Transmitter PASCAL Ci4
Type series CI4xxx
LABOM Mess- und Regeltechnik GmbH Im Gewerbepark 13 27798 Hude Germany
SA_001_2019-07_10.00
Hotline: +49 4408 804-444 Fax: +49 4408 804-100 e-mail: [email protected] www.labom.com
Page 1/4
SIL Instructions
Safety-related parameters
Safety Integrity Level
SIL2
Operating Modes
Low and continuous demand mode
Achitecture
1oo1
Device Type
B
Hardware Fault Tolerance
HFT
0
Safe Failure Fraction
SFF
95,29 %
Failure rate for safe detected failures
SD
1,81∙10
-7
1/h
Failure rate for safe undetected fail-
ures
SU
3,11∙10
-7
1/h
Failure rate for dangerous detected
failures
DD
3,42∙10
-7
1/h
Failure rate for dangerous undetected
failures
DU
4,13∙10
-8
1/h
Probability of a dangerous undetect-
ed failure per hour
PFH
4,13∙10
-8
1/h
Mean time between failures =
Mean time to failure
MTBF
=
MTTF
130 a
Mean time to dangerous failure
MTTF
d
2764 a
Inspection Interval
T
1
1 year
2 years
3 years
5 years
Probability of a dangerous undetected
failure on demand
PFD
1,84∙10
-4
3,64∙10
-4
5,45∙10
-4
9,06∙10
-4
for MTTR = MRT = 8 h