E51C2A, E51C3A Installation Guide

E51C2A FDS

E51C3A L

og

Regist

er

R/W NV Format Units Scale

Range

Description

• 142

R/W NV UInt

%

1-99

Phase Loss Voltage Threshold in percent of system voltage (register 

134). Default value is 10 (%). Any phase (as configured in register 

130) whose level drops below this threshold triggers a Phase Loss 

alert, i.e., if the System voltage is set to 480 V L-L, the L-N voltage 

for each phase should be 277 V. When the threshold is set to 10%, 

if any phase drops more than 10% below 277 V, (less than 249 V), 

or if any L-L voltage drops more than 10% below 480 V (less than 

432 V) the corresponding phase loss alarm bit in register 146 will 

be true.

Phase Loss Output

Note: The phases tested are determined 

by the System Type.

• 143

R/W NV UInt

%

1-99

Phase Loss Imbalance Threshold in Percent. Default is 25% phase 

to phase difference. For a 3-phase Y (3 + N) system type (40 in 

register 130), both Line to Neutral and Line to Line voltages are 

tested. In a 3-phase Δ System type (31 in register 130), only Line 

to Line voltages are examined. In a single split-phase (2 + N) 

system type (12 in register 130), just the line to neutral voltage 

are compared.

• 144

R/W NV UInt

Wh

10000, 

1000

100, 
10

Wh (& VARh, if equipped) 

Energy per Pulse Output 

Contact Closure. If the meter 

cannot find a pulse duration 

that will keep up with the 

max. system power (register 

135), it will reject the new 

value. Check the meter 

configuration and/or try a 

larger value.

kWh (& VARh, if equipped) Pulse Contacts

Note: The kWh pulse contact can keep up with a maximum power (Watts) of 

1800000 x Wh pulse weight ÷ contact closure duration (in msec)

• 145

R

NV UInt

msec

500, 
250, 
100, 
50, 
25, 
10

Pulse Contact Closure Duration 

in msec. Read-only. Set to 

the slowest duration that will 

keep up with the theoretical 

max. system power (register 

135). The open time ≥ the 

closure time, so the max. 

pulse rate (pulses per sec) 

is the inverse of double the 

pulse time.

• 146

R

UInt

Error Bitmap. 1 = Active:
Bit 0:   Phase A Voltage out of range
Bit 1:   Phase B Voltage out of range
Bit 2:   Phase C Voltage out of range
Bit 3:   Phase A Current out of range
Bit 4:   Phase B Current out of range
Bit 5:   Phase C Current out of range
Bit 6:   Frequency out of the range of 45 to 65 Hz -OR- insufficient voltage to determine frequency.
Bit 7:   Reserved for future use 
Bit 8:   Phase Loss A
Bit 9:   Phase Loss B 
Bit 10: Phase Loss C 
Bit 11:  Low Power Factor on A with one or more phases having a PF less than 0.5 due to mis-wiring of phases
Bit 12:  Low Power Factor on B
Bit 13:  Low Power Factor on C
Bit 14:   Energy pulse output overrun error. The pulse outputs are unable to keep up with the total real power 

(registers 3 and 261/262). To fix, increase the pulse energy register (register 144) and reset the energy 

accumulators (see reset register 129).

Bit 15:  Energy pulse output configuration error (present pulse energy setting may not keep up with the 

theoretical max. system power; see register 135). To fix, increase the pulse energy (register 144).

Modbus Point Map (cont.)

Содержание E51C2A

Страница 1: ...instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not...

Страница 2: ...5 35mm DIN Rail per EN 50022 OPERATING CONDITIONS Operating Temperature Range 30 to 70 C 22 to 158 F Storage Temperature Range 40 to 85 C 40 to 185 F Humidity Range 95 RH non condensing Altitude of Op...

Страница 3: ...nsions 4 Application Example 4 Data Outputs 5 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Diagrams 9 Quick Setup Instructi...

Страница 4: ...L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners TM E51C2A E51C3A Installation Guide Dimensions 4 2 107mm 3 6 91mm 1 5 39mm 2 3 59mm 1 9...

Страница 5: ...g E51C3Aonly RealTime Clock user configurable 10 user configurable log buffers each buffer holds 5760 16 bit entries User configures which 10 data points are stored in these buffers User configurable...

Страница 6: ...o ways on standard 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots...

Страница 7: ...re not valid in a particular System Type will display as on the User Interface or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wi...

Страница 8: ...re3CTnoPT UseSystemType11 2L UseSystemType12 2L 1n UseSystemType 31 3L UseSystemType10 1L 1n Wiring RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE CT terminals are referenced to the meter s neut...

Страница 9: ...NorL L Outputto meetmeterinputrequirements DCControlPowerfrom125Vdcto300Vdc ULandCEmax FuseRecommendations Keep the fuses close to the power source obey local and national code requirements For select...

Страница 10: ...screen Use the or buttons to select the parity d back to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the first screen a to the...

Страница 11: ...be rated for the short circuit current at the connection point All pulse outputs and communication circuits are only intended to be connected to non hazardous circuits SELV or Class 2 Do not connect...

Страница 12: ...Apparent Power S Export Demand Maximum Reactive Power Q Export Demand Maximum Real Power P Export Demand DKVAR Present Reactive Power Demand Q D KVA Present Apparent Power Demand S DEMND Demand Scroll...

Страница 13: ...Reactive Power Q Export Demand Maximum Real Power Export Demand D KQ Present Reactive Power Demand D KS Present Apparent Power Demand DEMND Demand Scroll When Idle Total Import Real Energy A KPh 3 KP...

Страница 14: ...Voltage Out of Range A B C A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Numbe...

Страница 15: ...Type Current Transformer S SYS Next S CT CT SZ 100 SYSTM 3L 1n 3L 2L 1n 2L 1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transfo...

Страница 16: ...n the ALARM PULSE screen and enable Energy pulse output configuration error bit in the Modbus Diagnostic Alert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse Whe...

Страница 17: ...l setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 Use register 159 to turn on data logging and select either Single Shot or Continuous...

Страница 18: ...able CTs and PTs allowing a much wider range of operation from 90V x 5A up to 32000V x 5000A To promote this the meter permits variable scaling of the 16 bit integer registers via the scale registers...

Страница 19: ...ly a fraction to be read correctly This is done to allow integer numbers to represent fractional numbers Range Defines the limit of the values that a register can contain Standard Modbus Default Setti...

Страница 20: ...t and Export correspond with Real Energy 016 LSR 017 R NV ULong kVAh E 0 to 0xFFFFFFFF Apparent Quadrants 1 4 Import MSR 018 LSR 019 R NV ULong kVAh E 0 to 0xFFFFFFFF Apparent Quadrants 2 3 Export MSR...

Страница 21: ...Real Energy Phase C MSR 054 LSR 055 R NV ULong kVARh E 0 to 0xFFFFFFFF Accumulated Q1 Reactive Energy Phase A MSR Import Accumulated Reactive Energy Qh Per Phase 056 LSR 057 R NV ULong kVARh E 0 to 0x...

Страница 22: ...2767 Real Power P Phase A Real Power P 092 R SInt kW W 32767 to 32767 Real Power P Phase B 093 R SInt kW W 32767 to 32767 Real Power P Phase C 094 R SInt kVAR W 32767 to 32767 Reactive Power Q Phase A...

Страница 23: ...e entering 200 yields a potential transformer ratio of 2 1 The default is 100 1 00 1 which is with no PT attached Set this value before setting the system voltage below 134 R W NV UInt 82 32000 Syste...

Страница 24: ...ergy per Pulse Output Contact Closure If the meter cannot find a pulse duration that will keep up with the max system power register 135 it will reject the new value Check the meter configuration and...

Страница 25: ...rved returns 0 Logging Configuration and Status 155 R W NV UInt Day Month See Bytes Most Significant Byte MSB Least Significant Byte LSB Date Time Clock Following a power cycle resets to Day 01 Month...

Страница 26: ...reset during the previous demand sub interval Bit 4 Logging Interrupted Logging has been interrupted power cycled log configuration change etc during the previous demand sub interval Bit 5 RTC Change...

Страница 27: ...77 R W NV UInt Log Register 9 Default is 156 Year Hour 178 R W NV UInt Log Register 10 Default is 157 Minutes Seconds Floating Point Data Summary of Active Phases 257 258 R NV Float kWh Accumulated Re...

Страница 28: ...user defined 315 316 R Float 1 0 4294967040 Pulse Counter 2 Export Reactive Energy Floating Point Data Per Phase 317 318 R Float kWh Accumulated Real Energy Phase A Import Accumulated Real Energy Ph...

Страница 29: ...nt Power Phase A 381 382 R Float kVA Apparent Power Phase A 383 384 R Float Ratio 0 0 1 0 Power Factor Phase A Power Factor PF 385 386 R Float Ratio 0 0 1 0 Power Factor Phase A 387 388 R Float Ratio...

Страница 30: ...device IDs Meter configuration by device ID 201 single phase A N or A B meter 202 split single phase A B N meter 203 Wye connect 3 phase ABCN meter 204 delta connect 3 phase ABC meter 40071 R NV UInt...

Страница 31: ...R M_AC_VAR_SF 32767 to 32767 M_AC_VAR_A Phase A AC Reactive Power 40100 R SInt VAR M_AC_VAR_SF 32767 to 32767 M_AC_VAR_B Phase B AC Reactive Power 40101 R SInt VAR M_AC_VAR_SF 32767 to 32767 M_AC_VAR_...

Страница 32: ...x0 to 0xFFFFFFFF M_Import_VARh_Q1 Quadrant 1 Total Imported Reactive Energy 40143 40144 R NV ULong VAR hours M_Energy_VAR_SF 0x0 to 0xFFFFFFFF M_Import_VARh_ Q1A Phase A Quadrant 1 Total Imported Reac...

Страница 33: ...Total Exported Reactive Energy 40173 40174 R NV UInt SF 1 M_Energy_VA_SF Reactive Energy Scale Factor Events 40175 R NV ULong Flags M_Events Bit Map See M_EVENT_flags 0 no event 40176 Event Bit Descr...

Страница 34: ...powering See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer Power meter address is incorrect Verify that the meter is correctly ad...

Отзывы: