E50H2, E50H5 Installation Guide

BACnet Programming 
Information

The E50Hx is programmable via BACnet protocol and can easily be connected to a BACnet MS/TP network using an off-the shelf 
BACnet router. It uses five types of BACnet objects. A standard PICS (below) describes the required characteristics of the BACnet 
implementation, but this additional descriptive context may be helpful to the integrator.

In addition to the required properties, the device object utilizes some optional properties to support other functionality, Time 
Synchronization (primarily used for data/trend logging on the device) and Description and Location properties to simplify 
installation and maintenance. Configure all of the meter’s functions, other than Data Logging and writable Device Properties, by 
writing the Present_Value  of the 11 Analog_Value objects. These values (except for the configuration register, AV1, which always 
returns zero when read) are all readable and stored in nonvolatile memory so that they are retained if power to the device is 
interrupted.

Data values other than log information and alerts are all accessed by reading the Present_Value of the 52 Analog_Input objects. 
Most of these values are instantaneous readings of measured service parameters. Some of them, (AI1, AI26, AI27, AI37-AI45, AI47, 
AI50 and AI51) represent accumulated values and are stored in nonvolatile memory as well. If power to the device is interrupted, 
these values are retained, but no additional information accumulates until the device completes its re-initialization.

Alerts are used to indicate conditions of potential concern to the installer or the system, such as input voltage or current on any 
phase that exceeds the meter’s measurement range, phase voltage below the Phase Loss Threshold set by the user, or Power 
Factor below 0.5 on any phase. Alerts are accessible individually by reading the Present_Value  of the Binary_Input objects or as a 
group by reading the Present_Value of Analog_Input object 52. Alerts are not latched and do not generate events to system. They 
indicate presence of these conditions at the time they are read, but the device does not latch and store them until they are read (if 
the condition changes before they are read, the alert will go away).

All Analog_Value, Analog_Input, and Binary_Input objects implement the reliability property and use it to indicate that the 
Present_Value properties are functional, valid and current. For complete assurance, check the Reliabilty property for a No_Fault_
Detected status before reading the Present_Value of any AV, AI or BI objects.

The E50H5 includes data logging capability, which is implemented using three Trend_Log objects. These are described in more 
detail in the section on data logging.

BACnet Protocol Implementation Conformance Statement (PICS)

Date:

January 1, 2013

Vendor Name:

Veris Industries, LLC

Product Name:

E50Hx Energy Meter

Product Model Number:

E50Hx

Applications Software Version:

1    

Firmware Revision:

x.xxx

BACnet Protocol Revision:

4

Product Description:

3-phase electrical energy meter

BACnet Standardized Device Profile (Annex L):

  BACnet Application Specific Controller (B-ASC)

List all BACnet Interoperability Building Blocks Supported (Annex K):

  DS-RP-B, DS-RPM-B, DS-WP-B, DM-DDB-B, DM-DOB-B, 

DM-DCC-B, T-VMT-I-B (E50H5 only), 
     DM-TS-B, DM-RD-B

Segmentation Capability:

  Segmentation not supported

Содержание E50H Series

Страница 1: ...may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful inter...

Страница 2: ...Degree of Protection IEC 60529 IP40 front display IP20 meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 A...

Страница 3: ...50H2 E50H5 Installation Guide Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Di...

Страница 4: ...Energy kWh Configurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real...

Страница 5: ...nly TheredAlarmLEDlights whenanyofthe3phase voltagesdropbelowthe selectedthreshold ThegreenEnergyLEDlights whenthepulse1input contactsareactiveorclosed CONTROL POWER 0 1A 50 60 Hz A B C N 1 2 Pulse In...

Страница 6: ...d 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside...

Страница 7: ...ge Wiring Symbols The E50HxA power meters have a number of different possible system wiring configurations see Wiring section To configure the meter set the System Type via the User Interface or by wr...

Страница 8: ...uipment damage WARNING Wiring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B...

Страница 9: ...oundeddelta seetheLinetoNeutral installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeter...

Страница 10: ...t is 001 3 Press to accept the value and go to the KBAUD screen Use or to select the baud rate default is 76 8K 4 Press to go to the ID1 screen and through the upper four digits of the Device Instance...

Страница 11: ...nal PhaseLoss AlarmOutput PulseInput Equivalent Circuit Main Menu IEC IEEE Description D D Demand MAX M Maximum Demand P W Present Real Power Q VAR Present Reactive Power S VA Present Apparent Power A...

Страница 12: ...ive Phases 3 KVA Total Apparent Power S B A B VBC B KW B VLN C A C VAC C KW C VLN A KVA B KVA C KVA A PF 3 PF B PF C PF 3KVAR Total Reactive Power Q AKVAR BKVAR CKVAR KVARh KVAh Accumulated Reactive E...

Страница 13: ...A Current Out of Range Voltage Out of Range A B C Not used on E5xHx A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR...

Страница 14: ...e the System Voltage if used Potential Transformer RATIO 001 00 Back S V Back Sytem Voltage Next Set System Voltage V LL The nominal Line to Line Voltage for the system This is used by the meter to ca...

Страница 15: ...efault is 1 block demand SEC Sub Interval length in seconds Default is 900 15 minutes Set to 0 for external sync to comms Next S DIS Display Units UNITS IEEE IEC Back Set Display Units to switch betwe...

Страница 16: ...dlast deviceofthedaisychain Shieldwire Notes The terminal s voltage and current ratings are compliant with the requirements of the EIA RS 485 communications standard The RS 485 transceivers are unit l...

Страница 17: ...emand number of subintervals per interval 1 block mode AV10 Demand sub interval length 900 sec 15 min AV11 default value is 90000 1 100 seconds AV11 BACnet MAC Address 001 n a BACnet MS TP Baud Rate 7...

Страница 18: ...o the device is interrupted these values are retained but no additional information accumulates until the device completes its re initialization Alerts are used to indicate conditions of potential con...

Страница 19: ...and 40 AV3 May only write values from 5 to 32000 AV4 May only write values 1 and 3 AV5 May only write values from 0 01 to 320 0 AV6 May only write values such that AV6 AV5 is from 82 to 660 absolute...

Страница 20: ...ame R NV E50Hx Energy Meter Firmware_Revision R NV Current Revision xyyy This is the BACnet processor firmware version in the format xyyy with an implied decimal point between the first two digits x y...

Страница 21: ...d To read a value immediately after writing it check the Reliability property first When it reports a No_Fault_Detected status the Present_Value of the object is current These objects support the Desc...

Страница 22: ...hen the threshold is set to 10 if any phase drops more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit will...

Страница 23: ...ty for a No_Fault_Detected status before reading the Present_Value If the line voltage or input frequency of the system being monitored falls out of the supported range the corresponding alert bits BI...

Страница 24: ...W_Max_ Demand Total Real Power Maximum Demand R NV kW 0 Max_Power AI45 This retains the largest value measured forTotal Real Power Demand AI34 for any single demand interval since the Max Demand was l...

Страница 25: ...ant bit and BI14 or BI15 is the most significant bit Binary_InputObjects Use the Present_Value properties of the Binary_Input objects as alerts for conditions of potential concern regarding to the sys...

Страница 26: ...le Start_Time Stop_Time Log_Interval Stop_When_Full or Record Count for any one of the objects will be reflected in the corresponding property of all three objects The Log_Interval property is also co...

Страница 27: ...sed in any of the fields Log_Device_Object_ Property W BACnetDeviceObjectProptertyReference Set point this to the Present_Value of any of objects AI1 through AI49 to establish which parameter to log D...

Страница 28: ...heck all CTs and PTs to verify correct connection PT polarity and adequate power See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer...

Отзывы: