background image

3

Dutchwest Direct Vent / Natural Vent Gas Heater

30001935 

General Information

The Dutchwest Direct Vent/Natural Vent Room Heater, 

Model  Nos. 3070, 3071, 3072 and 3073, is a vented gas 
appliance listed to the ANSI standard Z21.88b-2001  and 
CSA-2.33b-2001 for Vented Room Heaters, and  CSA 2.17-
M91, Gas-Fired Appliances For Use at High Altitudes.

The installation of the Dutchwest Direct Vent/Natural 

Vent Room Heater must conform with local codes, or in the 
absence of local codes, with National Fuel Gas Code, ANSI 
Z223.1/NFPA 54 — latest edition and CSA B-149.1  Instal-
lation Code. (EXCEPTION:  Do not derate this appliance 
for altitude.  Maintain the manifold pressure at 3.5”  w.c. for 
Natural Gas and 10.0” w.c. for LP gas at maximum input.) 

This appliance is only for use with the type of gas indicat-

ed on the rating plate. This appliance is not convertible for 
use with other gases unless a certified kit is used. 

Installation and replacement of gas piping, gas utiliza-

tion equipment or accessories, and repair and servicing 
of equipment shall be performed only by a qualified 
agency.  The term “qualified agency” means any individ-
ual, firm, corporation, or company that either in person 
or through a representative is engaged in and is respon-
sible for  (a) installation or replacement of gas piping, 
or (b), the connection, installation, repair, or servicing 
of equipment, who is experienced in such work, familiar 
with all precautions required, and has complied with all 
the requirements of the authority having jurisdiction.

The Dutchwest Direct Vent/Natural Vent Room Heater 

should be inspected before use and at least annually by 
a qualified service agency. It is imperative that control 
compartments, burners, and circulating air passage-
ways of the appliance be kept clean.

 

The Dutchwest Direct Vent/Natural Vent Room Heater and 

its individual shut-off valve must be disconnected from the 
gas supply piping during any pressure testing of that system 
at test pressures in excess of 1/2 psig (3.5 kPa).

The Dutchwest Direct Vent/Natural Vent Room Heater 

must be isolated from the gas supply piping system by clos-
ing its individual manual shutoff valve during any pressure 
testing of the gas supply piping system at test pressures 
equal to or less than 1/2 psig.

‘Direct Vent’ describes a sealed combustion system in 

which incoming outside air for combustion and outgoing 
exhaust enter and exit through two separate concentric 
passages within the same sealed vent system. The system 
does not use room air to support combustion. The Direct 
Vent system permits the gas appliance to be vented directly 
to the outside atmosphere through the side of the house or 
vertically through the roof. Conventional venting systems 
(Natural Vent) take air from the room for combustion and 
vent the exhaust vertically through the roof to the atmo-
sphere.

This appliance is approved for bedroom installations in the 

U.S. and Canada.

This appliance may be installed in an aftermarket* manu-

factured (mobile) home, where not prohibited by state or 
local codes. 

WARNING: Operation of this heater when not con-

nected to a properly installed and maintained venting 
system can result in carbon monoxide (CO) poisoning 
and possible death.

The Dutchwest Direct Vent/Natural Vent Room Heater, 

when installed, must be electrically grounded in accordance 
with local codes or, in the absence of local codes, with the 
National Electrical Code ANSI/NFPA 70, (latest edition), or of 
the current Canadian Electrical Code C22.1.

Due to high temperatures this appliance should be 

located out of traffic and away from furniture and drap-
eries.

WARNING:  This appliance is hot while in operation.  

Keep children, clothing, and furniture away.  Contact 
may cause burns or ignition of combustible materials.

Children and adults should be alerted to the hazards 

of high surface temperatures and should stay away to 
avoid burns or clothing ignition. Young children should 
be carefully supervised when they are in the same room 
as the appliance.

Clothing or other flammable materials should not be 

placed on or near the appliance. 

Any safety screen, glass or guard removed for servic-

ing an appliance must be replaced prior to operating the 
appliance.

The appliance area must be kept clear and free from 

combustible materials, gasoline, and other flammable 
vapors and liquids.

The flow of combustion and ventilation air must not 

be obstructed. The installation must include adequate 
accessibility and clearance for servicing and proper 
operation.

WARNING:  Do not operate the Room Heater with the 

glass panel removed, cracked or broken. Replacement 
of the panel should be done by a licensed or qualified 
service person.

Do not use this appliance if any part has been under 

water. Immediately call a qualified service technician 
to inspect the appliance and to replace any part of the 
control system and any gas control which has been 
under water.

Do not burn wood, trash or any other material for 

which this appliance was not designed. This appliance 
is designed to burn either natural gas or propane only.

This gas appliance must not be connected to a chim-

ney flue serving a separate solid-fuel burning appliance.

CAUTION: Label all wires prior to disconnection when 

servicing controls. Wiring errors can cause improper 
and dangerous operation.

Verify proper operation after servicing.
Proposition 65 Warning:

 Fuels used in gas, woodburn-

ing or oil fired appliances, and the products of combustion of 
such fuels, contain chemicals known to the State of Cali-
fornia to cause cancer, birth defects and other reproductive 
harm.

California Health & Safety Code Sec. 25249.6

* Aftermarket: 

 Completion of sale, nor for purpose of resale, from 

the manufacturer.

Содержание Dutchwest 2465

Страница 1: ...ANUAL BEFORE INSTALLING AND USING APPLIANCE INSTALLER CONSUMER SAFETY INFORMATION FOR YOUR SAFETY Installation and service must be performed by a quali ed installer service agency or the gas supplier...

Страница 2: ...12 Install the Optional Fan 13 Venting System Assembly Direct Vent 14 Install Vent Adapter Pipe CFM Vent Components 14 Install Vent Adapter Pipe Simpson Dura Vent Components 15 Side Wall Termination A...

Страница 3: ...the room for combustion and vent the exhaust vertically through the roof to the atmo sphere This appliance is approved for bedroom installations in the U S and Canada This appliance may be installed...

Страница 4: ...utchwest stove is shipped from the factory as a Direct Vent Gas Heater This heater may be convert ed into a Natural Vent unit in the eld If a Natural Vent heater is desired the Z31D00 FSDHAG Draft Hoo...

Страница 5: ...her most often The vent system requirements NOTE We do not recommend the use of wallpaper next to this stove Over time radiant heat may cause the wallpaper to shrink or may adversely affect the binder...

Страница 6: ...ST131c Dutchwest wall thimble 5 15 03 djt A A Effective Minimum Wall Thimble 57 1461 mm CFM Pipe Centerline 53 1359 mm Simpson DuraVent Pipe ST131c Fig 5 Minimum wall thimble centerline Wall and Ceil...

Страница 7: ...ncial and or local authorities having jurisdiction for installations at elevations above 4 500 feet 1 370m WARNING Improper installation adjustment alteration service or maintenance can cause in jury...

Страница 8: ...ning the installation consider the location of the vent terminal and clearances Some of the most common clearances to keep in mind are shown in Fig ure 10 Important All vent clearances must be maintai...

Страница 9: ...als shall not be recessed into a wall or siding Horizontal venting must be installed on a level plane without an inclining or declining slope There must not be any obstruction such as bushes garden sh...

Страница 10: ...tor assy I Clearance to service regulator vent outlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air i...

Страница 11: ...ctor plate supplied with the stove is not used Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with combustible and noncombustible exteriors G Combustible 6 15...

Страница 12: ...the Wall Vent Kit 7TFSMSK 1 90 Degree Elbow CG 1 24 Straight pipe CG 1 36 Straight pipe CG 1 Side Wall Termination 1 Firestop 1 Zero clearance sleeve 1 Hardware package 1 Finishing plate CG 1 Finishi...

Страница 13: ...onents 2 Remove the rear skirt insert panel at the bottom of the Rear Skirt Fig 13 and fasten the blower as sembly to the rebox back with the two Phillips pan head bolts originally installed in the re...

Страница 14: ...est restictor plate 5 15 03 ST759 Fig 16 Install the restrictor plate only if required for the vent ing con guration Refer to Page 8 2 Attach Inner Starter Pipe found in with the logset to the next se...

Страница 15: ...Simpson DuraVent install inner adapter pipe ST763 DW dura vent attach outer assy ST763 Fig 21 Simpson DuraVent install outer adapter pipe Side Wall Termination Assembly 1 Locate the vent opening on th...

Страница 16: ...equired if installing a second 90 elbow Fig 25 8 Slip the wall plate and trim collar over the interior end of the horizontal pipe and install into the wall sleeve Seal the joint inside the wall plate...

Страница 17: ...d Bracket Wall Screws and Anchors Waterproof Seal Around Pipe ST219 Fig 29 Use extension brackets to mount snorkel against recessed wall If the foundation is recessed use extension brackets not suppli...

Страница 18: ...types of B vent pipe use components from one maker or the other Follow the vent component maker s instructions exactly The heater will also accept standard or enam elled 7 150mm diameter pipe around...

Страница 19: ...the rebox 5 Loosely sprinkle the lava rocks directly on top of the burner in front of and between the decorative grate and the right and left logs Use the lava rock to cover brackets on the burner Fig...

Страница 20: ...inlet supply for adjustment of 5 5 w c In order to connect Propane use a tting with 3 8 NPT nipple on the valve side and 1 2 propane gas supply line with an input of 28 000 BTUs at a manifold pressure...

Страница 21: ...which holds the injectors at a 90 angle to the base Fig 40 This keeps the ori ces aligned with tubes on the inside of the burner Failure to do so could affect the ame appearance and performance of the...

Страница 22: ...e 3 8 locking nut provided Fig 43 The front attaches to the stove by four steel tabs that engage with corresponding cast ribs onto the sides and bottom of the stove body Position the front about 3 dow...

Страница 23: ...s sistance Do not operate the heater until the pilot ame is correct Follow regular maintenance procedures as described on Page 30 ST769 Dutchwest pilot location 5 15 03 djt Pilot Assembly ST769 Fig 45...

Страница 24: ...these instruc tions exactly B BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF Y...

Страница 25: ...e thermocouple operates the pilot ame Tighten the thermocouple The thermopile operates the main valve ON and OFF Clean and or adjust pilot for maximum ame impingement on thermocouple and thermopile Tu...

Страница 26: ...on a at padded surface such as a coun ter protected by a towel 4 Remove the logset from the rebox 5 Remove the rear log bracket by unfastening the screw Fig 49 6 Remove the right and left log bracket...

Страница 27: ...spring and diaphragm assembly FC107 D E F FC108 SIT regulator conversion 10 03 OF F P I L O T O FC108 Fig 52 Replace regulator CO105a gas conversion Pilot 1 28 00 djt Pilot Hood Pilot Bracket CO105a...

Страница 28: ...he tubes inside burner Failure to do so could affect the ame appearance and performance of the unit 22 Place conversion label on valve 23 Reinstall the right and left log bracket assembly 24 Reinstall...

Страница 29: ...ature stove paints available through your local dealer to touch up areas as needed Clean areas to be painted with a wire brush and be sure to cover the logs burner and valve assembly glass and frame a...

Страница 30: ...g properly check the ames periodically to con rms they match Figure 61 The ames will be blue during the rst 15 20 minutes of operation and will gradually turn to yellow after that Do not use your stov...

Страница 31: ...t circuit NOTE IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE SF 2 200 WIRE OR ITS EQUIVALENT Thermocouple Safety Limit Switch Valve ST665 Sa...

Страница 32: ...e changes in design materials speci cations prices and discontinue colors and products at any time without notice Dutchwest Direct Vent Natural Vent Gas Heater Models 2465 2466 Ref Description Dutchwe...

Страница 33: ...T24 10001297 20 Nut Electrode SIT 0 974 144 57886 21 Tubing Pilot w Fittings 1 8 x 24 10001296 22 Burner Housing Assembly NG LP 20002214 23 Grate Burner JDV 20002167 24 Ashdoor Handle Assy E V WSI 500...

Страница 34: ...itself does not require regular maintenance however periodic cleaning of the fan and the surround ing area is required Installation Refer to Page 13 for installation instructions Remote Controls The r...

Страница 35: ...vel fees or service charges for in home repair work It is the dealers op tion whether the repair work will be done in the customer s home or in the dealer s shop If upon inspection the damage is found...

Страница 36: ...Ef ciency Ratings Model EnerGuide Ratings Fireplace Ef ciency 2465 63 0 2466 63 0 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: