 28 25 26 27 30a b 23a b 31 32...

Страница 23: ...6 22a Ori ce Hood 69 0 0292 Front LP 30000513 22b Ori ce Hood 54 Front Natural 20000130 22c Or ce Hood 54 Rear LP 20000130 22d Or ce Hood 44 Rear NG 30000334 23a Ori ce Pilot 62 NG Top Convertible 100...

Страница 24: ...rolled by a snapstat that turns power on and off as the rebox tem perature rises above and falls below a preset tempera ture A rheostat provides for variable fan speeds Speci cations 115 Volt 60Hz 75...

Страница 25: ...25 Dutchwest Natural Vent Gas Heater 30002008...

Страница 26: ...26 Dutchwest Natural Vent Gas Heater 30002008...

Страница 27: ...stomer s home or in the dealer s shop Ifuponinspection thedamageisfoundtobethefaultofthemanufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or componen...

Страница 28: ...Ef ciency Ratings Model EnerGuide Ratings Fireplace Ef ciency 2467 51 4 2468 51 4 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: