E50H2, E50H5 Installation Guide

Legend

R/W  

R=read only; R/W=read or write 

NV 

Value is stored in non-volatile memory. The value are still available if the meter experiences a power loss and reset. 

Units 

Lists the physical units that a register holds.

Device Object

Property

R/W

NV

Value Returned

Additional information

Object_Identifier 

R/W

NV

 Device<n>

n is the 7 digit ID # set in the ID1 & ID2 setup screens on the meter. The BACnet Device 

ID is a decimal number from 1 to 4,193,999 that can be entered or viewed on the user 

screens or through this property. The default value set at the factory is a psuedo-

random number from 1,000,000 to 3,097,151 to reduce the likelihood of conflicts if 

multiple units are installed using their default IDs.

Object_Type 

R

NV

Device (8)

Object_Name

R

NV

Veris E50 Series Energy Meter  - S/N: <serial 

number>

Vendor_Name

R

NV

Veris Industries, LLC

Vendor_Identifier 

R

NV

133

Model_Name

R

NV

E50Hx Energy Meter

Firmware_Revision

R

NV

<Current Revision #>

“xyyy”. 
This is the BACnet processor firmware version in the format <xyyy>, with an implied 

decimal point between the first two digits (x.yyy)

Application_Software_ Version

R

NV

<Current version #>

“RS= xyyy, OS=xyyy, BACnet Gateway=xyyy”
The format <xyyy> has an implied decimal point between the first two digits (x.yyy)

Location

R/W

NV

<Location>

Limted to 64 Characters - Default value is “Installed location not yet identified”

Description

R

NV

Veris E50Hx DIN-Rail Energy Meter S/N: 

<serial number>

Protocol_Version

R

NV

1

BACnet Protocol Version 1

Protocol_Revsion

R

NV

4

BACnet Protocol Revision 4

Local_Date

R

Date

Set via BACnet Time Synchronization only - reverts to Jan 1, 2000 if control power drops

Local_Time

R

Time

Set via BACnet Time Synchronization only - reverts to 12:00:00 AM if control power 

drops

Segmentation_Supported

R

NV

NO_SEGMENTATION (3)

Segmentation is not supported

Max_Master

R/W

NV

1-127 (Factory Default is 127)

Highest possible MAC Address for Master nodes on the local MS/TP network

Max_Info_Frames

R

NV

1

Maximum number of information frames allowed before passing the MS/TP token

Max_APDU_Length_Accepted

R

NV

480

APDU_Timeout

R

NV

60000

Number_of_APDU_Retries 

R

NV

0

System_Status 

R

NV

Operational (0)

Protocol_Sevices_Supported

R

NV

0b0000000000001011010000000000000

011110000

Protocol_Object_Types_Supported

R

NV

0b1011000010000000000010000000000

BACnet Programming 
Information
(cont.)

Содержание E50H Series

Страница 1: ...may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful inter...

Страница 2: ...Degree of Protection IEC 60529 IP40 front display IP20 meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 A...

Страница 3: ...50H2 E50H5 Installation Guide Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Di...

Страница 4: ...Energy kWh Configurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real...

Страница 5: ...nly TheredAlarmLEDlights whenanyofthe3phase voltagesdropbelowthe selectedthreshold ThegreenEnergyLEDlights whenthepulse1input contactsareactiveorclosed CONTROL POWER 0 1A 50 60 Hz A B C N 1 2 Pulse In...

Страница 6: ...d 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside...

Страница 7: ...ge Wiring Symbols The E50HxA power meters have a number of different possible system wiring configurations see Wiring section To configure the meter set the System Type via the User Interface or by wr...

Страница 8: ...uipment damage WARNING Wiring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B...

Страница 9: ...oundeddelta seetheLinetoNeutral installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeter...

Страница 10: ...t is 001 3 Press to accept the value and go to the KBAUD screen Use or to select the baud rate default is 76 8K 4 Press to go to the ID1 screen and through the upper four digits of the Device Instance...

Страница 11: ...nal PhaseLoss AlarmOutput PulseInput Equivalent Circuit Main Menu IEC IEEE Description D D Demand MAX M Maximum Demand P W Present Real Power Q VAR Present Reactive Power S VA Present Apparent Power A...

Страница 12: ...ive Phases 3 KVA Total Apparent Power S B A B VBC B KW B VLN C A C VAC C KW C VLN A KVA B KVA C KVA A PF 3 PF B PF C PF 3KVAR Total Reactive Power Q AKVAR BKVAR CKVAR KVARh KVAh Accumulated Reactive E...

Страница 13: ...A Current Out of Range Voltage Out of Range A B C Not used on E5xHx A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR...

Страница 14: ...e the System Voltage if used Potential Transformer RATIO 001 00 Back S V Back Sytem Voltage Next Set System Voltage V LL The nominal Line to Line Voltage for the system This is used by the meter to ca...

Страница 15: ...efault is 1 block demand SEC Sub Interval length in seconds Default is 900 15 minutes Set to 0 for external sync to comms Next S DIS Display Units UNITS IEEE IEC Back Set Display Units to switch betwe...

Страница 16: ...dlast deviceofthedaisychain Shieldwire Notes The terminal s voltage and current ratings are compliant with the requirements of the EIA RS 485 communications standard The RS 485 transceivers are unit l...

Страница 17: ...emand number of subintervals per interval 1 block mode AV10 Demand sub interval length 900 sec 15 min AV11 default value is 90000 1 100 seconds AV11 BACnet MAC Address 001 n a BACnet MS TP Baud Rate 7...

Страница 18: ...o the device is interrupted these values are retained but no additional information accumulates until the device completes its re initialization Alerts are used to indicate conditions of potential con...

Страница 19: ...and 40 AV3 May only write values from 5 to 32000 AV4 May only write values 1 and 3 AV5 May only write values from 0 01 to 320 0 AV6 May only write values such that AV6 AV5 is from 82 to 660 absolute...

Страница 20: ...ame R NV E50Hx Energy Meter Firmware_Revision R NV Current Revision xyyy This is the BACnet processor firmware version in the format xyyy with an implied decimal point between the first two digits x y...

Страница 21: ...d To read a value immediately after writing it check the Reliability property first When it reports a No_Fault_Detected status the Present_Value of the object is current These objects support the Desc...

Страница 22: ...hen the threshold is set to 10 if any phase drops more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit will...

Страница 23: ...ty for a No_Fault_Detected status before reading the Present_Value If the line voltage or input frequency of the system being monitored falls out of the supported range the corresponding alert bits BI...

Страница 24: ...W_Max_ Demand Total Real Power Maximum Demand R NV kW 0 Max_Power AI45 This retains the largest value measured forTotal Real Power Demand AI34 for any single demand interval since the Max Demand was l...

Страница 25: ...ant bit and BI14 or BI15 is the most significant bit Binary_InputObjects Use the Present_Value properties of the Binary_Input objects as alerts for conditions of potential concern regarding to the sys...

Страница 26: ...le Start_Time Stop_Time Log_Interval Stop_When_Full or Record Count for any one of the objects will be reflected in the corresponding property of all three objects The Log_Interval property is also co...

Страница 27: ...sed in any of the fields Log_Device_Object_ Property W BACnetDeviceObjectProptertyReference Set point this to the Present_Value of any of objects AI1 through AI49 to establish which parameter to log D...

Страница 28: ...heck all CTs and PTs to verify correct connection PT polarity and adequate power See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer...

Отзывы: