background image

PIBV2A Post Indicator and 

Butterfly Valve Supervisory Switch

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Important

Please Read Carefully and Save

This instruction manual contains important information on the 

installation and operation of supervisory switches. Purchasers 

who install supervisory switches for use by others must leave 

this manual or a copy of it with the user. These instructions 

apply to Safe Signal switches for post indicator and butterfly 

type valves. Read all instructions carefully before beginning 

installation.

CAUTION

Do NOT use this switch in explosive or potentially explosive 

atmospheres. Do NOT leave unused wires exposed.

All supervisory switch installations must comply with local 

codes and ordinances and the requirements of the author-

ity having jurisdiction. Additional information is avail-

able in National Fire Protection Association standards NFPA 

13, 13D, 13R, 71, and 72. The connection of supervisory 

switches to alarm control units is governed by CAN/ULC-

S524-M91, standard for the Installation of Fire Alarm Systems. 

General  Installation Considerations

1.  Model PIBV2A is designed for installation in a 

1

2

˝ NPT 

tapped hole and located so that the actuating lever of the 

switch engages the target or flag of the valve . The switch 

actuating lever is spring loaded against the flag or target of the 

valve  and is released when the valve moves toward the closed 

position from the fully open position. The switch is factory set 

to indicate an alarm condition when the target and lever move 

in the direction toward the conduit entry hole when the valve 

closes, but can be reversed if the installation demands (refer 

to Section 4).

Specifications

Contact Ratings:               

10A @ 125/250 VAC

 

2.5 A @ 24 VDC

Cover Tamper Switch Ratings: 

5 A @ 125/250 VAC; 2.5 A @ 24 VDC

Dimensions: 8

1

4

˝ H X 3

1

2

˝ W X 3

1

4

˝ D

Maximum Stem Extension:        

3

5

32

˝

Operating Temperature Range:   

0°C - 49°C (32°F - 120°F)

Shipping 

Weight 

lbs. 

         

Enclosure Rating:               

NEMA Type 3R when mounted with the actuator vertical (cover on top) as tested by 

 

Underwriters Laboratories, Inc. (PIBV2A is ULC approved)

W0224-00

Figure 1:

COVER

TAMPER

SCREWS

TAMPER

PROOF

WRENCH

(P/N WFDW)

ACTUATING

CAM

ACTUATING

LEVER SCREW

NIPPLE SET SCREW

THREADED

NIPPLE

BASE HOUSING

ACTUATING

LEVER

RETAINING NUT

SWITCH ENCLOSURE

MOUNTING SCREWS

SPRING

HEX

WRENCH

(P/N HEXW)

4

1

/

4

˝ H

(ASSEMBLED)

3

1

/

4

˝ D

3

1

/

2

˝ W

2.  Model PIBV2A is equipped with a removable 

1

2

˝ NPT pipe 

nipple which is locked in place with two set screws.  A hex 

wrench is provided for this feature. The PIBV2 also includes 

an adjustable length actuating lever.

3.  The cover is secured with two tamper resistant screws which 

require a special key to remove. One key is included with 

each supervisory switch. Replacement and additional keys are 

available (Part No. WFDW).

I56-2481-C

  

I56-2481-C 

 

 4/21

Summary of Contents for PIBV2A

Page 1: ... loaded against the flag or target of the valve and is released when the valve moves toward the closed position from the fully open position The switch is factory set to indicate an alarm condition when the target and lever move in the direction toward the conduit entry hole when the valve closes but can be reversed if the installation demands refer to Section 4 Specifications Contact Ratings 10A ...

Page 2: ...ng lever of the PIBV2A from the end of the enclosure to this distance Tighten the screw which holds the actuating lever NOTE Place cover over PIBV2 to ensure that actuating lever does not interfere with cover If actuating lever interferes with cover remove lever and break off additional length at break away point Repeat step 8 to re install actuator lever Refer to Figure 7 9 Close the valve 3 to 4...

Page 3: ...itions Figure 4 The following are examples of acceptable mounting positions Actuator Vertical Down Actuator Horizontal T O O P E N CLOSE CLOSE Figure 3 CONDUIT ENTRY SOCKET HEAD SCREW SPRING IN FINAL POSITION ACTUATING LEVER SWITCH ENCLOSURE SPRING IN INITIAL POSITION SLIDE IN THIS DIRECTION Figure 5 W0225 00 The following mounting position is not acceptable Actuator Vertical Pointing Up 2 Ground ...

Page 4: ...3 Supervisory switches are not a substitute for insurance Building owners should always insure property and lives being protected NOTE Common and B connections will close when valve moves 1 5 of its total travel distance Break here W0321 00 Figure 7 Actuating Arm Breakaway Feature THREE YEAR LIMITED WARRANTY SAFE SIGNAL warrants that the equipment herein shall conform to said descriptions as to al...

Reviews: