INSTALLATION GUIDE

MODBUS REGISTER ADDRESSING

This table lists the addressed assigned to each data point. Registers are read MostSignificant Byte (MSB) first. 32 bit floating point values are encoded per IEEE Standard 754. 
For floating point format variables, each data point appears twice because two 16-bit addresses are required to hold a 32-bit float value. The 16 bit Most Significant Word 
(MSW) is in the lower address of the register pair, while the least Significant Word (LSW) is in the upper address.

Modbus RTU function codes supported:  3=read holding registers;  6=preset single register; 17=report Slave I.D.

Quick Reference of the Most Common Data Points

Address

Typical 

Offset

Units

Description

Integer: 

 multiplier required

Float:  

upper 16 bits

Float: 

 lower 16 bits

40001

0

 KWH

 Energy Consumption, LSW

X

40002

1

 KWH

 Energy Consumption, MSW

X

40003

2

 KW

 Real Power

X

40257

 ---

 KWH

 Energy Consumption

X

40258

 KWH

 Energy Consumption

X

40259

0

 KWH

 Energy Consumption (same 40257)

X

40260

 KWH

 Energy Consumption (same 40258)

X

40261

2

 KW

 Real Power

X

40262

 KW

 Real Power

X

Complete Listing of Data Points

Address

Typical 

Offset

Units

Description

Integer: 

 multiplier required

Float:  

upper 16 bits

Float: 

 lower 16 bits

40001

0

 KWH

 Energy Consumption, LSW

X

40002

1

 KWH

 Energy Consumption, MSW

X

40003

2

 KW

 Real Power

X

40004

3

 VAR

 Reactive Power

X

40005

4

 VA

 Apparent Power

X

40006

5

 ---

 Power Factor

X

40007

6

 VOLTS

 Voltage, line to line

X

40008

7

 VOLTS

 Voltage, line to neutral

X

40009

8

 AMPS

 Current

X

40010

9

 KW

 Real Power, Phase A

X

40011

10

 KW

 Real Power, Phase B

X

40012

11

 KW

 Real Power, Phase C

X

40013

12

 ---

 Power Factor, phase A

X

40014

13

 ---

 Power Factor, phase B

X

40015

14

 ---

 Power Factor, phase C

X

40016

15

 VOLTS

 Voltage, phase A-B

X

40017

16

 VOLTS

 Voltage, phase B-C

X

40018

17

 VOLTS

 Voltage, phase A-C

X

40019

18

 VOLTS

 Voltage, phase A-N

X

40020

19

 VOLTS

 Voltage, phase B-N

X

40021

20

 VOLTS

 Voltage, phase C-N

X

40022

21

 AMPS

 Current, phase A

X

40023

22

 AMPS

 Current, phase B

X

40024

23

 AMPS

 Current, phase C

X

40025

24

 KW

 Average Real Power

X

40026

25

 KW

 Minimum Real Power

X

40027

26

 KW

 Maximum Real Power

X

40257

 ---

 KWH

 Energy Consumption

X

40258

 KWH

 Energy Consumption

X

40259

0

 KWH

 Energy Consumption (same 40257)

X

40260

 KWH

 Energy Consumption (same 40258)

X

40261

2

 KW

 Real Power

X

40262

 KW

 Real Power

X

Содержание ENERCEPT H8035

Страница 1: ...d conductors Failure to follow these instructions will result in death or serious injury DANGER NOTICE This product is not intended for life or safety applications Do not install this product in hazar...

Страница 2: ...C 2 5 62mm D 1 2 30mm E 7 9 201mm F 6 0 151mm SMALL 100 300Amp A 3 8 96mm B 1 2 30mm C 1 3 31mm D 1 2 30mm E 4 0 100mm F 4 8 121mm PRODUCT IDENTIFICATION ModbusEnhancedDataStreamPowerTransducers MODE...

Страница 3: ...the NEC Improper installation of Enercept meter in the wire gutter of equipment may affect the thermal performance of the equipment The arrangement of CTs within the equipment must also be considered...

Страница 4: ...terminating resistor between and 4 The Modbus cable should be shielded twisted pair wire BELDEN 1120A or similar WARNING After wiring remove all scraps of wire or foil shield from the electrical panel...

Страница 5: ...rksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM INSTALLATION GUIDE ADDRESS SELECTION SWITCHES Each Modbus device must have a unique address These switches must be set...

Страница 6: ...Energy Consumption X 40259 0 KWH Energy Consumption same 40257 X 40260 KWH Energy Consumption same 40258 X 40261 2 KW Real Power X 40262 KW Real Power X CompleteListingofDataPoints Address Typical Of...

Страница 7: ...8 VOLTS Voltage phase C N X 40299 40 AMPS Current phase A X 40300 AMPS Current phase A X 40301 42 AMPS Current phase B X 40302 AMPS Current phase B X 40303 44 AMPS Current phase C X 40304 AMPS Current...

Страница 8: ...The latter are indicated by single row values Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 7 81E 03 0 03125 0 0625 0 125 0 25 40002 kWh 512 2048 4096 8192 16384 40003 kW 0 004 0 016 0 032 0 06...

Страница 9: ...pact number Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 128 32 16 8 4 40002 kWh 1 9531E 3 4 8828E 4 2 4414E 4 1 2207E 4 6 1035E 5 40003 kW 250 62 5 31 25 15 625 7 8125 40004 VAR 250 62 5 31 25...

Страница 10: ...ver a power factor lower than 0 5 could cause the LED to blink this way even if the unit is installed properly It does not matter which side of the CT faces towards the load If current is below 7 of f...