Verasys® 32 Point 24 VAC Application Controller Installation Instructions
26
Accessories Ordering Information
Repair Information
If the Verasys controllers fail to operate within their specifications, replace the controller. For a replacement
controller, contact your local Verasys representative.
Technical Specifications
Table 10: Accessories Information
Product Code Number
Description
PK-KIT3210-0
Removable terminal block kit for all spade connections
Table 11: LC-VAC300x-0 (Part 1 of 2)
Product Code Numbers
LC-VAC300x-0 Controller 24 Volts with Display
Supply Voltage
24 VAC, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2
(North America), Safety Extra-Low Voltage (SELV) (Europe).
Power Consumption
20 VA maximum
Note:
VA rating does not include any power supplied to the peripheral devices connected to
Binary Outputs (BOs) or Configurable Outputs (COs). This can consume up to 12 VA for each
BO or CO; for a possible total consumption of an additional 60 VA (maximum).
Ambient Conditions
Operating:
-20°C to 70°C (-4°F to 158°F); 10% to 95% Relative Humidity (RH)
noncondensing; Pollution Degree 2.
Storage:
-40°C to 85°C (-40°F to 185°F); 5% to 95% RH noncondensing.
Addressing
BACnet® MS/TP:
Valid field controller device addresses 4–127. Device addresses
0
–3 and 128–255 are reserved and not valid field controller addresses.
N2:
Valid field controller device addresses 1 to 255.
Communications Bus
BACnet® MS/TP, MODBUS and N2 through RS-485:
•
3-wire System Bus between the supervisory controller and field controller addresses.
•
3-wire Sensor Bus between controller, network sensors and other sensor/actuator
devices, includes a lead to source 15 VDC supply power from controller to bus devices.
•
3-wire one Modbus communication half-duplex (RTU port).
Processor
RX631 Renesas® 32-bit microcontroller.
Memory
16 MB flash memory and 8 MB RAM.