Thermo GSM Digital Thermostat User Manual
[delay] numerical value that indicates minutes of permanence after which the
threshold [threshold] can be considered an alarm
SET ALARM MAXIMUM restores the current configuration for the maximum
threshold
SET ALARM MINIMUM restores the current configuration for the minimum
threshold
Some examples:
SET ALARM MINIMUM INT 12 2 30 generates a minimum alarm if the measured
temperature by the internal probe decreases
12°C for 30 minutes and it considers the alarm
restored when the temperature exceeds 14°C
(12+2).
SET ALARM MAXIMUM EXT 28.5 1.5 50 generates a maximum alarm if the
measured temperature by the external
probe exceeds 28.5°C for 50 minutes and
considers the alarm restored when the
temperature decreases 27°C (28.5-1.5).
Note: the return alarm is immediate when the return alarm of the
temperature is reached (no delay)
Alarm of power supply failure
In case of power supply failure, the Thermo GSM has a buffer battery that permits
operation of the thermostat for about one hour.
The receivers of this alarm will receive the following messages in case of failure
and restoration of power supply:
POWER ALARM=INTERRUPTED (dd/mm/yy hh:mm)
END POWER ALARM=RESTORE (dd/mm/yy hh:mm)
By default, the phone number in the phonebook with index 1 receives alarm of
power supply failure.
Note: the alarm message is not sent instantaneously, but there is a delay
of a seconds (signalled by the flashing symbol ), allows the instrument
to have a stable GSM connection.