E51C2A, E51C3A Installation Guide

Supported System 
Types

The meter has a number of different possible system wiring configurations (see Wiring Diagrams section). To configure the meter, 
set the System Type via the User Interface or Modbus register 130  (if so equipped). The System Type tells the meter which of its 
current and voltage inputs are valid, which are to be ignored, and if neutral is connected. Setting the correct System Type prevents 
unwanted energy accumulation on unused inputs, selects the formula to calculate the Theoretical Maximum System Power, 
and determines which phase loss algorithm is to be used. The phase loss algorithm is configured as a percent of the Line-to-Line 
System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that  
have Neutral (12 & 40).

Values that are not valid in a particular System Type will display as “----” on the User Interface or as QNAN in the Modbus registers.

CTs

Voltage Connections

System Type

Phase Loss Measurements

Wiring 

Diagram

Number 

of wires

Qty

ID

Qty

ID

Type

Modbus 

Register 130

User Interface: 

SETUP>S SYS

VLL

VLN

Balance

Diagram 

number

Single-Phase Wiring
2

1

A

2

A, N

L-N

10

1L + 1n

AN

1

2

1

A

2

A, B

L-L

11

2L

AB

2

3

2

A, B

3

A, B, N

L-L with N 12

2L + 1n

AB

AN, BN

AN-BN

3

Three-Phase Wiring
3

3

A, B, C 3

A, B, C

Delta

31

3L

AB, BC, CA

AB-BC-CA

4

4

3

A, B, C 4

A, B, C, N Grounded 

Wye

40

3L + 1n

AB, BC, CA

AN, BN, CN AN-BN-CN & 

AB-BC-CA

5, 6

To avoid distortion, use parallel wires for control power and voltage inputs. 

The following symbols are used in the wiring diagrams on the following pages.

Symbol

Description

Voltage Disconnect Switch

Fuse (installer is responsible for ensuring compliance with local requirements. No 

fuses are included with the meter.)

Earth ground

X2

X1

Current Transducer

Potential Transformer

Protection containing a voltage disconnect switch with a fuse or disconnect circuit 

breaker. The protection device must be rated for the available short-circuit current at 

the connection point.

•  This product is designed only for use with E683 Series current transducers (CTs).

•  DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.

Failure to follow these instructions can result in equipment damage.

NOTICE

RISK OF EQUIPMENT DAMAGE

Wiring Symbols

Содержание E51C2A

Страница 1: ...instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not...

Страница 2: ...5 35mm DIN Rail per EN 50022 OPERATING CONDITIONS Operating Temperature Range 30 to 70 C 22 to 158 F Storage Temperature Range 40 to 85 C 40 to 185 F Humidity Range 95 RH non condensing Altitude of Op...

Страница 3: ...nsions 4 Application Example 4 Data Outputs 5 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Diagrams 9 Quick Setup Instructi...

Страница 4: ...L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners TM E51C2A E51C3A Installation Guide Dimensions 4 2 107mm 3 6 91mm 1 5 39mm 2 3 59mm 1 9...

Страница 5: ...g E51C3Aonly RealTime Clock user configurable 10 user configurable log buffers each buffer holds 5760 16 bit entries User configures which 10 data points are stored in these buffers User configurable...

Страница 6: ...o ways on standard 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots...

Страница 7: ...re not valid in a particular System Type will display as on the User Interface or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wi...

Страница 8: ...re3CTnoPT UseSystemType11 2L UseSystemType12 2L 1n UseSystemType 31 3L UseSystemType10 1L 1n Wiring RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE CT terminals are referenced to the meter s neut...

Страница 9: ...NorL L Outputto meetmeterinputrequirements DCControlPowerfrom125Vdcto300Vdc ULandCEmax FuseRecommendations Keep the fuses close to the power source obey local and national code requirements For select...

Страница 10: ...screen Use the or buttons to select the parity d back to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the first screen a to the...

Страница 11: ...be rated for the short circuit current at the connection point All pulse outputs and communication circuits are only intended to be connected to non hazardous circuits SELV or Class 2 Do not connect...

Страница 12: ...Apparent Power S Export Demand Maximum Reactive Power Q Export Demand Maximum Real Power P Export Demand DKVAR Present Reactive Power Demand Q D KVA Present Apparent Power Demand S DEMND Demand Scroll...

Страница 13: ...Reactive Power Q Export Demand Maximum Real Power Export Demand D KQ Present Reactive Power Demand D KS Present Apparent Power Demand DEMND Demand Scroll When Idle Total Import Real Energy A KPh 3 KP...

Страница 14: ...Voltage Out of Range A B C A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Numbe...

Страница 15: ...Type Current Transformer S SYS Next S CT CT SZ 100 SYSTM 3L 1n 3L 2L 1n 2L 1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transfo...

Страница 16: ...n the ALARM PULSE screen and enable Energy pulse output configuration error bit in the Modbus Diagnostic Alert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse Whe...

Страница 17: ...l setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 Use register 159 to turn on data logging and select either Single Shot or Continuous...

Страница 18: ...able CTs and PTs allowing a much wider range of operation from 90V x 5A up to 32000V x 5000A To promote this the meter permits variable scaling of the 16 bit integer registers via the scale registers...

Страница 19: ...ly a fraction to be read correctly This is done to allow integer numbers to represent fractional numbers Range Defines the limit of the values that a register can contain Standard Modbus Default Setti...

Страница 20: ...t and Export correspond with Real Energy 016 LSR 017 R NV ULong kVAh E 0 to 0xFFFFFFFF Apparent Quadrants 1 4 Import MSR 018 LSR 019 R NV ULong kVAh E 0 to 0xFFFFFFFF Apparent Quadrants 2 3 Export MSR...

Страница 21: ...Real Energy Phase C MSR 054 LSR 055 R NV ULong kVARh E 0 to 0xFFFFFFFF Accumulated Q1 Reactive Energy Phase A MSR Import Accumulated Reactive Energy Qh Per Phase 056 LSR 057 R NV ULong kVARh E 0 to 0x...

Страница 22: ...2767 Real Power P Phase A Real Power P 092 R SInt kW W 32767 to 32767 Real Power P Phase B 093 R SInt kW W 32767 to 32767 Real Power P Phase C 094 R SInt kVAR W 32767 to 32767 Reactive Power Q Phase A...

Страница 23: ...e entering 200 yields a potential transformer ratio of 2 1 The default is 100 1 00 1 which is with no PT attached Set this value before setting the system voltage below 134 R W NV UInt 82 32000 Syste...

Страница 24: ...ergy per Pulse Output Contact Closure If the meter cannot find a pulse duration that will keep up with the max system power register 135 it will reject the new value Check the meter configuration and...

Страница 25: ...rved returns 0 Logging Configuration and Status 155 R W NV UInt Day Month See Bytes Most Significant Byte MSB Least Significant Byte LSB Date Time Clock Following a power cycle resets to Day 01 Month...

Страница 26: ...reset during the previous demand sub interval Bit 4 Logging Interrupted Logging has been interrupted power cycled log configuration change etc during the previous demand sub interval Bit 5 RTC Change...

Страница 27: ...77 R W NV UInt Log Register 9 Default is 156 Year Hour 178 R W NV UInt Log Register 10 Default is 157 Minutes Seconds Floating Point Data Summary of Active Phases 257 258 R NV Float kWh Accumulated Re...

Страница 28: ...user defined 315 316 R Float 1 0 4294967040 Pulse Counter 2 Export Reactive Energy Floating Point Data Per Phase 317 318 R Float kWh Accumulated Real Energy Phase A Import Accumulated Real Energy Ph...

Страница 29: ...nt Power Phase A 381 382 R Float kVA Apparent Power Phase A 383 384 R Float Ratio 0 0 1 0 Power Factor Phase A Power Factor PF 385 386 R Float Ratio 0 0 1 0 Power Factor Phase A 387 388 R Float Ratio...

Страница 30: ...device IDs Meter configuration by device ID 201 single phase A N or A B meter 202 split single phase A B N meter 203 Wye connect 3 phase ABCN meter 204 delta connect 3 phase ABC meter 40071 R NV UInt...

Страница 31: ...R M_AC_VAR_SF 32767 to 32767 M_AC_VAR_A Phase A AC Reactive Power 40100 R SInt VAR M_AC_VAR_SF 32767 to 32767 M_AC_VAR_B Phase B AC Reactive Power 40101 R SInt VAR M_AC_VAR_SF 32767 to 32767 M_AC_VAR_...

Страница 32: ...x0 to 0xFFFFFFFF M_Import_VARh_Q1 Quadrant 1 Total Imported Reactive Energy 40143 40144 R NV ULong VAR hours M_Energy_VAR_SF 0x0 to 0xFFFFFFFF M_Import_VARh_ Q1A Phase A Quadrant 1 Total Imported Reac...

Страница 33: ...Total Exported Reactive Energy 40173 40174 R NV UInt SF 1 M_Energy_VA_SF Reactive Energy Scale Factor Events 40175 R NV ULong Flags M_Events Bit Map See M_EVENT_flags 0 no event 40176 Event Bit Descr...

Страница 34: ...powering See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer Power meter address is incorrect Verify that the meter is correctly ad...

Отзывы: