E50C1A Installation Guide

Modbus Point Map 
Overview

The E50C1A Basic Data Set (BDS) features Wh and VARh accumulators. The meter supports variable CTs and PTs, allowing a much 
wider range of operation from 90V x 5A up to 32000V x 5000A. To promote this, the meter permits variable scaling of the 16-bit 
integer registers via the scale registers. The 32-bit floating point registers do not need to be scaled.

Integer registers begin at 001 (0x001). Floats at 257 (0x101). Configuration registers at 129 (0x081). Values not supported in a 
particular System Type configuration will report QNAN (0x8000 in Integer Registers, 0x7FC00000 in Floating Point Registers).

Supported Modbus Commands

Note:  ID String information varies from model to model. Text shown here is an example.

Command

Description

0x03

Read Holding Registers

0x04

Read Input Registers

0x06

Preset Single Register

0x10

Preset Multiple Registers

0x11

Report ID
Return string:
byte0:   address
byte1:   0x11
byte2:   #bytes following w/out crc
byte3:   ID byte = 247
byte4:   status = 0xFF if the operating system is used; status = 0x00 if the reset system is used
: ID string = “Veris Industries E50xx Power Meter Full Data Set”  or “Veris Industries E50xx Power Meter - RESET 

SYSTEM RUNNING RS Version x.xxx” last 2 bytes: CRC

0x2B

Read Device Identification, BASIC implementation (0x00, 0x01 and 0x02 data), Conformity Level 1.
Object values:
0x01: “Veris Industries”
0x02: “ E50xx”
0x03: “Vxx.yyy”, where xx.yyy is the OS version number (reformatted version of the Modbus register #7001, (Firmware 

Version, Operating System).  

If register #7001 == 12345, then the 0x03 data would be “V12.345”).

Legend

The following table lists the addresses assigned to each data point. For floating point format variables, each data point appears 
twice because two 16-bit addresses are required to hold a 32-bit float value.

R/W 

R=read only; R/W=read from either int or float formats, write only to integer format.

NV

Value is stored in non-volatile memory. The value will still be available if the meter experiences a power loss and reset. 

Format

UInt

Unsigned 16-bit integer.

SInt

Signed 16-bit integer.

ULong

Unsigned 32-bit integer; Upper 16-bits (MSR) in lowest-numbered / first listed register (001/002 = MSR/LSR).

Float

32-bit floating point; Upper 16-bits (MSR) in lowest-numbered / first listed register (257/258 = MSR/LSR). Encoding 

is per IEEE standard 754 single precision.

Units

Lists the physical units that a register holds.

Scale Factor   Some Integer values must be multiplied by a constant scale factor (typically a fraction), to be read correctly. This is done to allow 

integer numbers to represent fractional numbers.

Range

Defines the limit of the values that a register can contain.

Содержание E50C1A

Страница 1: ...nd if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to...

Страница 2: ...529 IP40 front display IP20 meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 AWG 0 2 to 2 1 mm2 Rail T35...

Страница 3: ...Installation Guide Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setu...

Страница 4: ...VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners TM E50C1A Installation Guide Dimensions 4 2 107mm 3 6 91mm 1 5 39mm 2 3...

Страница 5: ...ndicator RS 485EquippedUnitsOnly TransmitData ReceiveData ReceiveDataError LCDScreen Buttons Up Select Right Next Down Select Left Back kWh 1234 5 Alarm Energy Two5 characterrows ofdisplaytext Toprowa...

Страница 6: ...35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside Th...

Страница 7: ...r System Type will display as on the User Interface or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID Type Modb...

Страница 8: ...TnoPT UseSystemType11 2L UseSystemType12 2L 1n UseSystemType 31 3L UseSystemType10 1L 1n Wiring RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE CT terminals are referenced to the meter s neutral...

Страница 9: ...L L Outputto meetmeterinputrequirements DCControlPowerfrom125Vdcto300Vdc ULandCEmax FuseRecommendations Keep the fuses close to the power source obey local and national code requirements For selecting...

Страница 10: ...ect the parameter screen you want to set 6 After you set the parameters you want use or to select the next Setup screen or to exit the Setup screens return to SETUP B ToEnterModbuscommunicationparamet...

Страница 11: ...powered and no phase loss alarm conditions are present All pulse outputs and communication circuits are only intended to be connected to non hazardous circuits SELV or Class 2 Do not connect to hazar...

Страница 12: ...KWh Accumulated Real Energy Ph SETUP ALERT RESET Back Display nOnE if no alerts To Setup Setup Meter Reset Data Phase Loss A B C Low Power Factor A B C Frequency Out of Range A Current Over Range Vol...

Страница 13: ...00 SYSTM 3L 1n 3L 2L 1n 2L 1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT in...

Страница 14: ...the selection if it cannot find a pulse duration that will allow the pulse output to keep up with Theoretical Maximum System Power see S_PWR screen When moving up to a larger energy the meter will jum...

Страница 15: ...47 k pull down to Shield RS 485 signal ground Wire the RS 485 bus as a daisy chain from device to device without any stubs Use 120 termination resistors at each end of the bus not included Shield is...

Страница 16: ...status 0x00 if the reset system is used bytes5 ID string Veris Industries E50xx Power Meter Full Data Set or Veris Industries E50xx Power Meter RESET SYSTEM RUNNING RSVersion x xxx last 2 bytes CRC 0x...

Страница 17: ...atio of 2 1 The default is 100 1 00 1 which is with no PT attached Set this value before setting the system voltage below 134 R W NV UInt 82 32000 SystemVoltage This voltage is line to line except for...

Страница 18: ...nd a pulse duration that will keep up with the max system power register 135 it will reject the new value Try a larger value kWh Pulse Contacts Note The kWh pulse contact can keep up with a maximum po...

Страница 19: ...nge Description 152 R W NV UInt 0 32767 Power Up Counter 153 R NV UInt 0 32767 Output Configuration E50C1 always returns 0 154 R UInt Reserved returns 0 Floating Point Data 257 258 R NV Float kWh Real...

Страница 20: ...ct connection to the same service PT polarity and adequate powering See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer Power meter...

Отзывы: