Sub menu 3 – Time 
After entering this menu, the value of the hour will 
start blinking. Using the 

 and 

 buttons, this 

value can be changed. When this is set correctly, it 
can  be  confirmed  by  pressing  the 

  button. 

Now  the  minutes  value  will  start  blinking,  which 
can  be  set  in  the  same  way  as  the  hour  value. 
When  this  is  set  correctly,  it  is  confirmed  by 
pressing 

.  Now  it  will  return  to  the  time  sub 

menu, and the specified time can be checked. 
 
Sub menu 4 – Date 
After  selection  of  the  sub  menu  with  the 

 

button, this sub menu can be changed by pressing 
the 

  button.  The  day  number  will  now  start 

blinking. Using the 

 and 

 buttons, the value 

can be adjusted until the correct value is obtained. 
The 

  button  will  confirm  your  setting.  Now 

the  month  number  will  start  blinking.  This  can  be 
set in the same way as the day number. When the 
month number is confirmed by pressing 

, the 

year  number  will  start  blinking.  This  can  be  set  in 
the same way as the day- and year number. When 
this is confirmed by pressing 

, it will return to 

the date sub menu, and the specified date can be 
checked. 
 
Sub menu 5 – Pump test 
In  this  sub  menu,  the  pump  can  be  tested.  The 
usefulness  will  be  explained  later  in  this  section. 
This  menu  can  be  selected  by  pressing  the 

 

button from the main menu. The display will show: 
'Pump test?'. When 

 is pressed, the pump will 

be  activated  for  30  seconds,  independent  of  the 
measured  temperatures.  After  30  seconds,  the 
display  will  show  'Pump  test  end',  which  can  be 
confirmed by pressing the 

 button again, and 

it will return to the sub menu pump test.  
 
Sub menu 6 – Code menu 
This  menu  is  to  be  used  solely  by  the  installer. 
Entering  the  correct  code  will  grant  access  to  the 
sensitive system settings. Read section 4.2.1 if you 
are  interested  in  what  your  installer  can  set  for 
you.  Make  sure  your  installer  is  aware  of  the 
settings  of  the  ventilation  equipment.  The 
ventilation  settings  will  influence  the  settings  of 
the Aquacom. 
 

3.2 Tips for using the Aquacom 

From  the  moment  the  Aquacom  is  attached  to 
your  ventilation  system,  there  are  several 
situations  which  should  be  taken  into  account 
while using the unit. 
-

 

The  ventilation  equipment  will  determine  the 
amount  of  air  which  will  be  drawn  (through 

the  Aquacom  unit).  When  this  amount  is 
higher,  more  ground  energy  will  be 
transferred to the ventilation air. The achieved 
temperature  rise  or  drop  however  will  be 
lower. 

-

 

When  the  Aquacom  is  turned  off,  the  heat 
exchanger can freeze during outside air winter 
conditions  and  a  high  ventilation  flow.  Never 
unplug  the  unit  from  the  wall  socket, 
otherwise  the  frost  protection  will  not  work. 
Also make sure enough anti-freeze is added to 
the water. 

-

 

For  extreme  winter  temperatures  (<  -15°C) 
and  a  high  ventilation  flow,  the  heat 
exchanger  can  freeze.  When  extreme  low 
temperatures  occur,  never  use  the  highest 
ventilation mode. 

-

 

When the heat recovery unit is engaged in the 
'summer  exitair  only'  mode,  no  air  is  drawn 
and the Aquacom will not have any effect. 

-

 

When  the  ground  temperature  will  not  have 
any  useful  effect,  the  Aquacom  will  disable 
itself. It will also enable itself by itself. 

-

 

Do  not  adjust  the  (potential)  bypass 
temperature  of  the  heat  recovery  unit.  This 
temperature  ensures  no  condensation  will 
appear in the system. 

-

 

The  Aquacom  unit  will  every  two  weeks  at 
least turn on  for two  minutes  when the plug 
in the wall socket. This will prevent the pump 
from forming rust and getting stuck. 

 

3.3 Maintenance by the user 

Major maintenance of the Aquacom should 
always be performed by a qualified installer. 
Do  not  try  to  perform  this  as  an  end  user. 

When performing the requirements below, make 
sure the plug is removed from the wall socket. 
 

We  recommend  to  commit  every  two  years  the 
following  the  major  maintenance  on  your 
ventilation unit: 
-

 

Check  the  fins  of  the  heat  exchanger  for 
damage 

-

 

Clean the heat exchanger 

-

 

Clean the drain 

-

 

Check the pump operation 

-

 

Check  (and  if  necessary  repair)  the  electrical 
wiring. 

-

 

Check the system pressure 

-

 

Check the glycol content 

In addition, we recommend cleaning the duct 
system every six years. 
 
Aquacom maintenance for the end user limits itself 
to  cleaning  and  replacing  the  filter.  Also  the 

Содержание Comair Aquacom

Страница 1: ......

Страница 2: ...rights reserved The information and instructions in this manual are subject to print errors and misspelling No rights can be derived from the information contained herein Version 2 0 Ventilair Group Nederland ...

Страница 3: ...rnal fan 15 4 3 Operation of the control unit 15 4 3 1 Operation of the control unit during summer operation 15 4 3 2 Operation of the control unit during winter operation 15 4 3 4 Pump protection 15 4 4 Maintenance by the installer 15 4 4 1 Pressurizing 15 4 4 2 Check the glycol content 16 4 4 3 Check the heat exchanger 16 4 4 4 Cleaning the heat exchanger block 16 4 4 5 Cleaning the drain 16 4 4...

Страница 4: ...nd mechanical extraction of contaminated air The amount of supplied and extracted air is adjusted by the valves That is why it is important to keep the same settings of the valves and to keep the valves at the same place It is also important that air can circulate well in the house so make sure that openings under doors are not sealed or reduced Cross flow heat exchanger The heat exchanger is the ...

Страница 5: ...s If the house is cooler than outside the heat is kept out by the heat exchanger The main advantage of this mechanical ventilation system is that the energy from the exhaust air is used to heat or cool fresh air This represents substantial energy and cost reduction compared to natural ventilation or system C To preheat the fresh supply air during wintertime a ground heat exchanger is applied This ...

Страница 6: ...The warranty on the unit expires if 1 The warranty has expired 2 The installation use and or maintenance does not meet the requirements listed in this guide 3 Major maintenance on the unit was committed by an unauthorized maintenance technician 4 There are signs of abuse or modifications on the device 5 Changes to the system have been made after completion of the installation 6 Improper tubing is ...

Страница 7: ...er failure occurs Aquacom will restart in the same mode in which it was before the power failure These buttons can be used to select the sub menus in the main menu In the different sub menus the values can be changed using these buttons This button is used to confirm your choice in a sub menu The control panel will remain in the sub menu of your choice until you change this yourself The display ho...

Страница 8: ... moment the Aquacom is attached to your ventilation system there are several situations which should be taken into account while using the unit The ventilation equipment will determine the amount of air which will be drawn through the Aquacom unit When this amount is higher more ground energy will be transferred to the ventilation air The achieved temperature rise or drop however will be lower Whe...

Страница 9: ...he plate on which the filter rests Possibly there are larger contaminations like stones and leaves Put in the new filter If there is an arrow on the filter this needs to point in the direction of the heat exchanger Close the front cover with the clip attachments on top Reconnect the plug of the external ventilation unit Reconnect the plug of the Aquacom unit Record the date of a possible filter re...

Страница 10: ...threads on the other side exchange the brackets of the side and place back the rings the cap nuts and the rubber caps Check whether the brackets are attached correctly and whether its positions are correct Remove both covers which are fixed by the clip closures Remove the cable of the control unit from the cable tie attached to the sheet metal Remove the three screws with which the control units h...

Страница 11: ...duct Make sure the duct will not be damaged Check whether there are no damages to the exterior of the ducts before replacing the soil Make sure the hose nowhere is lifted Air can accumulate here reducing the efficiency of the duct network Isolate vertical pieces of the hose up to the house In this way no large temperature gradient will be present which could cause the temperature of the glycol wat...

Страница 12: ... counterclockwise After this you change the sprout and lid and reattach them by turning them clockwise Place the inlet of fresh air preferably on the shady side of the house this way you avoid to supply extremely hot air in the summer Note also that the inlet of fresh air is placed sufficiently far from a flue exhaust according to local standards Also consider compound boundary rules and make sure...

Страница 13: ...is mounted and the system is filled the control unit has to be set Check again that all air pipes and electrical connections are connected properly 4 2 1 Setting the Aquacom In this part of the manual sub menu 6 will be explained further For setting the first five sub menus and the explanation of the buttons you are referred to section 3 1 Submenu 6 Code menu This menu is only intended for qualifi...

Страница 14: ...ny effect anymore on the operation of the Aquacom If the temperature after the heat exchanger will not rise by 0 5 C in 10 minutes the unit will display the error Tempdiff 0 5K This error message has to be removed manually by pressing one of the buttons Also see section 5 2 4 6 5 P summer This submenu enables you to set the reaction speed of the pump during summer operation using the P factor When...

Страница 15: ...om T2 Aquacom 4 3 2 Operation of the control unit during winter operation If the measured outside temperature is lower than the temperature set by T winter the pump will be enabled If there is only a small amount of heat required the pump will start switching on and off Every three minutes the pump will be activated for X percent of the time The percentage X for the time the pump is active each th...

Страница 16: ...eck the heat exchanger Open the front cover Then check if the fins are not bent and or the seams are not open Also check whether the copper tubes are not bent or leaking 4 4 4 Cleaning the heat exchanger block Open the front cover using the clip closures at the top of the unit Then remove the dust between the fins with a vacuum cleaner and brush Wipe gently with a brush between the fins If necessa...

Страница 17: ...e message is shown until the error is repaired If the pump has stopped it is not necessary an error First check the operation of the pump using the pump test as described in submenu 4 in section 3 1 When the error is repaired clear the error messages list Note for the installer If an error does not satisfy the next table s content use scheme 5 2 1 Error number Description Action Scheme 10 Short ci...

Страница 18: ...lace the control unit and place the plug back in the socket The error is tempo rarily fixed pay attention to whether new errors occur Pull the plug out of the socket Pull the plug out of the socket Replace the fuse at the control unit Put the plug back into the socket If the fuse breaks again pull the plug out of the socket and check all internal wiring Put the plug back in the socket Replace the ...

Страница 19: ...ing the clip locks and open the control unit Is the cable broken Yes Nee Replace the control unit and put the plug back in the socket Place a new sensor or repair the cable and put the plug back in the socket Pull the plug out of the socket Pull the plug out of the socket Temporarily change the wires of sensors T1 and T2 and restart the unit Place a new sensor in the right place and put the plug b...

Страница 20: ...lace the control unit and put the plug back in the socket Pull the plug out of the socket This scheme is meant for the installer only Maintenance performed by the end user is not only dangerous but also has disadvantageous conse quences for the warranty ...

Страница 21: ...lf that the glycol water mixture is protected good enough against freezing Wait for better weather Is there 230V on the pump No Yes Check whether all valves in the circuit are open and whether the pressure is high enough If so replace the pump Replace the control unit This scheme is meant for the installer only Maintenance performed by the end user is not only dangerous but also has disadvantageou...

Страница 22: ...d aluminum cross flow Air specifications Air filter class G4 Air resistance See figure below Electrical specifications Electrical connection 230V AC 10 50Hz Pump Wilo Stratos Pico A Power usage 8W Max 40W Current 0 44A Fuse 2A slow Control Aquacom control panel Deluxe 0 5 10 15 20 25 30 35 40 45 0 50 100 150 200 250 300 350 400 450 500 550 Pressure drop Pa Flow m hour Pressure drop Aquacom With in...

Страница 23: ...side will be switched All measures are in mm TNV Supply towards fan TVB Supply from outside 6 3 List of components 1 Heat exchanger 2 Temperature sensors a Air towards fan T2 b Air from outside T1 3 Filling unit 4 Pump 5 Flow meter 6 Expansion vessel 7 Filter 8 Mano meter 9 Automatic vent 10 Control unit 11 Mounting brackets 12 Electrical connection 13 Compression fitting water duct supply 14 Comp...

Страница 24: ...skets 1 Heat exchanger 1230715 1x 1 2 Temperature sensor 2 stuks 2070049 3 Filling unit 1230710 2x 1 4 Pump 1230712 2x 1 5 Flow meter 1230713 2x 1 6 Expansion vessel 1230733 1x 7 Filter G4 1230738 8 Mano meter 1230716 Teflon tape 9 Automatic vent 1230780 10 Control unit 1230781 13 Compression fitting water duct supply 1230750 1x 14 Compression fitting water duct extract 1230750 1x 1 Gasket 1230647...

Страница 25: ... completely Measure the length of the top of the coupling to the fender and draw this point on the PE duct Push the PE duct in the coupling up to the fender so the previously made mark coincides with the green head To make the assemblation easier the end of the duct can be wetted or lubricated with a KIWA approved lubricant Screw the coupling nuts by hand using enough force Make sure you do not tu...

Страница 26: ...r Check whether the manometer shows the correct pressure This should be between 0 8 and 1 bar Check whether the flow meter shows a flow Make sure the pump is turned on Watch out for the wiring and possible parts through which current might be flowing If the pump is inactive use the function pump test as described in section 3 1 submenu 4 The flow should amount 6 l min If the pump is active and the...

Страница 27: ...of the socket of both the Aquacom and the eternal fan Close the front cover and put the plug back into the socket of both the Aquacom and the external fan Replace the filter make sure the arrow on the filter points towards the heat exchanger Clean the sheet metal on which the filter rests ...

Страница 28: ...ion 2 6 3 3 and 4 4 need to be taken into account or the warranty will expire The maintenance actions for the installer consist of the following parts 1 Replace filters 2 Straighten the fins of the heat exchanger 3 Cleaning the heat exchanger block 4 Cleaning the condensate drain 5 Check the pump operation 6 Repairing damage to electrical wiring 7 Pressurizing system and expansion vessel 8 Checkin...

Страница 29: ...e after 10 years Pump operating hours winter summer Date Installer name Address Phone number Remarks Maintenance after 12 years Pump operating hours winter summer Date Installer name Address Phone number Remarks Maintenance after 14 years Pump operating hours winter summer Date Installer name Address Phone number Remarks Maintenance after 16 years Pump operating hours winter summer Date Installer ...

Страница 30: ...ir Group Nederland B V Kerver 16 5521 DB Eersel The Netherlands Tel 31 0 497 36 00 31 Fax 31 0 497 33 08 93 www comair nl info comair nl Your Aquacom installer Date Installer name Address Phone number Remarks ...

Отзывы: