Dutchwest Direct Vent / Natural Vent Gas Heater

30001935

Vertical Termination - Direct Vent ONLY

A vertical vent system must terminate no less than 8’ 
(2.44m) and no more than 40’ (12m) above the appli-
ance flue collar. A 2

¹⁄₄

” restrictor plate (supplied) must 

be used where specified in all vertically terminated vent 
systems. (Fig. 8) 

NOTE: The restrictor plate supplied 

with the vertical termination should be discarded. 
Install restrictor plate supplied with stove directly at 
stove outlet.

 A vertically terminated vent system must 

also conform to the following criteria:
•    No more than three 90˚ elbows may be used.
•  Two 45˚ elbows may be substituted for one 90˚ 

elbow. No more than six elbows may be used.

•    Vent must rise a minimum of 2 feet before offset is 

used.

•    Termination height must conform to roof clearance 

as specified in Figure 9.

20
19
18
16
15
14
13
12
11
10
9
8
7
6
5

  4
  3

2
1
0

20

1

2

3

4

5

6

7

8 9

10 11 12 13 14 15 16 17 18 19

Vertical Run (in feet)

(Measure from the appliance flue collar to the top of the vent pipe.)

Horizontal Run (in feet)

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

ST132a

FDV28

Vertical 

vent run

12/3/99 djt

area

modified

1/11/00 djt

All Vertical Termina-
tions in this area 
Require use of the 
2

¹⁄₄

” Restrictor Plate*

Vertical terminations 

must be within this area

Unacceptable Venting 

Configuration

No Restrictor Plate

ST132a

Fig. 8 

 Vertical vent  termination window.

*The Restrictor Plate is used on Direct Vent Installations 
Only

Vent Termination Clearances

When planning the installation, consider the location 
of the vent terminal and clearances. Some of the most 
common clearances to keep in mind are shown in Fig-
ure 10. 

Important: All vent clearances must be maintained. 
Check your vent termination clearances against 
Figures 9 through 11.

The vent should be placed so that people cannot be  
burned by accidentally touching the vent surfaces when 
the stove is operating.
The vent termination should be located where it cannot 
be damaged by such things as automobile doors, lawn 
mowers or snowblowers and it should be located away 
from areas where it could become blocked by snow, 
etc.
Some considerations are:
•   Obstructions or impediments to venting.
•   Nearby combustible materials that could come into 

contact with combustion exhaust gases.

•   Other nearby openings {within 12” (305mm)} through 

which exhaust gas could reenter the building.

•   All vegetation within 3’ ((76mm) that may interfere 

with the draft.

Other factors that influence where the installation will 
be sited include the location of outside walls, where 
additional heat may be desired in the home, where the 
family members gather most regularly, and perhaps 
most importantly, the distance limitations of the venting 
system.

 

IMPORTANT

 

Direct Vent Only

•   The horizontal termination must not be recessed 

into the exterior wall or siding.

•   Horizontal vent runs must be level toward the vent 

termination.

•   Clearances around the vent termination must be 

maintained.

•  For installations using Simpson DuraVent pipe, 

parallel installations with minimum wall clearance 
have restricted access for connecting the Hori-
zontal Vent Cap straps to the vent pipe. See the 
maker’s instructions for recommended installation 
procedures.

Содержание Dutchwest 2465

Страница 1: ...ANUAL BEFORE INSTALLING AND USING APPLIANCE INSTALLER CONSUMER SAFETY INFORMATION FOR YOUR SAFETY Installation and service must be performed by a quali ed installer service agency or the gas supplier...

Страница 2: ...12 Install the Optional Fan 13 Venting System Assembly Direct Vent 14 Install Vent Adapter Pipe CFM Vent Components 14 Install Vent Adapter Pipe Simpson Dura Vent Components 15 Side Wall Termination A...

Страница 3: ...the room for combustion and vent the exhaust vertically through the roof to the atmo sphere This appliance is approved for bedroom installations in the U S and Canada This appliance may be installed...

Страница 4: ...utchwest stove is shipped from the factory as a Direct Vent Gas Heater This heater may be convert ed into a Natural Vent unit in the eld If a Natural Vent heater is desired the Z31D00 FSDHAG Draft Hoo...

Страница 5: ...her most often The vent system requirements NOTE We do not recommend the use of wallpaper next to this stove Over time radiant heat may cause the wallpaper to shrink or may adversely affect the binder...

Страница 6: ...ST131c Dutchwest wall thimble 5 15 03 djt A A Effective Minimum Wall Thimble 57 1461 mm CFM Pipe Centerline 53 1359 mm Simpson DuraVent Pipe ST131c Fig 5 Minimum wall thimble centerline Wall and Ceil...

Страница 7: ...ncial and or local authorities having jurisdiction for installations at elevations above 4 500 feet 1 370m WARNING Improper installation adjustment alteration service or maintenance can cause in jury...

Страница 8: ...ning the installation consider the location of the vent terminal and clearances Some of the most common clearances to keep in mind are shown in Fig ure 10 Important All vent clearances must be maintai...

Страница 9: ...als shall not be recessed into a wall or siding Horizontal venting must be installed on a level plane without an inclining or declining slope There must not be any obstruction such as bushes garden sh...

Страница 10: ...tor assy I Clearance to service regulator vent outlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air i...

Страница 11: ...ctor plate supplied with the stove is not used Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with combustible and noncombustible exteriors G Combustible 6 15...

Страница 12: ...the Wall Vent Kit 7TFSMSK 1 90 Degree Elbow CG 1 24 Straight pipe CG 1 36 Straight pipe CG 1 Side Wall Termination 1 Firestop 1 Zero clearance sleeve 1 Hardware package 1 Finishing plate CG 1 Finishi...

Страница 13: ...onents 2 Remove the rear skirt insert panel at the bottom of the Rear Skirt Fig 13 and fasten the blower as sembly to the rebox back with the two Phillips pan head bolts originally installed in the re...

Страница 14: ...est restictor plate 5 15 03 ST759 Fig 16 Install the restrictor plate only if required for the vent ing con guration Refer to Page 8 2 Attach Inner Starter Pipe found in with the logset to the next se...

Страница 15: ...Simpson DuraVent install inner adapter pipe ST763 DW dura vent attach outer assy ST763 Fig 21 Simpson DuraVent install outer adapter pipe Side Wall Termination Assembly 1 Locate the vent opening on th...

Страница 16: ...equired if installing a second 90 elbow Fig 25 8 Slip the wall plate and trim collar over the interior end of the horizontal pipe and install into the wall sleeve Seal the joint inside the wall plate...

Страница 17: ...d Bracket Wall Screws and Anchors Waterproof Seal Around Pipe ST219 Fig 29 Use extension brackets to mount snorkel against recessed wall If the foundation is recessed use extension brackets not suppli...

Страница 18: ...types of B vent pipe use components from one maker or the other Follow the vent component maker s instructions exactly The heater will also accept standard or enam elled 7 150mm diameter pipe around...

Страница 19: ...the rebox 5 Loosely sprinkle the lava rocks directly on top of the burner in front of and between the decorative grate and the right and left logs Use the lava rock to cover brackets on the burner Fig...

Страница 20: ...inlet supply for adjustment of 5 5 w c In order to connect Propane use a tting with 3 8 NPT nipple on the valve side and 1 2 propane gas supply line with an input of 28 000 BTUs at a manifold pressure...

Страница 21: ...which holds the injectors at a 90 angle to the base Fig 40 This keeps the ori ces aligned with tubes on the inside of the burner Failure to do so could affect the ame appearance and performance of the...

Страница 22: ...e 3 8 locking nut provided Fig 43 The front attaches to the stove by four steel tabs that engage with corresponding cast ribs onto the sides and bottom of the stove body Position the front about 3 dow...

Страница 23: ...s sistance Do not operate the heater until the pilot ame is correct Follow regular maintenance procedures as described on Page 30 ST769 Dutchwest pilot location 5 15 03 djt Pilot Assembly ST769 Fig 45...

Страница 24: ...these instruc tions exactly B BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF Y...

Страница 25: ...e thermocouple operates the pilot ame Tighten the thermocouple The thermopile operates the main valve ON and OFF Clean and or adjust pilot for maximum ame impingement on thermocouple and thermopile Tu...

Страница 26: ...on a at padded surface such as a coun ter protected by a towel 4 Remove the logset from the rebox 5 Remove the rear log bracket by unfastening the screw Fig 49 6 Remove the right and left log bracket...

Страница 27: ...spring and diaphragm assembly FC107 D E F FC108 SIT regulator conversion 10 03 OF F P I L O T O FC108 Fig 52 Replace regulator CO105a gas conversion Pilot 1 28 00 djt Pilot Hood Pilot Bracket CO105a...

Страница 28: ...he tubes inside burner Failure to do so could affect the ame appearance and performance of the unit 22 Place conversion label on valve 23 Reinstall the right and left log bracket assembly 24 Reinstall...

Страница 29: ...ature stove paints available through your local dealer to touch up areas as needed Clean areas to be painted with a wire brush and be sure to cover the logs burner and valve assembly glass and frame a...

Страница 30: ...g properly check the ames periodically to con rms they match Figure 61 The ames will be blue during the rst 15 20 minutes of operation and will gradually turn to yellow after that Do not use your stov...

Страница 31: ...t circuit NOTE IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE SF 2 200 WIRE OR ITS EQUIVALENT Thermocouple Safety Limit Switch Valve ST665 Sa...

Страница 32: ...e changes in design materials speci cations prices and discontinue colors and products at any time without notice Dutchwest Direct Vent Natural Vent Gas Heater Models 2465 2466 Ref Description Dutchwe...

Страница 33: ...T24 10001297 20 Nut Electrode SIT 0 974 144 57886 21 Tubing Pilot w Fittings 1 8 x 24 10001296 22 Burner Housing Assembly NG LP 20002214 23 Grate Burner JDV 20002167 24 Ashdoor Handle Assy E V WSI 500...

Страница 34: ...itself does not require regular maintenance however periodic cleaning of the fan and the surround ing area is required Installation Refer to Page 13 for installation instructions Remote Controls The r...

Страница 35: ...vel fees or service charges for in home repair work It is the dealers op tion whether the repair work will be done in the customer s home or in the dealer s shop If upon inspection the damage is found...

Страница 36: ...Ef ciency Ratings Model EnerGuide Ratings Fireplace Ef ciency 2465 63 0 2466 63 0 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: