E51C2A, E51C3A Installation Guide

Read/Write Collision

If the demand sub-interval timeout occurs while the user is reading a page (register 158 ≠ 0), the log data will be held in RAM 
until the next demand subinterval. At that time, both the saved data from the previous cycle and the new data will be written to 
the log, whether the page register has been set back to 0 or not. Error bits in the Log Status Register (160) track these conditions. 
Subsequent log writes will proceed normally. Provided the log read is concluded in less time than the demand sub-interval, this 
mechanism handles the occasional collision and prevents the user from reading data as the buffer is being updated.

The Log Status Register has additional error flag bits that indicate whether logging has been reset or interrupted (power cycle, 
etc.) during the previous demand sub-interval, and whether the Real-Time Clock has been changed (re-initialized to default date/
time due to a power-cycle or modified via Modbus commands).

The E51C2A Full Data Set (FDS) model features data outputs such as demand calculations, per phase signed watts VA and VAR, 
import/export Wh and VAh, and VARh accumulators by quadrant. The E51C3A Data Logging model includes the FDS and adds log 
configuration registers 155-178 and log buffer reading at registers 8000-13760. The meter supports variable CTs and PTs, allowing 
a much wider range of operation from 90V x 5A up to 32000V x 5000A. To promote this, the meter permits variable scaling of the 
16-bit integer registers via the scale registers. The 32-bit floating point registers do not need to be scaled.

Integer registers begin at 001 (0x001). Floats at 257 (0x101). Configuration registers at 129 (0x081). Values not supported in a 
particular System Type configuration report QNAN (0x8000 in Integer Registers, 0x7FC00000 in Floating Point Registers). Register 
addresses are in PLC style base 1 notation. Subtract 1 from all addresses for the base 0 value used on the Modbus RS-485 link.

Supported Modbus Commands

Note:  ID String information varies from model to model. Text shown here is an example.

Command

Description

0x03

Read Holding Registers

0x04

Read Input Registers

0x06

Preset Single Register

0x10

Preset Multiple Registers

0x11

Report ID
Return string:
byte0:   address
byte1:   0x11
byte2:   #bytes following w/out crc
byte3:   ID byte = 247
byte4:   status = 0xFF if the operating system is used; status = 0x00 if the reset system is used
: ID string = “Veris Industries E51xxA Power Meter Full Data Set”  or “Veris Industries E51xxA Power Meter - RESET 

SYSTEM RUNNING RS Version x.xxx” last 2 bytes: CRC

0x2B

Read Device Identification, BASIC implementation (0x00, 0x01 and 0x02 data), Conformity Level 1.
Object values:
0x01: “Veris Industries”
0x02: “ E51xxA”
0x03: “Vxx.yyy”, where xx.yyy is the OS version number (reformatted version of the Modbus register #7001, (Firmware 

Version, Operating System).  

If register #7001 == 12345, then the 0x03 data would be “V12.345”).

Legend

The following table lists the addresses assigned to each data point. For floating point format variables, each data point appears 
twice because two 16-bit addresses are required to hold a 32-bit float value. Negative signed integers are 2’s complement.

Modbus Point Map 
Overview

Data Logging  
(E51C3 only), cont.

Содержание E51C2A

Страница 1: ...instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not...

Страница 2: ...5 35mm DIN Rail per EN 50022 OPERATING CONDITIONS Operating Temperature Range 30 to 70 C 22 to 158 F Storage Temperature Range 40 to 85 C 40 to 185 F Humidity Range 95 RH non condensing Altitude of Op...

Страница 3: ...nsions 4 Application Example 4 Data Outputs 5 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Diagrams 9 Quick Setup Instructi...

Страница 4: ...L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners TM E51C2A E51C3A Installation Guide Dimensions 4 2 107mm 3 6 91mm 1 5 39mm 2 3 59mm 1 9...

Страница 5: ...g E51C3Aonly RealTime Clock user configurable 10 user configurable log buffers each buffer holds 5760 16 bit entries User configures which 10 data points are stored in these buffers User configurable...

Страница 6: ...o ways on standard 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots...

Страница 7: ...re not valid in a particular System Type will display as on the User Interface or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wi...

Страница 8: ...re3CTnoPT UseSystemType11 2L UseSystemType12 2L 1n UseSystemType 31 3L UseSystemType10 1L 1n Wiring RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE CT terminals are referenced to the meter s neut...

Страница 9: ...NorL L Outputto meetmeterinputrequirements DCControlPowerfrom125Vdcto300Vdc ULandCEmax FuseRecommendations Keep the fuses close to the power source obey local and national code requirements For select...

Страница 10: ...screen Use the or buttons to select the parity d back to the S COM screen 6 to the S CT Set Current Transducer screen If this unit does not have an RS 485 port this will be the first screen a to the...

Страница 11: ...be rated for the short circuit current at the connection point All pulse outputs and communication circuits are only intended to be connected to non hazardous circuits SELV or Class 2 Do not connect...

Страница 12: ...Apparent Power S Export Demand Maximum Reactive Power Q Export Demand Maximum Real Power P Export Demand DKVAR Present Reactive Power Demand Q D KVA Present Apparent Power Demand S DEMND Demand Scroll...

Страница 13: ...Reactive Power Q Export Demand Maximum Real Power Export Demand D KQ Present Reactive Power Demand D KS Present Apparent Power Demand DEMND Demand Scroll When Idle Total Import Real Energy A KPh 3 KP...

Страница 14: ...Voltage Out of Range A B C A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR A b C PASWD 00000 PASWD 00000 Model Numbe...

Страница 15: ...Type Current Transformer S SYS Next S CT CT SZ 100 SYSTM 3L 1n 3L 2L 1n 2L 1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transfo...

Страница 16: ...n the ALARM PULSE screen and enable Energy pulse output configuration error bit in the Modbus Diagnostic Alert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse Whe...

Страница 17: ...l setting the buffers hold 60 days of data An external timer can be used over Modbus by setting this register to 0 Use register 159 to turn on data logging and select either Single Shot or Continuous...

Страница 18: ...able CTs and PTs allowing a much wider range of operation from 90V x 5A up to 32000V x 5000A To promote this the meter permits variable scaling of the 16 bit integer registers via the scale registers...

Страница 19: ...ly a fraction to be read correctly This is done to allow integer numbers to represent fractional numbers Range Defines the limit of the values that a register can contain Standard Modbus Default Setti...

Страница 20: ...t and Export correspond with Real Energy 016 LSR 017 R NV ULong kVAh E 0 to 0xFFFFFFFF Apparent Quadrants 1 4 Import MSR 018 LSR 019 R NV ULong kVAh E 0 to 0xFFFFFFFF Apparent Quadrants 2 3 Export MSR...

Страница 21: ...Real Energy Phase C MSR 054 LSR 055 R NV ULong kVARh E 0 to 0xFFFFFFFF Accumulated Q1 Reactive Energy Phase A MSR Import Accumulated Reactive Energy Qh Per Phase 056 LSR 057 R NV ULong kVARh E 0 to 0x...

Страница 22: ...2767 Real Power P Phase A Real Power P 092 R SInt kW W 32767 to 32767 Real Power P Phase B 093 R SInt kW W 32767 to 32767 Real Power P Phase C 094 R SInt kVAR W 32767 to 32767 Reactive Power Q Phase A...

Страница 23: ...e entering 200 yields a potential transformer ratio of 2 1 The default is 100 1 00 1 which is with no PT attached Set this value before setting the system voltage below 134 R W NV UInt 82 32000 Syste...

Страница 24: ...ergy per Pulse Output Contact Closure If the meter cannot find a pulse duration that will keep up with the max system power register 135 it will reject the new value Check the meter configuration and...

Страница 25: ...rved returns 0 Logging Configuration and Status 155 R W NV UInt Day Month See Bytes Most Significant Byte MSB Least Significant Byte LSB Date Time Clock Following a power cycle resets to Day 01 Month...

Страница 26: ...reset during the previous demand sub interval Bit 4 Logging Interrupted Logging has been interrupted power cycled log configuration change etc during the previous demand sub interval Bit 5 RTC Change...

Страница 27: ...77 R W NV UInt Log Register 9 Default is 156 Year Hour 178 R W NV UInt Log Register 10 Default is 157 Minutes Seconds Floating Point Data Summary of Active Phases 257 258 R NV Float kWh Accumulated Re...

Страница 28: ...user defined 315 316 R Float 1 0 4294967040 Pulse Counter 2 Export Reactive Energy Floating Point Data Per Phase 317 318 R Float kWh Accumulated Real Energy Phase A Import Accumulated Real Energy Ph...

Страница 29: ...nt Power Phase A 381 382 R Float kVA Apparent Power Phase A 383 384 R Float Ratio 0 0 1 0 Power Factor Phase A Power Factor PF 385 386 R Float Ratio 0 0 1 0 Power Factor Phase A 387 388 R Float Ratio...

Страница 30: ...device IDs Meter configuration by device ID 201 single phase A N or A B meter 202 split single phase A B N meter 203 Wye connect 3 phase ABCN meter 204 delta connect 3 phase ABC meter 40071 R NV UInt...

Страница 31: ...R M_AC_VAR_SF 32767 to 32767 M_AC_VAR_A Phase A AC Reactive Power 40100 R SInt VAR M_AC_VAR_SF 32767 to 32767 M_AC_VAR_B Phase B AC Reactive Power 40101 R SInt VAR M_AC_VAR_SF 32767 to 32767 M_AC_VAR_...

Страница 32: ...x0 to 0xFFFFFFFF M_Import_VARh_Q1 Quadrant 1 Total Imported Reactive Energy 40143 40144 R NV ULong VAR hours M_Energy_VAR_SF 0x0 to 0xFFFFFFFF M_Import_VARh_ Q1A Phase A Quadrant 1 Total Imported Reac...

Страница 33: ...Total Exported Reactive Energy 40173 40174 R NV UInt SF 1 M_Energy_VA_SF Reactive Energy Scale Factor Events 40175 R NV ULong Flags M_Events Bit Map See M_EVENT_flags 0 no event 40176 Event Bit Descr...

Страница 34: ...powering See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer Power meter address is incorrect Verify that the meter is correctly ad...

Отзывы: