H681x-5A Series Installation Guide

These products provide basic insulation to 600 Vac between the sensed conductor and the output leads. For reinforced 
applications, the installer must provide appropriate insulation. Reinforced insulation is provided for applications to 300 Vac 
between the sensed conductor and the output leads.

Ratings

4.   Close and latch the CT, and mount it securely. 

 

RISK OF INJURY OR EQUIPMENT DAMAGE/ RISQUE DE BLESSURE OU DE 
DÉTÉRIORATION DE L’ÉQUIPEMENT

•  Secure the I-bar to U-bar so that it remains in place. Close the CT with a suitable cable tie. / Fixer la barre 

  en I à la barre en U de sorte qu’elle reste fermement en place. Fermer le TC à l’aide d’un serre-câble 

 adapté.

Failure to follow these instructions may result in injury, fire or equipment damage. / 
Le non-respect de ces instructions peut entraîner un risque de blessure, d’incendie ou 
de détérioration de l’équipement.

WARNING/AVERTISSEMENT

 

Note: These CT devices have a detachable I-bar. If the I-bar is removed, re-orient it according to the markings on the core 

surface, then re-attach it. In any application where fault currents can exceed 20 times the rated current of the CT, use wire ties 

or similar fasteners to secure both sides of the I-bar to the CT housing. 

 

Note: The CTs except UL2808 require a single cable tie to secure the I-bar. Make sure to use the hole provided for cable tie. The 

UL2808 200 - 400 A and UL2808 600 - 800 A CTs require a double cable tie. The UL2808 1000 - 2400 A CTs have a push-pin to 

secure the I-bar and no cable tie is required.

5.   Reconnect power to the panel. 

Note:  An optional mounting kit is available for these devices (Veris part number AH06).

Installation (cont.)

Содержание H681-5A Series

Страница 1: ...nsducteurs de courant To reduce the risk of electric shock always open or disconnect circuit from power distribution system or service of building before installing of servicing current transformers Pour réduire le risque d électrocution toujours ouvrir ou déconnecter le circuit du système de distribution électrique ou du service du bâtiment avant toute installation ou intervention sur des transfo...

Страница 2: ... to 70 C 40 to 158 F Humidity Range 0 to 95 non condensing Altitude of Operation 3 km max Mounting Location Not suitable for wet locations For indoor use only WARRANTY Limited Warranty 5 years COMPLIANCE INFORMATION Agency Approvals UL61010 1 IEC 61010 1 EN 61010 1 Installation Category Category III Pollution Degree 2 INPUTS Frequency Range 50 60 Hz Leads 16 AWG 8 ft 2 4 m 20 ft 6 m ACCURACY Accur...

Страница 3: ...duct indicating source side H6810 Small UL2808 200 400Amp A 3 23 82 mm B 1 4 36 mm C 1 4 36 mm D 1 12 28 mm E 3 25 83 mm F 4 12 105 mm H6811 Medium UL2808 600 800Amp A 4 95 126 mm B 2 9 74 mm C 2 46 63 mm D 1 2 31 mm E 5 36 136 mm F 5 83 148 mm H6812 Large UL2808 1000 2400Amp A 4 91 125 mm B 5 73 146 mm C 2 47 63 mm D 1 16 30 mm E 8 12 206 mm F 4 91 125 mm B E F C D A A B E C F D A B E C F D Dimen...

Страница 4: ...he CT with a suitable cable tie Fixer la barre en I à la barre en U de sorte qu elle reste fermement en place Fermer leTC à l aide d un serre câble adapté Failure to follow these instructions may result in injury fire or equipment damage Le non respect de ces instructions peut entraîner un risque de blessure d incendie ou de détérioration de l équipement WARNING AVERTISSEMENT Note These CT devices...

Отзывы: