H8035/H8036
Z201686-0K
PAGE 7
©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
10101
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
Address
Typical
Offset
Units
Description
Integer:
multiplier required
Float:
upper 16 bits
Float:
lower 16 bits
40263
4
VAR
Reactive Power
X
40264
VAR
Reactive Power
X
40265
6
VA
Apparent Power
X
40266
VA
Apparent Power
X
40267
8
---
Power Factor
X
40268
---
Power Factor
X
40269
10
VOLTS
Voltage, line to line
X
40270
VOLTS
Voltage, line to line
X
40271
12
VOLTS
Voltage, line to neutral
X
40272
VOLTS
Voltage, line to neutral
X
40273
14
AMPS
Current
X
40274
AMPS
Current
X
40275
16
KW
Real Power, phase A
X
40276
KW
Real Power, phase A
X
40277
18
KW
Real Power, phase B
X
40278
KW
Real Power, phase B
X
40279
20
KW
Real Power, phase C
X
40280
KW
Real Power, phase C
X
40281
22
---
Power Factor, phase A
X
40282
---
Power Factor, phase A
X
40283
24
---
Power Factor, phase B
X
40284
---
Power Factor, phase B
X
40285
26
---
Power Factor, phase C
X
40286
---
Power Factor, phase C
X
40287
28
VOLTS
Voltage, phase A-B
X
40288
VOLTS
Voltage, phase A-B
X
40289
30
VOLTS
Voltage, phase B-C
X
40290
VOLTS
Voltage, phase B-C
X
40291
32
VOLTS
Voltage, phase A-C
X
40292
VOLTS
Voltage, phase A-C
X
40293
34
VOLTS
Voltage, phase A-N
X
40294
VOLTS
Voltage, phase A-N
X
40295
36
VOLTS
Voltage, phase B-N
X
40296
VOLTS
Voltage, phase B-N
X
40297
38
VOLTS
Voltage, phase C-N
X
40298
VOLTS
Voltage, phase C-N
X
40299
40
AMPS
Current, phase A
X
40300
AMPS
Current, phase A
X
40301
42
AMPS
Current, phase B
X
40302
AMPS
Current, phase B
X
40303
44
AMPS
Current, phase C
X
40304
AMPS
Current, phase C
X
40305
46
KW
Average Real Power
X
40306
KW
Average Real Power
X
40307
48
KW
Minimum Real Power
X
40308
KW
Minimum Real Power
X
40309
50
KW
Maximum Real Power
X
40310
KW
Maximum Real Power
X
Note: Modbus addresses in the 4xxxx format follow the Modicon protocol specification for point addressing. The actual address sent is the value shown, minus 40001.
In other words, the leading “4” is omitted, and the remaining 4-digit number is decremented so that point 40001 is requested with a value of zero in the actual Modbus
communication. Some Modbus implementations require point addresses to be specified beginning at zero or 40000, instead of 40001. Programing code may also require
addresses which correspond to actual values transmitted, so a value of zero is used to request data beginning at Modbus address 40001.
In many applications, a single Modbus command is used to read all of the data available from the Enercept. For integers, the beginning address is 40001 (or zero in the actual
Modbus command), and for floats the first address used would typically be 40259 (or 258 in the actual Modbus command). Although the first float appears at address 40257,
it is not necessary to read this value because it is a duplicate copy of the kWh value (required by the product firmware). When a block of data is read, the “typical offset” values
index to the data within the block.
"Multiplier required" indicates that a multiplication is required to properly scale the integer value. See Using Integer Data Types section.