background image

Z201970-0M 

Page 3 of 4 

©2021 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0621 

 

12345 SW Leveton Drive, Tualatin OR  97062 USA

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

H681x-5A Series Installation Guide

Installation

 Installation must be performed by a qualified electrician.

 Disconnect and lock out power to the electrical panel.

1.   Connect the secondary leads to the burden or test switching/shorting bar. The white wire is the x1 lead.

2.   Depress the tabs on one end of the CT to open it. Check the core ends on both sections of the CT to ensure there is no rust or 

debris in the closure areas.

3.   Slip the CT over the primary leads. Note labeling on the product indicating “source side.”

H6810/Small UL2808

200-400 Amp

A = 3.23” (82 mm)
B = 1.4” (36 mm)
C = 1.4” (36 mm)
D = 1.12” (28 mm)
E = 3.25” (83 mm)
F = 4.12” (105 mm)

H6811/Medium UL2808 

600-800 Amp

A =  4.95” (126 mm)
B = 2.9” (74 mm)
C = 2.46” (63 mm)
D = 1.2” (31 mm)
E = 5.36” (136 mm)
F = 5.83” (148 mm)

H6812/Large UL2808

1000-2400 Amp

A = 4.91” (125 mm)
B = 5.73” (146 mm)
C = 2.47” (63 mm)
D = 1.16” (30 mm)
E = 8.12” (206 mm)
F = 4.91” (125 mm)

B

E

F

C

D

A

A

B

E

C

F

D

A

B

E

C

F

D

Dimensions

Split-Core

UL2808

A

B

E

F

C

D

B

E

F

C

D

A

A

B

E

C

F

D

H6810

SMALL

100 Amp

200 Amp

300 Amp

H6811

MEDIUM

400 Amp

600 Amp

800 Amp

H6812

LARGE

800 Amp

1600 Amp

2000 Amp

2400 Amp

A =   3.8"   (96 mm)

B =   1.5"   (38 mm)

C =   1.3"   (32 mm)

D =   1.1"   (29 mm)

E =   3.9"   (100 mm)

F =   4.8"   (121 mm)

A =   4.9"   (125 mm)

B =   2.9"   (73 mm)

C =   2.5"   (62 mm)

D =   1.1"   (29 mm)

E =   5.2"   (132 mm)

F =   5.9"   (151 mm)

A =   4.9"   (125 mm)

B =   5.5"   (139 mm)

C =   2.5"   (62 mm)

D =   1.1"   (29 mm)

E =   7.9"   (201 mm)

F =   5.9"   (151 mm)

H6810/Small

200-300 Amp

A =  3.8” (96 mm) 
B =  1.2” (31 mm)
C =  1.3” (32 mm)
D = 1.2” (31 mm)
E =  4.0" (100 mm)
F =  4.8" (121 mm)

H6811/Medium 

400-800 Amp

A = 4.9” (125 mm) 
B = 2.9” (73 mm)
C = 2.5” (62 mm)
D = 1.2" (31 mm)
E = 5.2” (132 mm)
F = 6.0" (152 mm)

H6812/Large  

800-2400 Amp

A = 4.9” (125 mm) 
B = 5.5” (139 mm)
C = 2.5” (62 mm)
D = 1.2” (31 mm)
E =  7.9" (201 mm)
F = 6.0" (152 mm)

Содержание H681-5A Series

Страница 1: ...nsducteurs de courant To reduce the risk of electric shock always open or disconnect circuit from power distribution system or service of building before installing of servicing current transformers Pour réduire le risque d électrocution toujours ouvrir ou déconnecter le circuit du système de distribution électrique ou du service du bâtiment avant toute installation ou intervention sur des transfo...

Страница 2: ... to 70 C 40 to 158 F Humidity Range 0 to 95 non condensing Altitude of Operation 3 km max Mounting Location Not suitable for wet locations For indoor use only WARRANTY Limited Warranty 5 years COMPLIANCE INFORMATION Agency Approvals UL61010 1 IEC 61010 1 EN 61010 1 Installation Category Category III Pollution Degree 2 INPUTS Frequency Range 50 60 Hz Leads 16 AWG 8 ft 2 4 m 20 ft 6 m ACCURACY Accur...

Страница 3: ...duct indicating source side H6810 Small UL2808 200 400Amp A 3 23 82 mm B 1 4 36 mm C 1 4 36 mm D 1 12 28 mm E 3 25 83 mm F 4 12 105 mm H6811 Medium UL2808 600 800Amp A 4 95 126 mm B 2 9 74 mm C 2 46 63 mm D 1 2 31 mm E 5 36 136 mm F 5 83 148 mm H6812 Large UL2808 1000 2400Amp A 4 91 125 mm B 5 73 146 mm C 2 47 63 mm D 1 16 30 mm E 8 12 206 mm F 4 91 125 mm B E F C D A A B E C F D A B E C F D Dimen...

Страница 4: ...he CT with a suitable cable tie Fixer la barre en I à la barre en U de sorte qu elle reste fermement en place Fermer leTC à l aide d un serre câble adapté Failure to follow these instructions may result in injury fire or equipment damage Le non respect de ces instructions peut entraîner un risque de blessure d incendie ou de détérioration de l équipement WARNING AVERTISSEMENT Note These CT devices...

Отзывы: