ZEC410 VAV Controllers Installation Instructions
16
To ensure the best bus performance, set sequential device addresses with no gaps in the device address range
(4, 5, 6, and so on). The field controllers do not need to be physically connected on the bus in their numerical
device address order.
4.
Write each field controller’s device address on the white label below the DIP switch block on the controller’s
cover.
Refer to the
MS/TP Communications Bus Technical Bulletin (LIT-12011034)
for more information on field controller
device addresses and how to set them on MS/TP Bus devices.
Accessories
Table 3 lists the ZEC controller accessories.
Operation
The ZEC controller is pre-programmed for the VAV box operating sequence as ordered. You do not need to
program the controller; however, you need to provide configuration information using either the Balancing Sensor
or the Zone Setup screen on the Verasys System Smart Building Hub.
For detailed information on Verasys
System, including dehumidification capability, DCV, occupancy sensing, and
general operating modes, refer to the Verasys
System Operation Overview Technical Bulletin (LIT-12012370)
.
Table 3: Zone Controller Accessories
Product Code
Number
Description
Zone Temperature Sensors (Hardwired)
TE-68NT-0N00S
Wall temperature sensor, 1k ohm, nickel with temperature occupancy button.
TE-68NT-1N00S
Wall temperature sensor, 1k ohm, nickel with warmer/cooler (W/C) adjustment and temperature
occupancy pushbutton.
Zone CO
2
Sensor
NS-BCN7004-0
BACnet network CO
2
sensor designed to function directly with Johnson Controls BACnet MS/TP digital
controllers, in a 80 mm x 120 mm (3 in. x 4.5 in.) enclosure with terminal block and modular jack wiring
connections.
Only addresses 212 to 214 are supported.
Second Zone Damper Actuator
1
1. You must purchase the actuator and add it to a damper without a ZEC310 controller.
M9106-GGA-2
6 n•m torque non-spring return damper actuator
Network Sensors for Zone Temperature
NS-BTB7003-0
Network sensor, 120 x 80 mm (4.7 x 3.1 in.), Johnson Controls® logo, local setpoint, terminals
NS-BTB7003-2
Network sensor, 120 x 80 mm (4.7 x 3.1 in.), no logo, local setpoint, terminals
NS-BTN7003-0
Network sensor, 120 x 80 mm (4.7 x 3.1 in.), no logo, no setpoint, terminals
NS-BTN7003-2
Network sensor, 120 x 80 mm (4.7 x 3.1 in.), no logo, no setpoint, terminals.
NS-BTP7002-0
Network sensor, 120 x 80 mm (4.7 x 3.1 in.), Johnson Controls logo, Warmer/Cooler adjustment,
terminals
NS-BTP7002-2
Network sensor, 120 x 80 mm (4.7 x 3.1 in.), no logo, warmer/cooler adjustment, terminals
Occupancy Lighting Switch
NS-BCN7004
Occupancy sensing light switch for control of indoor incandescent and fluorescent lights
RIBU1C
Enclosed relay for OLS-2100-1 sensor
Balancing Tool
NS-ATV7003-0
Handheld VAV balancing tool