Verasys® 32 Point 24 VAC Application Controller Installation Instructions

3

Do not mount the controller on surfaces prone to vibration, such as duct work.

Do not mount the controller in areas where electromagnetic emissions from other devices or wiring can 
interfere with controller communication.

Follow these additional guidelines when you mount a field controller in a panel or enclosure:

Mount the controller so that the enclosure walls do not prevent cover removal and obstruct ventilation through 
the controller.

Mount the controller so that the power transformer and other devices do not radiate excessive heat to the 
controller.

Do not install the controller in an airtight enclosure.

Use a zip-tie to secure the controller when you ship it.

Figure 1:  Verasys Application Controller mounting position

DIN Rail Mount Applications

Mounting the field controller horizontally on 35 mm DIN rail is the preferred mounting method.

To mount a field controller on 35 mm DIN rail, complete the following steps:

1.

Securely mount a 20 cm (8 in.) or longer section of a 35 mm DIN rail horizontally and centered in the appropriate 
space so that the controller mounts as in in Figure 1.

2.

Pull the two lower mounting clips outward from the controller to the extended position.

3.

Hang the controller on the DIN rail by the hooks at the top of the DIN rail channel on the back of the controller 
and position the controller snuggly  against the DIN rail.

4.

Zip tie the controller to the DIN rail when you ship.

5.

Push the bottom mounting clips inward (up) to secure  the controller on the DIN rail.

To remove the controller from the DIN rail, pull the  bottom mounting clips out to the extended position and 
carefully lift the controller off the DIN rail.             

IMPORTANT:

Do not overtighten the mounting screws.  Overtightening the screws may damage the mounting 

clips.

Horizontal Mount Position

Required for DIN Rail Mounting

Содержание LC-VAC300 0 Series

Страница 1: ...e devices and remote connectivity Verasys Smart Building Hub SBH compatible through the BACnet MSTP system bus connection Dedicated Sensor bus for Johnson Controls smart end devices Dedicated Modbus p...

Страница 2: ...the ambient condition requirements listed in Table 11 Ensure sufficient space around the controller for cable and wire connections for easy cover removal and good ventilation through the controller Pr...

Страница 3: ...field controller horizontally on 35 mm DIN rail is the preferred mounting method To mount a field controller on 35 mm DIN rail complete the following steps 1 Securely mount a 20 cm 8 in or longer sect...

Страница 4: ...Verasys 32 Point 24 VAC Application Controller Installation Instructions 4 Figure 2 Back of Controller Showing Extended Mounting Clips DIN Rail Channel and Mounting Dimensions mm in...

Страница 5: ...her aucune partie du circuit imprim lorsque celui ci est sous tension Le non respect de ces pr cautions peut provoquer des blessures graves voire mortelles Risk of Electric Shock Disconnect or isolate...

Страница 6: ...Table 5 and use a spade connector with screw terminals Figure 3 shows I O spade terminals Figure 3 Verasys Application Controller Spade Terminals Field Wiring For all I O terminals listed in Table 5 u...

Страница 7: ...the other field controllers in a daisy chain configuration using 3 wire twisted shielded cable as shown in the following figure See Table 7 for more information on functions ratings requirements and...

Страница 8: ...cts internally to the Sensor bus terminal block See Table 7 for more information The sensor bus port pin assignment is shown in Figure 8 Figure 8 Pin Number Assignments for Sensor Bus Ports on Verasys...

Страница 9: ...ne to many Modbus devices Each Modbus device has a unique Modbus Register table and you must configure it within the application of the Verasys Controller Figure 9 Modbus Terminal Block COM Cable Shie...

Страница 10: ...ngs for wiring details EOL Switch The red end of line switch EOL is located under the cover of the controller You can set the red EOL switch when the device is located at the end of the trunk or at th...

Страница 11: ...ut power for actuator supply 7 24 VAC class 2 power supply terminal block See the Supply Power Terminal Block section 8 Cover lift tabs 9 Sensor Bus Port RJ 12 6 pin Modular Jack See Sensor Bus Port s...

Страница 12: ...ype of Field Device Type of Input Output Termination Diagrams Resistive Input resistance temperature detector RTD Monitor UI Voltage Input External Source UI Voltage Input Internal Source UI Voltage I...

Страница 13: ...k from EPP 100 UI Dry Contact Binary Input UI BI Table 2 Termination Details Part 2 of 6 Type of Field Device Type of Input Output Termination Diagrams Controller FIELD DEVICE VDC Output 15V IN IN ICO...

Страница 14: ...e V e r a s y s 2 4 V A C S u p p ly a r e b o th g r o u n d e d to F u n c tio n a l E a r th e n s u r e th a t th e p h a s in g b e tw e e n th e tw o s u p p lie s a r e a lig n e d H O T Common...

Страница 15: ...f Input Output Termination Diagrams Common Power Calibration Output Current Input Voltage Input Feedback Terminal Block 1 1 2 3 4 5 6 OCOM OUT Controller 24 VAC COM 24 VAC HOT 24VAC Load OUT OCOM CONT...

Страница 16: ...and BO 7 Hardware Interlock Relays BO See Table 3 for Selectable Operating Modes Table 2 Termination Details Part 5 of 6 Type of Field Device Type of Input Output Termination Diagrams 240VAC Load OUT...

Страница 17: ...ing BO Relay 6 Open Short BO Relay 6 energizes when BI11 is Active 24 VAC present on BI11 7 J2 1 and J2 2 J2 2 and J2 3 Open Open BO Relays 7 remains de engerized in default state NO cannot be control...

Страница 18: ...ring and cables separate from high voltage wiring All input and output cables regardless of wire size or number of wires must consist of stranded insulated and twisted copper wires Shielded cable is n...

Страница 19: ...INn terminals provides 80 mA total current Note 80mA current limit is shared between the BI 15V supply and the UI 15V supply Same as Universal INn INn Analog Input Voltage Mode 0 10 VDC 10 VDC maximum...

Страница 20: ...al Mode 24 VAC Input Present Logic 1 Active ICOMn Binary Input Common for all Binary Input IN terminals 15 V 15 VDC Power Source for active 3 wire input devices connected to the Universal INn terminal...

Страница 21: ...Resistive 3A Inductive Cos phi 0 6 20 to 70 C 4 to 158 F 100K cycles The RELAY output terminals can accommodate the following maximum wire sizes Two wires per terminal 1 5 mm2 16 AWG maximum or One w...

Страница 22: ...y Commons Note Reference all relay commons to the same pole of the supply circuit PWM Output OUT5 PWM PWM Output User selectable PWM output voltage 5V 12V default and 15V 10 mA continuous current 100...

Страница 23: ...low voltage wiring and cables separate from high voltage wiring All Sensor and System bus cables regardless of wire size must be twisted insulated stranded copper wire Using shielded cable is best pra...

Страница 24: ...Signal Reference and 15 VDC Common 15 VDC 71 5 ohms at 4 W N A 24 AWG 3 pair CAT3 cable 30 5 m 100 ft Sensor Bus Terminal Lower Sensor Bus Communications 0 6 mm2 22 AWG stranded 4 wire 2 twisted pairs...

Страница 25: ...ces Not for use on field controllers 117 Reserved for SBH 4 to 127 Used for MS TP devices also known as field controllers that are hardwired to a Sensor and System bus Table 9 Status LEDs and Descript...

Страница 26: ...ted to Binary Outputs BOs or Configurable Outputs COs This can consume up to 12 VA for each BO or CO for a possible total consumption of an additional 60 VA maximum Ambient Conditions Operating 20 C t...

Страница 27: ...0 mV accuracy in 0 to 10 VDC applications Terminations Input Output Fixed Spade terminals Sensor System Modbus 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Sensor Bus Tool Port RJ 12 6 Pin Modula...

Страница 28: ...f their respective owners 2018 Johnson Controls www johnsoncontrols com 28 European Single Point of Contact NA SA Single Point of Contact APAC Single Point of Contact JOHNSON CONTROLS WESTENDHOF 3 451...

Отзывы: