Installation Guide
Temperature
TWS Series
TM
Temperature calibration allows for a calibration offset of ±9.9° (C or F) at the user’s discretion. To calibrate temperature, move the
RUN/CAL jumper to CAL position.
Calibration
Instructions
Menu Options
O U T P U T
0 - 1 0 V
T E M P S E T
+ 5 0
+ 9 5
C A L T
+ 0 . 0 F
6 8 . 5 º F
U N I T S
* º F º C
S E T P O I N T
7 0 F
S E T P O I N T
7 0 F
SETPOINT MODE
(Enter by any keypress when
RH Yes/No jumper is in Yes position)
NORMAL MODE
Output Scaling
(does not affect LCD display)
Only for switch in
Volts position
CONFIG/CAL MODE
(Enter by any keypress when
Run/Cal jumper is in CAL position)
Press +/- to change, press Select button to select
Press +/- to change, press Select button to select
Options are 50-95˚F (10-35˚C) or 32-122˚F (0-50˚C)
Press +/- to change, press Select button to select
Press +/- to change, press Select button to select
Setpoint in ˚C if Celsius units are selected
Press +/- to change, press Select button to select
Setpoint in ˚C if Celsius units are selected
Press +/- to change, press Select button to select
Setpoint in ˚C if Celsius units are selected
-
+
Display screen
Scroll down
Select
Scroll up