14
6.1 T summer
When this menu is chosen, it is possible to change
this value between 11 and 30 °C. The entered value
is confirmed by pressing
. As soon as the air
temperature before the heat exchanger is higher
than this value, the Aquacom will start up. When
the measured outside temperature gets lower, the
Aquacom will turn itself off until a switching point
is reached again. Summer operation is not
dependent on the date.
6.2 T2 Aquacom
When this menu is chosen, it is possible to change
this value between 11 and 22 °C. The entered value
is confirmed by pressing
. As soon as the air
temperature after the heat exchanger during
summer operation is lower than this value, the
Aquacom will turn itself off. This way the unit
makes sure the air is not cooled back too far,
possibly causing draft complaints. If the
temperature is set too high, the unit will often be
turned off. It is recommended to maintain the
factory setting of 18 °C. This parameter will be
ignored when the switching point for winter
operation is reached.
6.3 T winter
When this menu is chosen, it is possible to change
this value between 10 and -10 °C. The entered
value is confirmed by pressing
. As soon as
the air temperature before the heat exchanger is
lower than this value, the Aquacom will start up.
When the temperature becomes higher, the
Aquacom will switch off until a switching point is
reached again. Winter operation is not dependent
on the date.
6.4 Frost limit
When this menu is chosen, it is possible to change
this value between 0 and -10 °C. The entered value
is confirmed by pressing
. As soon as the air
temperature after the heat exchanger is lower
than this value, the pump will start working
continuously. When the measured temperature
becomes higher, the Aquacom will turn itself off
until a switching point is reached again. This
protection will prevent the heat exchanger from
freezing by continuously pumping the glycol water
mixture in case of severe frost, provided that the
unit is not turned off. When this temperature is set
higher than the switching point for winter
operation, the switching point for winter operation
does not have any effect anymore on the
operation of the Aquacom. If the temperature
after the heat exchanger will not rise by 0.5 °C in
10 minutes, the unit will display the error '
Tempdiff < 0.5K'. This error message has to be
removed manually by pressing one of the buttons.
Also see section 5.2.4.
6.5 P summer
This submenu enables you to set the reaction
speed of the pump during summer operation,
using the P-factor. When this menu is selected, it is
possible to change this value between 8 and 15
using the
and
buttons. The entered value
is confirmed by pressing
. For a high value the
Aquacom will respond less quickly. For a low value
the Aquacom will respond very fast. It is
recommended not to change this value.
6.6 P winter
This submenu enables you to set the reaction
speed of the pump during winter operation, using
the P-factor. When this menu is selected, it is
possible to change this value between 8 and 15
using the
and
buttons. The entered value
is confirmed by pressing
. For a high value the
Aquacom will respond less quickly. For a low value
the Aquacom will respond very fast. It is
recommended not to change this value.
6.7 Set language
This submenu enables you to change the language
of the control unit. After this menu is activated, the
language can be changed by pressing the
and
buttons.
will confirm you choice.
6.8 Calibrate sensors
In this menu the sensors can be calibrated with
each other.
Only perform this action when a
sensor is replaced and the sensors are at the same
temperature
. Before you perform this action, place
both sensors together, preferably in a container
with melting ice-water. Next you select this menu
from the main menu and press
twice. The
control unit now middles the measured values and
saves these. If you erroneously entered this menu
and the control unit shows 'Calibrate sensors', you
can go back to the main menu by pressing
.
6.9 Operating hours
When this menu is entered, you can switch
between displaying the operating hours during
summer and winter operation by pressing the
and
buttons. This counter is not resettable,
and if the pump is replaced, the number of
operating hours needs to be written down in the
maintenance schedule.
6.10 Error messages
When this menu is accessed, the display will show
the saved error messages. Also repaired errors
which are not deleted will be shown here. Using