ZEC410 VAV Controllers Installation Instructions

3

To mount the ZEC controllers:

1.

Ensure that you have the appropriate personal protective equipment (PPE), such as a hard hat, safety glasses, 
steel toe boots, and gloves.

2.

Disconnect power from the controller transformer as well as the VAV box fan and heater circuits, if applicable.

3.

Set all the switches on the field controller to their known settings, and then set the Master-Slave/Token-Passing 
(MS/TP) address, and ensure that EOL is set to Off. See 

Setup and Adjustments

4.

Place the ZEC controller in the proper mounting position on the actuator shaft so that the wiring  connections 
are easily accessible. Make sure the  ZEC controller base is parallel to the VAV box  (perpendicular to the 
damper shaft). If needed, use  a spacer to offset tipping of the ZEC controller caused by the shaft bushings.

Note:

Use the alignment marks to center the captive  spacer to ensure sufficient ZEC movement  in either direction 

(Figure 8).

5.

Secure the self-drilling No. 10 screw through the captive spacer with a power screwdriver and 
100 mm (4 in.) extension socket. Otherwise, use  a punch to mark the position of the shoulder washer,  and then 
drill a hole into the VAV box using a 5/16 in. drill bit. Insert the mounting screw and tighten it against the spacer.

6.

Locate the damper position using the typical marking  on the end of the damper shaft.

Table 1:  Verasys System Bus Controller Addressing

System Bus 
Address/Range

Standalone Verasys System Bus
(not integrated into a BACnet BAS 
network)

Verasys System Bus 
(integrated into a BACnet BAS network)

1

May be used for Verasys system controllers

Used for BACnet reserved function devices - not 
used for Verasys System Bus controllers

2

3

Address used by an FC Bus or System Bus - connected to a Smart Building Hub - not used for Verasys 
System Bus controllers or BACnet device address

May be used for Verasys System Bus controllers if 
there is not an FC Bus or System Bus connected 
Smart Building Hub

May be used for Verasys System Bus controllers if 
there is not an FC Bus or System Bus connected

4

May be used for Verasys System Bus controllers

May be used for Verasys System Bus controllers if 
there is a not a BACnet device address conflict

117

Address used by the Smart Building Hub - not used for other Verasys System Bus controllers or BACnet 
device address

118 through 127

May be used for Verasys System Bus controllers

May be used for Verasys System Bus controllers if 
there is not a BACnet device address conflict

IMPORTANT:

 Do not overtighten the screw, or the  threads may strip. If you mount the ZEC to the VAV box, 

make sure that the screws do not  interfere with damper blade movement.

Alignment

Marks

Figure 1: Captive Spacer Alignment Marks

Содержание ZEC410

Страница 1: ...ol system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the ZEC410 VAV contro...

Страница 2: ...ven surface whenever possible Use shims or washers to mount the ZEC securely and evenly on the mounting surface if necessary Mount the ZEC in an area free of corrosive vapors that matches the ambient...

Страница 3: ...it against the spacer 6 Locate the damper position using the typical marking on the end of the damper shaft Table 1 Verasys System Bus Controller Addressing System Bus Address Range Standalone Verasys...

Страница 4: ...d stop the closed end stop is set by the closed damper For 45 and 60 boxes hard stops must be provided at both full closed and full open damper positions By installing the ZEC controller at the full o...

Страница 5: ...op ration de r glage Veiller ne toucher aucune partie du circuit imprim lorsque celui ci est sous tension Le non respect de ces pr cautions peut provoquer des blessures graves voire mortelles IMPORTA...

Страница 6: ...modular SA Bus ports provide a connection for the VAV Balancing Tool The FC Bus port is not used in ZEC installations Figure 3 SA Bus Terminal Block Wiring Stranded 4 Wire 2 Twisted Pair Shielded Cab...

Страница 7: ...remental outputs for the heating control 2 Wire the network temperature sensor and CO2 sensor to the ZEC s SA Bus 3 Wire the FC Bus in a daisy chain 4 Ensure that the ZEC s device address DIP switches...

Страница 8: ...ZEC410 1 SUPHTG1 C Optional ZN T SA DA ZN CO2 Optional OCC S Optional DA T Optional HTG3 C Optional HTG2 C Optional E C HTG1 C Optional SF C SUPHTG1 C Optional ZN T SA RA DA ZN CO2 Optional OCC S Opt...

Страница 9: ...TAT IS SELECTED 24V COM 24V HOT SA PWR COM TO NEXT DEVICE FRO M LAST DEVICE MS TP MS TP Oc cupancy Sensor O LS 2100 1 CONNECTOR O N BACK OF SENSOR ZONE SENSOR ZN CO2 24V HOT COM SA PWR 24V COM SEE RIS...

Страница 10: ...e zone temperature drops below the unoccupied heating setpoint the supplemental heating coil is fully used before the reheat heat coil enables The damper is at the minimum cfm Unit Enable A network un...

Страница 11: ...ECTOR ON BACK OF SENSOR ZONE SENSOR ZN T IF NETSTAT IS SELECTED 24V COM 24V HOT SA PWR COM TO NEXT DEVICE FROM LAST DEVICE MS TP MS TP TO RE D WIRE OCCUP ANCY S WITCH TO BLACK WIRE OCCUP ANCY S WITCH...

Страница 12: ...ne temperature drops below the unoccupied heating setpoint the supplemental heating coil is fully used before the reheat heat coil enables The damper is at the minimum cfm Unit Enable A network unit e...

Страница 13: ...ONNECTTOAIR FLOWPROBE SF C OPTIONAL DA T DISCHARGEAIRTEMP OPTIONAL 24VHot 24VCom NOTE SUPPLEMENTALVALVESDEFAULTTOA 60 SECONDINCREMENTALACTUATOR THISIS ADJUSTABLEINVERASYS SUPHTG O OPTIONAL CW CCW COM...

Страница 14: ...rily sets the VAV box to Standby mode when the occupancy is not sensed When the box senses occupancy the zone switches back to occupied Standby mode uses standby temperature setpoints that are slightl...

Страница 15: ...than or equal to the intended device address to ON Then continue setting lower numbered switches until the total equals the intended address For example if the intended device address is 21 set Switc...

Страница 16: ...erature sensor 1k ohm nickel with temperature occupancy button TE 68NT 1N00S Wall temperature sensor 1k ohm nickel with warmer cooler W C adjustment and temperature occupancy pushbutton Zone CO2 Senso...

Страница 17: ...cally at the sensor Refer to the Verasys System User s Guide LIT 12012371 for more information CO2 Demand Controlled Ventilation DCV CO2 DCV ensures high Indoor Air Quality IAQ for the zone by using u...

Страница 18: ...f the bus for testing purposes and test the bus portion connected to the Zone Coordinator Correcting Physical Communication Bus Problems The communication bus is subject to a number of physical factor...

Страница 19: ...50 to 60 Hz Class 2 power supply or Safety Extra Low Voltage SELV at 50 60 Hz 20 VAC minimum Power Consumption 10 VA 14 VA maximum Ambient Conditions Ambient Operating Conditions 0 to 50 C 32 to 122 F...

Отзывы: