S-5
SECTION I: VENDOR INSTALLATION (CONTINUED)
For Type 1 and Type 2 outlets, test for Grounding and Polarization as follows:
1.
With a test device (volt meter or test light), connect one probe to the receptacle’s
neutral contact and the other to the live contact. The test device should show a
reaction.
2.
Connect one probe to the receptacle’s earth contact and the other to the live contact.
The test device should show a reaction.
For Type 3 through Type 5 outlets, test for Grounding as follows:
1
.
With a test device (volt meter or test light), determine which of the receptacle’s power
contacts is the live contact.
A.
Connect one probe to the receptacle’s earth contact.
B.
Connect the second probe to the left (or upper) power contact. If a reaction
occurs, this is the live power contact. If a reaction does not occur, move the
second probe to the right (or lower) contact. A reaction should occur, indicating
that this is the live power contact.
2.
Connect one probe to the receptacle’s live power contact (as determined in step 1).
Connect the second probe to the other power contact (neutral). The test device
should show a reaction.
IF THE ABOVE CONDITIONS ARE NOT MET FOR THE GIVEN OUTLET
TYPE, CONTACT A LICENSED ELECTRICIAN AND HAVE THE
NECESSARY CORRECTIONS MADE.