E50H2, E50H5 Installation Guide

#

Name

Description R/W

NV

Units

Range

Factory 

Default 

Value

Additional information

AV6

System_

Voltage

System 

Voltage

R/W

NV

Volts

from 82 (times 

the PT_Ratio 

in AV5) to

660 (times 

the PT_Ratio 

in AV5 - 

absolute 

limits are 

82-32000)

600

System Voltage – This voltage is Line to Line unless in System Type 10 (in object AV2), in 

which case it is Line to Neutral. This value is used to by the meter to calculate the full 

scale power for the analog outputs and pulse configuration (see below), and as full 

scale for phase loss (in object AV8). Do not set the meter to voltages outside the range 

of 82-660 volts times the PT Ratio in object AV5.

AV7

Display_

Units

Display Units R/W

NV

n/a

0,1

1

Display Units: 0 = IEC (U, V, P, Q, S), 1 = IEEE (default: VLL, VLN, W, VAR, VA)

AV8

Phase_Loss_

Voltage_

Threshold

Phase Loss 

Voltage 

Threshold

R/W

NV

Percent

1-99

10

Phase Loss Voltage Threshold in percent of System Voltage (in object AV6). Default is 

10 (10%).  Any phase (as configured in AV2) whose level drops below this threshold 

triggers a Phase Loss alert -  i.e. if the System voltage is set to 480 V L-L, the L-N 

voltage for each phase should be 277 V. When the threshold is set to 10%, if any phase 

drops more than 10% below 277 V, (less than 249 V), or if any L-L voltage drops more 

than 10% below 480 V (less than 432 V) the corresponding phase loss alarm bit will 

be true.

AV9

Phase_Loss_

Imbalance_

Threshold

Phase Loss 

Imbalance 

Threshold

R/W

NV

Percent

1-99

25

Phase Loss Imbalance Threshold in Percent. Default is 25% phase to phase difference. 

For a 3-phase Y (3 + N) system type (40 in object AV2), both Line to Neutral and Line 

to Line voltages are tested. In a 3-phase ∆ System type (31 in object AV2), only Line to 

Line voltages are examined. In a single split-phase (2 + N) system type (12 in object 

AV2), only the line to neutral voltage are compared. 

AV10 Subintervals

Number 

Subintervals 

Per Demand 

Interval 

R/W

NV

1-6

1

Number of Sub-Intervals per Demand Interval. Sets the number of sub-intervals that 

make a single demand interval. For block demand, set this to 1. Default is 1. When 

Sub-Interval Length (in object AV11) is set to 0 (sync-to-comms mode), the meter 

ignores this value.

AV11 Subinterval_

Length

Subinterval 

Length

R/W

NV

hundreths 

of a 

second

0,  

10-32767

90000

Sub-Interval Length in hundredths of a second. For sync-to-comms mode, which allows 

manual triggerring of demand intervals and the logging of another Trend_Log record, 

set this value to 0 and write 21211 to the reset register (object AV1) each time the 

sub-interval must be externally reset. Default is 90000 (15 minutes). This variable is 

tied directly to the Log_Interval property of all three Trend_Log objects (their value 

is always the same as this one). Changing any of these four properties changes all of 

them.

Trend_Log values are only used on the E50H5 model.

BACnet Programming Information (cont.)

Содержание E50H Series

Страница 1: ...may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful inter...

Страница 2: ...Degree of Protection IEC 60529 IP40 front display IP20 meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 A...

Страница 3: ...50H2 E50H5 Installation Guide Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Di...

Страница 4: ...Energy kWh Configurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real...

Страница 5: ...nly TheredAlarmLEDlights whenanyofthe3phase voltagesdropbelowthe selectedthreshold ThegreenEnergyLEDlights whenthepulse1input contactsareactiveorclosed CONTROL POWER 0 1A 50 60 Hz A B C N 1 2 Pulse In...

Страница 6: ...d 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside...

Страница 7: ...ge Wiring Symbols The E50HxA power meters have a number of different possible system wiring configurations see Wiring section To configure the meter set the System Type via the User Interface or by wr...

Страница 8: ...uipment damage WARNING Wiring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B...

Страница 9: ...oundeddelta seetheLinetoNeutral installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeter...

Страница 10: ...t is 001 3 Press to accept the value and go to the KBAUD screen Use or to select the baud rate default is 76 8K 4 Press to go to the ID1 screen and through the upper four digits of the Device Instance...

Страница 11: ...nal PhaseLoss AlarmOutput PulseInput Equivalent Circuit Main Menu IEC IEEE Description D D Demand MAX M Maximum Demand P W Present Real Power Q VAR Present Reactive Power S VA Present Apparent Power A...

Страница 12: ...ive Phases 3 KVA Total Apparent Power S B A B VBC B KW B VLN C A C VAC C KW C VLN A KVA B KVA C KVA A PF 3 PF B PF C PF 3KVAR Total Reactive Power Q AKVAR BKVAR CKVAR KVARh KVAh Accumulated Reactive E...

Страница 13: ...A Current Out of Range Voltage Out of Range A B C Not used on E5xHx A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR...

Страница 14: ...e the System Voltage if used Potential Transformer RATIO 001 00 Back S V Back Sytem Voltage Next Set System Voltage V LL The nominal Line to Line Voltage for the system This is used by the meter to ca...

Страница 15: ...efault is 1 block demand SEC Sub Interval length in seconds Default is 900 15 minutes Set to 0 for external sync to comms Next S DIS Display Units UNITS IEEE IEC Back Set Display Units to switch betwe...

Страница 16: ...dlast deviceofthedaisychain Shieldwire Notes The terminal s voltage and current ratings are compliant with the requirements of the EIA RS 485 communications standard The RS 485 transceivers are unit l...

Страница 17: ...emand number of subintervals per interval 1 block mode AV10 Demand sub interval length 900 sec 15 min AV11 default value is 90000 1 100 seconds AV11 BACnet MAC Address 001 n a BACnet MS TP Baud Rate 7...

Страница 18: ...o the device is interrupted these values are retained but no additional information accumulates until the device completes its re initialization Alerts are used to indicate conditions of potential con...

Страница 19: ...and 40 AV3 May only write values from 5 to 32000 AV4 May only write values 1 and 3 AV5 May only write values from 0 01 to 320 0 AV6 May only write values such that AV6 AV5 is from 82 to 660 absolute...

Страница 20: ...ame R NV E50Hx Energy Meter Firmware_Revision R NV Current Revision xyyy This is the BACnet processor firmware version in the format xyyy with an implied decimal point between the first two digits x y...

Страница 21: ...d To read a value immediately after writing it check the Reliability property first When it reports a No_Fault_Detected status the Present_Value of the object is current These objects support the Desc...

Страница 22: ...hen the threshold is set to 10 if any phase drops more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit will...

Страница 23: ...ty for a No_Fault_Detected status before reading the Present_Value If the line voltage or input frequency of the system being monitored falls out of the supported range the corresponding alert bits BI...

Страница 24: ...W_Max_ Demand Total Real Power Maximum Demand R NV kW 0 Max_Power AI45 This retains the largest value measured forTotal Real Power Demand AI34 for any single demand interval since the Max Demand was l...

Страница 25: ...ant bit and BI14 or BI15 is the most significant bit Binary_InputObjects Use the Present_Value properties of the Binary_Input objects as alerts for conditions of potential concern regarding to the sys...

Страница 26: ...le Start_Time Stop_Time Log_Interval Stop_When_Full or Record Count for any one of the objects will be reflected in the corresponding property of all three objects The Log_Interval property is also co...

Страница 27: ...sed in any of the fields Log_Device_Object_ Property W BACnetDeviceObjectProptertyReference Set point this to the Present_Value of any of objects AI1 through AI49 to establish which parameter to log D...

Страница 28: ...heck all CTs and PTs to verify correct connection PT polarity and adequate power See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer...

Отзывы: