manualshive.com logo in svg
background image

ZL0071-0F 

Page 1 of 28 

©2018 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0818 

 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must 
control conductive pollution and the possibility of condensation or high humidity. Consider the 
enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship with 
the environment. Installation category:  CAT II or CAT III.  Provide a disconnect device to disconnect the 
meter from the supply source. Place this device in close proximity to the equipment and within easy 
reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the 
relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. In the US 
and Canada, disconnecting fuse holders can be used. Provide overcurrent protection and disconecting 
device for supply conductors with approved current limiting devices suitable for protecting the wiring. 
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the 
device may be impaired.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Product may use multiple voltage/power sources. Disconnect ALL sources before

 servicing.
•  Use a properly rated voltage sensing device to confirm that power is off.
  DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION.
•  Current transformer secondaries must be shorted or connected to a burden at all times.
•  Products rated only for basic insulation must be installed on insulated conductors.
•  Replace all doors, covers and protective devices before powering the equipment.

Failure to follow these instructions will result in death or serious injury.

A qualified person is one who has skills and knowledge related to the construction and 

operation of this electrical equipment and installations, and has received safety 

training to recognize and avoid the hazards involved.  

NEC Article 100

If this product is used in a manner not specified by the manufacturer, the protection 

provided by the product may be impaired. No responsibility is assumed by the 

manufacturer for any consequences arising out of the use of this material.

DANGER

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  The installer is responsible for conformance to all applicable codes.

•  Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION

NOTE: This equipment has been tested by the manufacturer and found to 

comply with the limits for a class B digital device, pursuant to part 15 of 

the FCC Rules. These limits are designed to provide reasonable protection 

against harmful interference when the equipment is operated in a 

residential environment. This equipment generates, uses, and can radiate 

radio frequency energy and, if not installed and used in accordance with 

the instruction manual, may cause harmful interference to radio 

communications. This device complies with part 15 of the FCC Rules. 

Operation is subject to the following two conditions:

   

(1) This device may not cause harmful interference, and

   

(2) this device must accept any interference received, including

   

      interference that may cause undesired operation.

   Modifications to this product without the express authorization of the 

manufacturer nullify this statement. 

WARNING

LOSS OF CONTROL

∙  Assure that the system will reach a safe state during and after a control path failure.
∙  Separate or redundant control paths must be provided for critical control functions.
∙  Test the effect of transmission delays or failures of communication links.

1

∙  Each implementation of equipment using communication links must be individually 

and thoroughly tested for proper operation before placing it in service.

Failure to follow these instructions may cause injury, death or equipment damage.

1

For additional information about anticipated transmission delays or failures of the link, refer to 

NEMA ICS 1.1 (latest edition). 

Safety Guidelines for the Application, Installation, and Maintenance 

of Solid-State Control

 or its equivalent in your specific country, language, and/or location.

Control system design must consider the potential failure modes of control paths and, for 

certain critical control functions, provide a means to acheive a safe state during and after a 

path failure. Examples of critical control functions are emergency stop and over-travel stop.

TM

The safety of any system incorporating this equipment is the responsibility of the 

assembler of the system.

Installation Guide

Power Monitoring

Product Identification

Model

BACnet MS/TP 

Protocol Output

Alarm 

Output

Full Data 

Set

Data 

Logging

Pulse 

Input

E50H2

 

E50H5

(2 pulses)

Product Overview

The E50H2 and E50H5 DIN rail power meters provide a solution for measuring energy data with a single device. 
Inputs include control power, CT, and 3-phase voltage. Both models support BACnet MS/TP protocol. The E50H2 
has one pulse contact input and a phase loss alarm output. The E50H5 has data logging capability and two pulse 
contact inputs. The LCD screen on the faceplate allows instant output viewing. 

The meter is housed in a plastic enclosure suitable for installation on T35 DIN rail according to EN 50022. It can be 
mounted with any orientation over the entire ambient temperature range, either on a DIN rail or in a panel. The 
E50Hx meters are not sensitive to CT orientation, reducing installation errors.

E50H2, E50H5

Compact Power and Energy Meters 

With BACnet MS/TP Support

Specifications

MEASUREMENT ACCURACY

   Real Power and Energy

IEC 62053-22 Class 0.2S, ANSI C12.20 0.2%

   Reactive Power and Energy

IEC 62053-23 Class 2, 2%

   Current

0.4% (+0.015% per °C deviation from 25 °C) from 5% to 100% of range;  

0.8% (+0.015% per °C deviation from 25 °C) from 1% to 5% of range

   Voltage

0.4% (+0.015% per °C deviation from 25 °C) from 90 V

L-N

 to 600 Vac

L-L

   Sample Rate

2520 samples per second 

   Data Update Rate

1 sec

   Type of Measurement

True RMS up to the 21st harmonic 60 Hz; One to three phase AC system

INPUT VOLTAGE CHARACTERISTICS

   Measured AC Voltage

Minimum 90V

L-N

 (156V

L-L

) for stated accuracy;  

UL Maximum:  600V

L-L

 (347V

L-N

); CE Maximum:  300V

L-N

   Metering Over-Range

+20%

   Impedance

2.5 MΩ 

L-N 

/5 MΩ 

L-L

   Frequency Range

45 to 65 Hz

INPUT CURRENT CHARACTERISTICS

CT  Scaling                                             

Primary: Adjustable from 5 A to 32,000 A

   Measurement Input Range

0 to 0.333 Vac or 0 to 1.0 Vac (+20% over-range), rated for use with Class 1 

voltage inputs

   Impedance

10.6 kΩ (1/3 V mode) or 32.1 kΩ (1 V mode)

®

T

E

S

T

I

N

G

  L

A B O R

A

T

O

R

I

E

S

· B

A C n e t ·

E50H2 only

Содержание E50H Series

Страница 1: ...may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful inter...

Страница 2: ...Degree of Protection IEC 60529 IP40 front display IP20 meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 A...

Страница 3: ...50H2 E50H5 Installation Guide Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power Di...

Страница 4: ...Energy kWh Configurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line Line and Line Neutral Power Real...

Страница 5: ...nly TheredAlarmLEDlights whenanyofthe3phase voltagesdropbelowthe selectedthreshold ThegreenEnergyLEDlights whenthepulse1input contactsareactiveorclosed CONTROL POWER 0 1A 50 60 Hz A B C N 1 2 Pulse In...

Страница 6: ...d 35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside...

Страница 7: ...ge Wiring Symbols The E50HxA power meters have a number of different possible system wiring configurations see Wiring section To configure the meter set the System Type via the User Interface or by wr...

Страница 8: ...uipment damage WARNING Wiring N L1 X2 X1 White Black A B C N X1 X2 X1 X2 X1 X2 A B C Diagram1 1 PhaseLine to Neutral2 Wire System1CT Diagram2 1 PhaseLine to Line2 Wire System1CT L1 L2 X2 X1 X2 X1 A B...

Страница 9: ...oundeddelta seetheLinetoNeutral installationlimits InCEcompliantinstallations thelinesmust beneutral earth referencedatlessthan300VACL N TheControlPowerTransformermaybewiredL NorL L Outputto meetmeter...

Страница 10: ...t is 001 3 Press to accept the value and go to the KBAUD screen Use or to select the baud rate default is 76 8K 4 Press to go to the ID1 screen and through the upper four digits of the Device Instance...

Страница 11: ...nal PhaseLoss AlarmOutput PulseInput Equivalent Circuit Main Menu IEC IEEE Description D D Demand MAX M Maximum Demand P W Present Real Power Q VAR Present Reactive Power S VA Present Apparent Power A...

Страница 12: ...ive Phases 3 KVA Total Apparent Power S B A B VBC B KW B VLN C A C VAC C KW C VLN A KVA B KVA C KVA A PF 3 PF B PF C PF 3KVAR Total Reactive Power Q AKVAR BKVAR CKVAR KVARh KVAh Accumulated Reactive E...

Страница 13: ...A Current Out of Range Voltage Out of Range A B C Not used on E5xHx A B C INFO MODEL OS SN RS Serial Number Reset System Operating System ALERT INFO PLOSS A b C LOWPF A b C F ERR A I OVR A b C V OVR...

Страница 14: ...e the System Voltage if used Potential Transformer RATIO 001 00 Back S V Back Sytem Voltage Next Set System Voltage V LL The nominal Line to Line Voltage for the system This is used by the meter to ca...

Страница 15: ...efault is 1 block demand SEC Sub Interval length in seconds Default is 900 15 minutes Set to 0 for external sync to comms Next S DIS Display Units UNITS IEEE IEC Back Set Display Units to switch betwe...

Страница 16: ...dlast deviceofthedaisychain Shieldwire Notes The terminal s voltage and current ratings are compliant with the requirements of the EIA RS 485 communications standard The RS 485 transceivers are unit l...

Страница 17: ...emand number of subintervals per interval 1 block mode AV10 Demand sub interval length 900 sec 15 min AV11 default value is 90000 1 100 seconds AV11 BACnet MAC Address 001 n a BACnet MS TP Baud Rate 7...

Страница 18: ...o the device is interrupted these values are retained but no additional information accumulates until the device completes its re initialization Alerts are used to indicate conditions of potential con...

Страница 19: ...and 40 AV3 May only write values from 5 to 32000 AV4 May only write values 1 and 3 AV5 May only write values from 0 01 to 320 0 AV6 May only write values such that AV6 AV5 is from 82 to 660 absolute...

Страница 20: ...ame R NV E50Hx Energy Meter Firmware_Revision R NV Current Revision xyyy This is the BACnet processor firmware version in the format xyyy with an implied decimal point between the first two digits x y...

Страница 21: ...d To read a value immediately after writing it check the Reliability property first When it reports a No_Fault_Detected status the Present_Value of the object is current These objects support the Desc...

Страница 22: ...hen the threshold is set to 10 if any phase drops more than 10 below 277V less than 249V or if any L L voltage drops more than 10 below 480V less than 432V the corresponding phase loss alarm bit will...

Страница 23: ...ty for a No_Fault_Detected status before reading the Present_Value If the line voltage or input frequency of the system being monitored falls out of the supported range the corresponding alert bits BI...

Страница 24: ...W_Max_ Demand Total Real Power Maximum Demand R NV kW 0 Max_Power AI45 This retains the largest value measured forTotal Real Power Demand AI34 for any single demand interval since the Max Demand was l...

Страница 25: ...ant bit and BI14 or BI15 is the most significant bit Binary_InputObjects Use the Present_Value properties of the Binary_Input objects as alerts for conditions of potential concern regarding to the sys...

Страница 26: ...le Start_Time Stop_Time Log_Interval Stop_When_Full or Record Count for any one of the objects will be reflected in the corresponding property of all three objects The Log_Interval property is also co...

Страница 27: ...sed in any of the fields Log_Device_Object_ Property W BACnetDeviceObjectProptertyReference Set point this to the Present_Value of any of objects AI1 through AI49 to establish which parameter to log D...

Страница 28: ...heck all CTs and PTs to verify correct connection PT polarity and adequate power See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer...

Отзывы: