Route  the  garden  hoses  to  the  container  in 
which  the  glycol  water  mixture  has  been 
mixed, like in the image below: 

 

-

 

Using  the  submersible  pump,  fill  the  system 
with the glycol-water mixture. The transparent 
return  hose  will  show  whether  many  air 
bubbles are still present. 

-

 

When  during  30  minutes  hardly  any  air 
bubbles  return,  lock  the  return  valve  on  the 
filling  unit  (6)  and  let  the  pressure  rise  up  to 
maximum 1 bar. The pressure is shown by the 
manometer.  When  the  operation  pressure  is 
reached, also close the supply valve(5) on the 
filling unit, and turn off the submersible pump. 

-

 

Remove  the  garden  hoses  and  drain  the 
surplus in the container. 

-

 

Open the cap of the automatic vent. 

-

 

Open valve number one. 

-

 

Plug  in  the  Aquacom  in  the  wall  socket  and 
make  sure  the  pump  starts  working.  If 
necessary  use  the  function  pump  test  as 
described in section 3.1, sub menu 4. See after 
30 minutes whether the operation pressure is 
maintained. If this has dropped too far, either 
the system contained too much air or there is 
a leakage. 

-

 

If  the  pressure  is  too  low,  you  will  refill  the 
system again, using the same steps, up to the 
operation  pressure  and  test  it  again  for  30 
minutes.  If  the  pressure  again  decreases  and 
there  is  no  visible  leakage,  the  duct  system 
leaks and needs to be replaced. 

-

 

The rest of the glycol water can be handed in 
at a recycling center. 

 

4.2 Setting the Aquacom 

Once the unit is mounted and the system is filled, 
the control unit has to be set. Check again that all 
air  pipes and electrical connections are connected 
properly.  
 

4.2.1 Setting the Aquacom 

In  this  part  of  the  manual,  sub  menu  6  will  be 
explained  further.  For  setting  the  first  five  sub 
menus and the explanation of the buttons, you are 
referred to section 3.1. 
 
Submenu 6 - Code menu 
This  menu  is  only  intended  for  qualified  installers 
and requires a code. Contact your dealer to obtain 
this  code.  Select  submenu  p4  code  with 

  from 

the main menu and press 

 twice. Next you can 

change  the  first  digit  using  the 

  and 

 

buttons.  You  can  confirm  the  input  by  pressing 

 again and you can fill in the next field. If the 

code  is  incorrect,  the  display  will  return  to  its 
original state. If the code is correct, you will enter 
the main menu. The following sub menus can now 
be selected: 
 

Submenu 

Description 

Factorys
etting. 

6.1 T summer 

Set switching point 
summer 

23°C 

6.2 T2 Aquacom 

Set switching point 
cold protection 

18°C 

6.3 T winter 

Set switching point 
winter 

2°C 

6.4 Frost limit 

Set frost limit 

-10 

6.5 P summer 

Set control unit 
summer sensitivity 

13°C 

6.6 P winter 

Set control unit winter 
sensitivity 

13°C 

6.7 English language 

Set language 

NL 

6.8 Calibrate 
sensors? 

Equalize sensor 
temperatures 

6.9 Operating hours 

Display number of 
operating hours  

6.10 Old errors 

Display old errors  

 
Use the 

 and 

 buttons to select a submenu. 

Use the 

 button to enter the selected  menu. 

As  long  as  a  menu  is  not  confirmed,  the  value  is 
displayed at which the selected menu is set now. If 
you wait for 15 seconds you will exit the menu. 
 
 
 
 
 
 
 

Содержание Comair Aquacom

Страница 1: ......

Страница 2: ...rights reserved The information and instructions in this manual are subject to print errors and misspelling No rights can be derived from the information contained herein Version 2 0 Ventilair Group Nederland ...

Страница 3: ...rnal fan 15 4 3 Operation of the control unit 15 4 3 1 Operation of the control unit during summer operation 15 4 3 2 Operation of the control unit during winter operation 15 4 3 4 Pump protection 15 4 4 Maintenance by the installer 15 4 4 1 Pressurizing 15 4 4 2 Check the glycol content 16 4 4 3 Check the heat exchanger 16 4 4 4 Cleaning the heat exchanger block 16 4 4 5 Cleaning the drain 16 4 4...

Страница 4: ...nd mechanical extraction of contaminated air The amount of supplied and extracted air is adjusted by the valves That is why it is important to keep the same settings of the valves and to keep the valves at the same place It is also important that air can circulate well in the house so make sure that openings under doors are not sealed or reduced Cross flow heat exchanger The heat exchanger is the ...

Страница 5: ...s If the house is cooler than outside the heat is kept out by the heat exchanger The main advantage of this mechanical ventilation system is that the energy from the exhaust air is used to heat or cool fresh air This represents substantial energy and cost reduction compared to natural ventilation or system C To preheat the fresh supply air during wintertime a ground heat exchanger is applied This ...

Страница 6: ...The warranty on the unit expires if 1 The warranty has expired 2 The installation use and or maintenance does not meet the requirements listed in this guide 3 Major maintenance on the unit was committed by an unauthorized maintenance technician 4 There are signs of abuse or modifications on the device 5 Changes to the system have been made after completion of the installation 6 Improper tubing is ...

Страница 7: ...er failure occurs Aquacom will restart in the same mode in which it was before the power failure These buttons can be used to select the sub menus in the main menu In the different sub menus the values can be changed using these buttons This button is used to confirm your choice in a sub menu The control panel will remain in the sub menu of your choice until you change this yourself The display ho...

Страница 8: ... moment the Aquacom is attached to your ventilation system there are several situations which should be taken into account while using the unit The ventilation equipment will determine the amount of air which will be drawn through the Aquacom unit When this amount is higher more ground energy will be transferred to the ventilation air The achieved temperature rise or drop however will be lower Whe...

Страница 9: ...he plate on which the filter rests Possibly there are larger contaminations like stones and leaves Put in the new filter If there is an arrow on the filter this needs to point in the direction of the heat exchanger Close the front cover with the clip attachments on top Reconnect the plug of the external ventilation unit Reconnect the plug of the Aquacom unit Record the date of a possible filter re...

Страница 10: ...threads on the other side exchange the brackets of the side and place back the rings the cap nuts and the rubber caps Check whether the brackets are attached correctly and whether its positions are correct Remove both covers which are fixed by the clip closures Remove the cable of the control unit from the cable tie attached to the sheet metal Remove the three screws with which the control units h...

Страница 11: ...duct Make sure the duct will not be damaged Check whether there are no damages to the exterior of the ducts before replacing the soil Make sure the hose nowhere is lifted Air can accumulate here reducing the efficiency of the duct network Isolate vertical pieces of the hose up to the house In this way no large temperature gradient will be present which could cause the temperature of the glycol wat...

Страница 12: ... counterclockwise After this you change the sprout and lid and reattach them by turning them clockwise Place the inlet of fresh air preferably on the shady side of the house this way you avoid to supply extremely hot air in the summer Note also that the inlet of fresh air is placed sufficiently far from a flue exhaust according to local standards Also consider compound boundary rules and make sure...

Страница 13: ...is mounted and the system is filled the control unit has to be set Check again that all air pipes and electrical connections are connected properly 4 2 1 Setting the Aquacom In this part of the manual sub menu 6 will be explained further For setting the first five sub menus and the explanation of the buttons you are referred to section 3 1 Submenu 6 Code menu This menu is only intended for qualifi...

Страница 14: ...ny effect anymore on the operation of the Aquacom If the temperature after the heat exchanger will not rise by 0 5 C in 10 minutes the unit will display the error Tempdiff 0 5K This error message has to be removed manually by pressing one of the buttons Also see section 5 2 4 6 5 P summer This submenu enables you to set the reaction speed of the pump during summer operation using the P factor When...

Страница 15: ...om T2 Aquacom 4 3 2 Operation of the control unit during winter operation If the measured outside temperature is lower than the temperature set by T winter the pump will be enabled If there is only a small amount of heat required the pump will start switching on and off Every three minutes the pump will be activated for X percent of the time The percentage X for the time the pump is active each th...

Страница 16: ...eck the heat exchanger Open the front cover Then check if the fins are not bent and or the seams are not open Also check whether the copper tubes are not bent or leaking 4 4 4 Cleaning the heat exchanger block Open the front cover using the clip closures at the top of the unit Then remove the dust between the fins with a vacuum cleaner and brush Wipe gently with a brush between the fins If necessa...

Страница 17: ...e message is shown until the error is repaired If the pump has stopped it is not necessary an error First check the operation of the pump using the pump test as described in submenu 4 in section 3 1 When the error is repaired clear the error messages list Note for the installer If an error does not satisfy the next table s content use scheme 5 2 1 Error number Description Action Scheme 10 Short ci...

Страница 18: ...lace the control unit and place the plug back in the socket The error is tempo rarily fixed pay attention to whether new errors occur Pull the plug out of the socket Pull the plug out of the socket Replace the fuse at the control unit Put the plug back into the socket If the fuse breaks again pull the plug out of the socket and check all internal wiring Put the plug back in the socket Replace the ...

Страница 19: ...ing the clip locks and open the control unit Is the cable broken Yes Nee Replace the control unit and put the plug back in the socket Place a new sensor or repair the cable and put the plug back in the socket Pull the plug out of the socket Pull the plug out of the socket Temporarily change the wires of sensors T1 and T2 and restart the unit Place a new sensor in the right place and put the plug b...

Страница 20: ...lace the control unit and put the plug back in the socket Pull the plug out of the socket This scheme is meant for the installer only Maintenance performed by the end user is not only dangerous but also has disadvantageous conse quences for the warranty ...

Страница 21: ...lf that the glycol water mixture is protected good enough against freezing Wait for better weather Is there 230V on the pump No Yes Check whether all valves in the circuit are open and whether the pressure is high enough If so replace the pump Replace the control unit This scheme is meant for the installer only Maintenance performed by the end user is not only dangerous but also has disadvantageou...

Страница 22: ...d aluminum cross flow Air specifications Air filter class G4 Air resistance See figure below Electrical specifications Electrical connection 230V AC 10 50Hz Pump Wilo Stratos Pico A Power usage 8W Max 40W Current 0 44A Fuse 2A slow Control Aquacom control panel Deluxe 0 5 10 15 20 25 30 35 40 45 0 50 100 150 200 250 300 350 400 450 500 550 Pressure drop Pa Flow m hour Pressure drop Aquacom With in...

Страница 23: ...side will be switched All measures are in mm TNV Supply towards fan TVB Supply from outside 6 3 List of components 1 Heat exchanger 2 Temperature sensors a Air towards fan T2 b Air from outside T1 3 Filling unit 4 Pump 5 Flow meter 6 Expansion vessel 7 Filter 8 Mano meter 9 Automatic vent 10 Control unit 11 Mounting brackets 12 Electrical connection 13 Compression fitting water duct supply 14 Comp...

Страница 24: ...skets 1 Heat exchanger 1230715 1x 1 2 Temperature sensor 2 stuks 2070049 3 Filling unit 1230710 2x 1 4 Pump 1230712 2x 1 5 Flow meter 1230713 2x 1 6 Expansion vessel 1230733 1x 7 Filter G4 1230738 8 Mano meter 1230716 Teflon tape 9 Automatic vent 1230780 10 Control unit 1230781 13 Compression fitting water duct supply 1230750 1x 14 Compression fitting water duct extract 1230750 1x 1 Gasket 1230647...

Страница 25: ... completely Measure the length of the top of the coupling to the fender and draw this point on the PE duct Push the PE duct in the coupling up to the fender so the previously made mark coincides with the green head To make the assemblation easier the end of the duct can be wetted or lubricated with a KIWA approved lubricant Screw the coupling nuts by hand using enough force Make sure you do not tu...

Страница 26: ...r Check whether the manometer shows the correct pressure This should be between 0 8 and 1 bar Check whether the flow meter shows a flow Make sure the pump is turned on Watch out for the wiring and possible parts through which current might be flowing If the pump is inactive use the function pump test as described in section 3 1 submenu 4 The flow should amount 6 l min If the pump is active and the...

Страница 27: ...of the socket of both the Aquacom and the eternal fan Close the front cover and put the plug back into the socket of both the Aquacom and the external fan Replace the filter make sure the arrow on the filter points towards the heat exchanger Clean the sheet metal on which the filter rests ...

Страница 28: ...ion 2 6 3 3 and 4 4 need to be taken into account or the warranty will expire The maintenance actions for the installer consist of the following parts 1 Replace filters 2 Straighten the fins of the heat exchanger 3 Cleaning the heat exchanger block 4 Cleaning the condensate drain 5 Check the pump operation 6 Repairing damage to electrical wiring 7 Pressurizing system and expansion vessel 8 Checkin...

Страница 29: ...e after 10 years Pump operating hours winter summer Date Installer name Address Phone number Remarks Maintenance after 12 years Pump operating hours winter summer Date Installer name Address Phone number Remarks Maintenance after 14 years Pump operating hours winter summer Date Installer name Address Phone number Remarks Maintenance after 16 years Pump operating hours winter summer Date Installer ...

Страница 30: ...ir Group Nederland B V Kerver 16 5521 DB Eersel The Netherlands Tel 31 0 497 36 00 31 Fax 31 0 497 33 08 93 www comair nl info comair nl Your Aquacom installer Date Installer name Address Phone number Remarks ...

Отзывы: