7
www.ventilation-system.com
Technical data for cooling mode:
Model
Air flow [m
3
/h]
Intake air
temperature
[°С]
Temperature difference 90/70 °C
Power [kW]
Output temperature
[°C]
Water flow [m
3
/h]
Water pressure loss
[kPa]
AOW 25
2200
35
9.1
26.0
1.6
7.5
30
5.8
22.5
1.0
6.1
25
3.2
21.0
0.6
2.1
20
2.0
18.0
0.3
0.9
AOW 30
3000
35
11.4
27.0
2.0
11.2
30
7.3
22.9
1.3
5.0
25
3.9
21.1
0.7
1.6
20
2.4
17.7
0.4
0.7
AOW 45
3850
35
18.0
24.9
3.1
31.8
30
10.8
21.7
1.9
12.9
25
7.3
19.0
1.3
6.3
20
3.2
17.4
0.5
1.4
Note
:
The AOW1 and AOW1z unit models are not designed for cooling as they are not equipped with elements necessary for condensate
removal.
1 – heat exchanger
2 – axial fan with a protecting grille
3 – casing
4 - louvre shutters
5 – terminal box
6 – heat exchanger spigots
AOW
H
4
1
B
5
2
L 1
L
3
6
К
43
H1
B1
Overall dimensions:
Model
Dimensions [mm]
Number of pipe rows
Weight
[kg]
B
B1
H
H1
L
L1
K
AOW 25
680
785
605
468
360
286
G 3/4"
2
37.0
AOW 30
680
785
655
518
360
286
G 3/4"
2
40.0
AOW 45
780
885
710
570
380
300
G 3/4"
2
50.0