H8035/H8036
Z201686-0K
PAGE 9
©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
10101
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
INSTALLATION GUIDE
As an alternative to the table on the previous page, it can be convenient to invert the values for use as divisors, where the
integer value returned by the Enercept is divided by a number from the table below. In most cases, the divisors are a more
compact number.
Addr
Units
100A
300/400A
800A
1600A
2400A
40001
kWh
128
32
16
8
4
40002
kWh
1.9531E-3
4.8828E-4
2.4414E-4
1.2207E-4
6.1035E-5
40003
kW
250
62.5
31.25
15.625
7.8125
40004
VAR
250
62.5
31.25
15.625
7.8125
40005
VA
250
62.5
31.25
15.625
7.8125
40006
---
32768
40007
VOLTS
32
40008
VOLTS
64
40009
AMPS
256
64
32
16
8
40010
kW
1000
250
125
62.5
31.25
40011
kW
1000
250
125
62.5
31.25
40012
kW
1000
250
125
62.5
31.25
40013
---
32768
40014
---
32768
40015
---
32768
40016
VOLTS
32
40017
VOLTS
32
40018
VOLTS
32
40019
VOLTS
64
40020
VOLTS
64
40021
VOLTS
64
40022
AMPS
256
64
32
16
8
40023
AMPS
256
64
32
16
8
40024
AMPS
256
64
32
16
8
40025
kW
250
62.5
31.25
15.625
7.8125
40026
kW
250
62.5
31.25
15.625
7.8125
40027
kW
250
62.5
31.25
15.625
7.8125