manualshive.com logo in svg
background image

H8035/H8036

Z201686-0K 

PAGE 3 

©2010 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]  

10101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

TM

INSTALLATION GUIDE

OPERATION

The H8035 and H8036 three-phase power transducers monitor energy parameters 
from aggregate kW (real power) and kWh (consumption) to power factor per phase. 
Integration of electronics lowers hardware and installation costs. The sensors 
automatically detect phase reversal, so CT load orientation is not a concern. The CTs 
and electronics are calibrated as a set, so it is necessary to color-match the CTs and 
voltage leads when installing. These devices monitor up to 63 loads at a time on a 
single RS-485 drop.

With two platforms to choose from (H8035 Energy Only or H8036 Enhanced Data 
Stream), the applications for these devices are diverse, including aggregate billing, 
tenant monitoring, energy management, performance contracting, demand limiting 
and cooling plant optimization.

INSTALLATION

Disconnect and lock out power before installation.

The Enercept meter, including the current transformers (CTs), voltage connection 
fuses, and fusepac, is permitted within electrical distribution equipment including 
but not limited to panelboards, switchboards, motor control centers, and 
transformers. Carefully review the equipment in which the Enercept meter will be 
installed. The following installation conditions should be considered during the 
installation process:

• 

 Review the equipment enclosure for ventilation openings. Wires will cross 
many of these openings in a normal installation, however, do not install 
the Enercept where it will substantially block ventilation openings in the 
enclosure.

• 

 The Enercept meter and the wiring installed within a wiring space 
or gutter should not exceed 75 percent cross sectional fill at the 
Enercept meter parts as addressed in the NEC. Improper installation of 
Enercept meter in the wire gutter of equipment may affect the thermal 
performance of the equipment.   

• 

 The arrangement of CTs within the equipment must also be considered to 
ensure the bending radius of conductors is not adversely affected.

• 

 Review the arrangement and location of the CTs within the equipment. 
The CT must not create undue strain on the conductor. A CT may require 
appropriate support in order to address such a condition.

1.  Choose a unique address and set the switches for that address as 

shown in the Address Selection Switches section. Only addresses 1 
to 63 can be used.

2.  Connect the voltage leads to the phase conductors, at a location 

that is not normally turned off. Connect voltage leads on the Line 
side of the conductor to ensure constant power to the Enercept. For 
a 3-phase system, connect the red lead to phase A, black to phase 
B, and yellow to phase C. See the Wiring section on the following 
page.

3.  Snap the CT onto the conductor.  

Connect CTs  to the correspondingly 
colored voltage lead. If the 
application can exceed 20 times the 
rated CT current, use wire ties to 
secure the I-bar to the CT housing. 
This CT automatically detects phase 
reversal, so CT load orientation is not 
important.

4.  Remove the terminal block and attach the RS-485 wires. Observe (+), (-), and 

Shield polarity. Insulate any exposed wiring. 

SHIELD

SHIELD

S

S

SHIELD

120

Terminator

PRODUCT DIAGRAM

Fuse P

ack

Enercept

®

1

2

3

4

5

6

1.  

Voltage leads:

  Input range is 208 to 480V.

2.  

Fuses:

  Maximum current draw 60mA. Fuses provided by the factory are rated 

1/2A, 600VAC, 200 KAIC. Replace only with fuses of the same type and rating.

3.  

Modbus connector

4.  

Status LED:

  Blink codes: slow green for normal operation; slow red for incorrect 

wiring or low power factor (less than 0.5); fast red for maximum current 
exceedance.

5.  

Modbus address switches:

  Used to set the pulse output rate.

6.  

External CTs:

  Permanently attached; do not disconnect or use with other power 

transducers.

Color match CTs and voltage leads! Example:  clamp the 

red labeled CT around the power conductor connected to 

the red voltage wire.

Wire tie

RS-485

CONNECTION

STATUS

+

-

Shield

ADDRESS

1
2
4
8

16
32

 

 

 

 

 

 

Содержание ENERCEPT H8035

Страница 1: ...d conductors Failure to follow these instructions will result in death or serious injury DANGER NOTICE This product is not intended for life or safety applications Do not install this product in hazar...

Страница 2: ...C 2 5 62mm D 1 2 30mm E 7 9 201mm F 6 0 151mm SMALL 100 300Amp A 3 8 96mm B 1 2 30mm C 1 3 31mm D 1 2 30mm E 4 0 100mm F 4 8 121mm PRODUCT IDENTIFICATION ModbusEnhancedDataStreamPowerTransducers MODE...

Страница 3: ...the NEC Improper installation of Enercept meter in the wire gutter of equipment may affect the thermal performance of the equipment The arrangement of CTs within the equipment must also be considered...

Страница 4: ...terminating resistor between and 4 The Modbus cable should be shielded twisted pair wire BELDEN 1120A or similar WARNING After wiring remove all scraps of wire or foil shield from the electrical panel...

Страница 5: ...rksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM INSTALLATION GUIDE ADDRESS SELECTION SWITCHES Each Modbus device must have a unique address These switches must be set...

Страница 6: ...Energy Consumption X 40259 0 KWH Energy Consumption same 40257 X 40260 KWH Energy Consumption same 40258 X 40261 2 KW Real Power X 40262 KW Real Power X CompleteListingofDataPoints Address Typical Of...

Страница 7: ...8 VOLTS Voltage phase C N X 40299 40 AMPS Current phase A X 40300 AMPS Current phase A X 40301 42 AMPS Current phase B X 40302 AMPS Current phase B X 40303 44 AMPS Current phase C X 40304 AMPS Current...

Страница 8: ...The latter are indicated by single row values Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 7 81E 03 0 03125 0 0625 0 125 0 25 40002 kWh 512 2048 4096 8192 16384 40003 kW 0 004 0 016 0 032 0 06...

Страница 9: ...pact number Addr Units 100A 300 400A 800A 1600A 2400A 40001 kWh 128 32 16 8 4 40002 kWh 1 9531E 3 4 8828E 4 2 4414E 4 1 2207E 4 6 1035E 5 40003 kW 250 62 5 31 25 15 625 7 8125 40004 VAR 250 62 5 31 25...

Страница 10: ...ver a power factor lower than 0 5 could cause the LED to blink this way even if the unit is installed properly It does not matter which side of the CT faces towards the load If current is below 7 of f...

Отзывы: