INSTALLATION OF THE UNIT WITH AN MKP-AOW MOUNTING SET
The MKP-AOW mounting set (not included in the delivery set) is used for ceiling mounting of the unit by means of the mounting studs
or chains.
INSTALLATION OF THE UNIT WITH MKP-AOW
min 300 mm
Mounting stud
INSTALLATION OF THE UNIT WITH AN MKU-AOW MULTI-ANGLE BRACKET
The MKU-AOW mounting multi-angle bracket (not included in the delivery set) is used for ceiling or wall mounting of the unit.
The MKU-AOW bracket design enables wall or ceiling installation of the unit at the angle of 30° and 45°.
RIGHT ANGLE MOUNTING WITH MKU-
AOW
30° MOUNTING WITH MKU-AOW
45° MOUNTING WITH MKU-AOW
30°
45°
UNIT REACH DISTANCE
Failure to provide the minimum distance of 0.3 mm to walls or ceiling will impair the unit aerodynamic and thermal characteristics as
well as service life of the unit.
Wall mounting
Minimum distance to the wall is 0.3 m.
Mounting height is from 3 to 8 m.
Maximum air blowing range is 16 m.
Ceiling mounting
Minimum distance to the ceiling is 0.3 m.
Mounting height is from 4 to 14 m.
16 m
3-
8
m
4-14 m
16
m