INSTALLATION GUIDE

Address

Typical 

Offset

Units

Description

Integer: 

 multiplier required

Float:  

upper 16 bits

Float: 

 lower 16 bits

40263

4

 VAR

 Reactive Power

X

40264

 VAR

 Reactive Power

X

40265

6

 VA

 Apparent Power

X

40266

 VA

 Apparent Power

X

40267

8

 ---

 Power Factor

X

40268

 ---

 Power Factor

X

40269

10

 VOLTS

 Voltage, line to line

X

40270

 VOLTS

 Voltage, line to line

X

40271

12

 VOLTS

 Voltage, line to neutral

X

40272

 VOLTS

 Voltage, line to neutral

X

40273

14

 AMPS

 Current

X

40274

 AMPS

 Current

X

40275

16

 KW

 Real Power, phase A

X

40276

 KW

 Real Power, phase A

X

40277

18

 KW

 Real Power, phase B

X

40278

 KW

 Real Power, phase B

X

40279

20

 KW

 Real Power, phase C

X

40280

 KW

 Real Power, phase C

X

40281

22

 ---

 Power Factor, phase A

X

40282

 ---

 Power Factor, phase A

X

40283

24

 ---

 Power Factor, phase B

X

40284

 ---

 Power Factor, phase B

X

40285

26

 ---

 Power Factor, phase C

X

40286

 ---

 Power Factor, phase C

X

40287

28

 VOLTS

 Voltage, phase A-B

X

40288

 VOLTS

 Voltage, phase A-B

X

40289

30

 VOLTS

 Voltage, phase B-C

X

40290

 VOLTS

 Voltage, phase B-C

X

40291

32

 VOLTS

 Voltage, phase A-C

X

40292

 VOLTS

 Voltage, phase A-C

X

40293

34

 VOLTS

 Voltage, phase A-N

X

40294

 VOLTS

 Voltage, phase A-N

X

40295

36

 VOLTS

 Voltage, phase B-N

X

40296

 VOLTS

 Voltage, phase B-N

X

40297

38

 VOLTS

 Voltage, phase C-N

X

40298

 VOLTS

 Voltage, phase C-N

X

40299

40

 AMPS

 Current, phase A

X

40300

 AMPS

 Current, phase A

X

40301

42

 AMPS

 Current, phase B

X

40302

 AMPS

 Current, phase B

X

40303

44

 AMPS

 Current, phase C

X

40304

 AMPS

 Current, phase C

X

40305

46

 KW

 Average Real Power

X

40306

 KW

 Average Real Power

X

40307

48

 KW

 Minimum Real Power

X

40308

 KW

 Minimum Real Power

X

40309

50

 KW

 Maximum Real Power

X

40310

 KW

 Maximum Real Power

X

Note: Modbus addresses in the 4xxxx format follow the Modicon protocol specification for point addressing. The actual address sent is the value shown, minus 40001. 
In other words, the leading “4” is omitted, and the remaining 4-digit number is decremented so that point 40001 is requested with a value of zero in the actual Modbus 
communication. Some Modbus implementations require point addresses to be specified beginning at zero or 40000, instead of 40001. Programing code may also require 
addresses which correspond to actual values transmitted, so a value of zero is used to request data beginning at Modbus address 40001.

In many applications, a single Modbus command is used to read all of the data available from the Enercept. For integers, the beginning address is 40001 (or zero in the actual 
Modbus command), and for floats the first address used would typically be 40259 (or 258 in the actual Modbus command). Although the first float appears at address 40257, 
it is not necessary to read this value because it is a duplicate copy of the kWh value (required by the product firmware). When a block of data is read, the “typical offset” values 
index to the data within the block.

"Multiplier required" indicates that a multiplication is required to properly scale the integer value. See Using Integer Data Types section.

Содержание ENERCEPT H8035

Страница 1: ...d conductors Failure to follow these instructions will result in death or serious injury DANGER NOTICE This product is not intended for life or safety applications Do not install this product in hazar...

Страница 2: ...C 2 5 62mm D 1 2 30mm E 7 9 201mm F 6 0 151mm SMALL 100 300Amp A 3 8 96mm B 1 2 30mm C 1 3 31mm D 1 2 30mm E 4 0 100mm F 4 8 121mm PRODUCT IDENTIFICATION ModbusEnhancedDataStreamPowerTransducers MODE...

Страница 3: ...the NEC Improper installation of Enercept meter in the wire gutter of equipment may affect the thermal performance of the equipment The arrangement of CTs within the equipment must also be considered...

Страница 4: ...terminating resistor between and 4 The Modbus cable should be shielded twisted pair wire BELDEN 1120A or similar WARNING After wiring remove all scraps of wire or foil shield from the electrical panel...

Страница 5: ...rksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM INSTALLATION GUIDE ADDRESS SELECTION SWITCHES Each Modbus device must have a unique address These switches must be set...

Страница 6: ...Energy Consumption X 40259 0 KWH Energy Consumption same 40257 X 40260 KWH Energy Consumption same 40258 X 40261 2 KW Real Power X 40262 KW Real Power X CompleteListingofDataPoints Address Typical Of...

Страница 7: ...8 VOLTS Voltage phase C N X 40299 40 AMPS Current phase A X 40300 AMPS Current phase A X 40301 42 AMPS Current phase B X 40302 AMPS Current phase B X 40303 44 AMPS Current phase C X 40304 AMPS Current...

Страница 8: ...The latter are indicated by single row values Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 7 81E 03 0 03125 0 0625 0 125 0 25 40002 kWh 512 2048 4096 8192 16384 40003 kW 0 004 0 016 0 032 0 06...

Страница 9: ...pact number Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 128 32 16 8 4 40002 kWh 1 9531E 3 4 8828E 4 2 4414E 4 1 2207E 4 6 1035E 5 40003 kW 250 62 5 31 25 15 625 7 8125 40004 VAR 250 62 5 31 25...

Страница 10: ...ver a power factor lower than 0 5 could cause the LED to blink this way even if the unit is installed properly It does not matter which side of the CT faces towards the load If current is below 7 of f...