FLUE TERMINAL POSITION
The minimum distances permissible from the flue terminal to obstructions and
ventilation openings are shown in Figure 1.
DIMENSION TERMINAL POSITION
MINIMUM
DISTANCE
A
Directly below an opening, air brick or window, etc...
300mm
B
Below gutters, soil pipes or drain pipes
75mm
C
Below eaves
200mm
D
Below balconies or car port roof
200mm
E
From a vertical drainpipe or soil pipe
150mm
F
From an internal or external corner
200mm
G
Above ground or balcony level
300mm
H
From a surface facing the terminal
600mm
I
From a terminal facing a terminal
1200mm
J
From the opening in a carport
1200mm
K
Vertically from a terminal on the same wall
1500mm
L
Horizontally from a terminal on the same wall
300mm
FITTING THE FIREBOX - SURFACE FITTED
1
Note:
For surface fitting of the Fanfare the fire surround must have a minimum rebate
of 130mm (See Figure 2). Alternatively the depth of the firebox can be accommodated
within a false chimney breast (See Figure 3).
Note:
Diagrams shown with recessed fan unit.