background image

ZEC410 VAV Controllers Installation Instructions

14

Sequence of Operation - Multizone Unit VAV with Proportional Reheat Control

Occupied Mode: 

When the zone temperature is between the occupied heating and cooling setpoints (inside of the 

bias), the primary air damper is at the minimum cfm and mechanical heating is unavailable. When the zone 
temperature rises above the cooling setpoint, the primary air damper increases the cfm and mechanical heating is 
unavailable. When the zone temperature drops below the heating setpoint, the supplemental heating coil is fully 
used before the reheat coil enables. The damper is controlled to provide a minimum cfm.

Note:

The box reheat and supplemental reheat is a box option. If you select neither, you have a cooling only box.

Unoccupied Mode:

 When in unoccupied mode, if the zone temperature is between the unoccupied heating and 

cooling setpoints (inside of the bias), the primary air damper is at the minimum cfm and mechanical heating is 
unavailable. When the zone temperature rises above the unoccupied cooling setpoint, the primary air damper 
increases the cfm, if available, and mechanical heating is unavailable. When the zone temperature drops below the 
unoccupied heating setpoint, the supplemental heating coil is fully used before the reheat heat coil enables. The 
damper is at the minimum cfm.

Unit Enable: 

A network unit enable sign controls the box mode.

Fan Control (Optional):

 For parallel fans, upon a call for heat, the fan cycles on. For all other states, the fan is off. 

For Series fan, during the occupied mode the fan runs continuously. During the unoccupied mode, the fan cycles 
on with a call for heating or cooling.

Occupancy Lighting Switch (Optional): 

You can add an occupancy lighting switch to the box. This temporarily 

sets the VAV box to Standby mode when the occupancy is not sensed. When the box senses occupancy, the zone 
switches back to occupied. Standby mode uses standby temperature setpoints that are slightly higher or lower than 
the occupied cooling or heating setpoints, respectively. The VAV Box alos uses unoccupied flow setpoints in 
addition to the low standby temperatures.

Demand Control Ventilation (Optional): 

When Zone CO

2

 sensors are wired to the boxes to sense the air quality 

in the zone, the minimum damper flows are proportionally reset based on the air quality (CO

2

) setpoint. The reset 

of damper minimum flows does not exceed the maximum value you set. The CO

2

 sensor with the highest value 

determines the reset if more than one sensor is wired. 

ZEC Terminal Functions, Ratings, Requirements, and Wiring Guidelines

Input and Output Wiring Guidelines

Table 2 provides information about the functions, ratings, and requirements for the ZEC input and output terminals.

In addition to the wiring guidelines Table 2, observe these guidelines when wiring ZEC inputs and outputs:

Run all low-voltage wiring and cables separate from high-voltage wiring.

All input and output cables, regardless of wire size or number of wires, should consist of twisted, insulated, and 
stranded copper wires.

Shielded cable is not required for input or output cables.

Shielded cable is recommended for input and output cables that are exposed to high electromagnetic or radio 
frequency noise.

System and Zone Bus Supply Power Wiring Guidelines

Table 2 provides information about terminal block functions, ratings, and requirements.

In addition to the guidelines in Table 2, observe these guidelines when wiring the System/Zone Buses and supply 
power:

Run all low-voltage wiring and cables separate from high-voltage wiring.

All FC and SA Bus cables, regardless of wire size, should be twisted, insulated, stranded copper wire.

Shielded cable is strongly recommended for all FC and SA Bus cables.

Содержание ZEC410

Страница 1: ...ol system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the ZEC410 VAV contro...

Страница 2: ...ven surface whenever possible Use shims or washers to mount the ZEC securely and evenly on the mounting surface if necessary Mount the ZEC in an area free of corrosive vapors that matches the ambient...

Страница 3: ...it against the spacer 6 Locate the damper position using the typical marking on the end of the damper shaft Table 1 Verasys System Bus Controller Addressing System Bus Address Range Standalone Verasys...

Страница 4: ...d stop the closed end stop is set by the closed damper For 45 and 60 boxes hard stops must be provided at both full closed and full open damper positions By installing the ZEC controller at the full o...

Страница 5: ...op ration de r glage Veiller ne toucher aucune partie du circuit imprim lorsque celui ci est sous tension Le non respect de ces pr cautions peut provoquer des blessures graves voire mortelles IMPORTA...

Страница 6: ...modular SA Bus ports provide a connection for the VAV Balancing Tool The FC Bus port is not used in ZEC installations Figure 3 SA Bus Terminal Block Wiring Stranded 4 Wire 2 Twisted Pair Shielded Cab...

Страница 7: ...remental outputs for the heating control 2 Wire the network temperature sensor and CO2 sensor to the ZEC s SA Bus 3 Wire the FC Bus in a daisy chain 4 Ensure that the ZEC s device address DIP switches...

Страница 8: ...ZEC410 1 SUPHTG1 C Optional ZN T SA DA ZN CO2 Optional OCC S Optional DA T Optional HTG3 C Optional HTG2 C Optional E C HTG1 C Optional SF C SUPHTG1 C Optional ZN T SA RA DA ZN CO2 Optional OCC S Opt...

Страница 9: ...TAT IS SELECTED 24V COM 24V HOT SA PWR COM TO NEXT DEVICE FRO M LAST DEVICE MS TP MS TP Oc cupancy Sensor O LS 2100 1 CONNECTOR O N BACK OF SENSOR ZONE SENSOR ZN CO2 24V HOT COM SA PWR 24V COM SEE RIS...

Страница 10: ...e zone temperature drops below the unoccupied heating setpoint the supplemental heating coil is fully used before the reheat heat coil enables The damper is at the minimum cfm Unit Enable A network un...

Страница 11: ...ECTOR ON BACK OF SENSOR ZONE SENSOR ZN T IF NETSTAT IS SELECTED 24V COM 24V HOT SA PWR COM TO NEXT DEVICE FROM LAST DEVICE MS TP MS TP TO RE D WIRE OCCUP ANCY S WITCH TO BLACK WIRE OCCUP ANCY S WITCH...

Страница 12: ...ne temperature drops below the unoccupied heating setpoint the supplemental heating coil is fully used before the reheat heat coil enables The damper is at the minimum cfm Unit Enable A network unit e...

Страница 13: ...ONNECTTOAIR FLOWPROBE SF C OPTIONAL DA T DISCHARGEAIRTEMP OPTIONAL 24VHot 24VCom NOTE SUPPLEMENTALVALVESDEFAULTTOA 60 SECONDINCREMENTALACTUATOR THISIS ADJUSTABLEINVERASYS SUPHTG O OPTIONAL CW CCW COM...

Страница 14: ...rily sets the VAV box to Standby mode when the occupancy is not sensed When the box senses occupancy the zone switches back to occupied Standby mode uses standby temperature setpoints that are slightl...

Страница 15: ...than or equal to the intended device address to ON Then continue setting lower numbered switches until the total equals the intended address For example if the intended device address is 21 set Switc...

Страница 16: ...erature sensor 1k ohm nickel with temperature occupancy button TE 68NT 1N00S Wall temperature sensor 1k ohm nickel with warmer cooler W C adjustment and temperature occupancy pushbutton Zone CO2 Senso...

Страница 17: ...cally at the sensor Refer to the Verasys System User s Guide LIT 12012371 for more information CO2 Demand Controlled Ventilation DCV CO2 DCV ensures high Indoor Air Quality IAQ for the zone by using u...

Страница 18: ...f the bus for testing purposes and test the bus portion connected to the Zone Coordinator Correcting Physical Communication Bus Problems The communication bus is subject to a number of physical factor...

Страница 19: ...50 to 60 Hz Class 2 power supply or Safety Extra Low Voltage SELV at 50 60 Hz 20 VAC minimum Power Consumption 10 VA 14 VA maximum Ambient Conditions Ambient Operating Conditions 0 to 50 C 32 to 122 F...

Отзывы: