Verasys® 32 Point 24 VAC Application Controller Installation Instructions
20
BINARY
(Inputs)
(Dry)
INn
Binary Input - Dry Contact
Maintained Mode
0.01 second minimum pulse width
Internal 17 V. 100k ohm pull-up
See Guideline
A
Binary Input - Pulse Counter/
Accumulator Mode
0.01 second minimum pulse width
(50 Hz at 50% duty cycle)
Internal 17 V. 100k ohm pull-up
ICOMn
Binary Input Common
for all Binary
Input (IN) terminals
Note:
Binary ICOM
n
are all internally
interconnection and interconnected
with the controller’s power supply
COM. (ICOM1-2-3, ICOM4-5-6,
ICOM7-12, and COM).
BINARY
(Inputs)
(24VAC non-
critical)
INn
Binary Input - 24 VAC Non-Critical
Mode
24 VAC Input Present: Logic 1
(Active)
ICOMn
Binary Input Common
for all Binary
Input (IN) terminals
+15 V
15 VDC Power Source
for active
(3-wire) input devices connected to
the Universal IN
n
terminals;
provides 80 mA total current.
Note:
80mA current limit is shared
between the BI + 15V supply and the
UI + 15V supply.
Same as Binary
INn
Note:
Use 3-wire cable for devices
that source power from the +15V
terminal.
COM
15 VDC Power Source
for active
(3-wire) input devices connected to
the Universal IN
n
terminals;
provides 80 mA total current.
Note:
80mA current limit is shared
between the BI + 15V supply and the
UI + 15V supply.
Same as Binary
INn
Table 5: Controller Terminal Blocks, Functions, Ratings, Requirements, and Cables (Part 2 of 4)
Terminal Block
Label
Terminal Label
Function, Ratings, Requirements
Determine Wire Size and Maximum
Cable Length
1