Next, drill the holes for anchoring the fastening brackets to
the wall using as a first option the 4 holes on the ends of
the bracket as shown on the drilling template (see fig. 6).
If the wall is not very solid, it is advisable to use some
extra anchor bolts.
As you can see, the bracket can be fastened in a number of
different ways and positions. The air conditioner is heavier
on the left-hand side, so it is best to make sure of a solid
anchorage on that side. The anchor bolts provided require
holes with a diameter of 10mm. In any case, the wall
should be inspected carefully to determine the best
possible anchorage and type of bolts suitable for particular
installations.
Warning: The manufacturer is not liable in the case of
underestimation of the structural integrity of the
anchorage made at the time of installation. We
therefore recommend that you perform this operation
with the maximum care. If not done properly, it can
case serious damage to persons and property.
When installing model equipped with heating pump, if no
drainage well for condensate has been provided built into
the wall (see paragraph 2.3.2), it will be necessary, to
allow drainage of the condensate, to drill a hole through
t h e wall measuring 16mm in diameter in the position
shown on the template (see fig 6.)