English
- 30 -
Thermo GSM Digital Thermostat User Manual
where:
[recipient] indicates the phone number in the phonebook to send the alarm.
Some examples:
SEND ALARM EXTERNAL 1 3 4 sends a text message to phone numbers 1, 3, 4 in
the phonebook in case of alarm on digital input
SEND ALARM MAXIMUM 2 sends a text message to phone number 2 in the
phonebook in case of alarm for exceeded temperature
threshold
SEND ALARM POWER 5 sends a text message to phone number 5 in the
phonebook in case of failure of power supply.
If the receiver is not specified, the instrument replies with the list of phone numbers
that receive the alarm. For example:
SEND ALARM EXTERNAL
EXTERNAL ALARM=1, 3, 4
Note: a new setting of receivers overwrites the previous setting, therefore it
is necessary to indicate all receivers in a single command.
To delete a setting of the receivers, use “EMPTY” .
For example:
SEND ALARM POWER EMPTY deletes all receivers in case of alarm for electrical
network failure
Definition of the alarm from digital input
It is possible to specify the condition for which an alarm occurs in the digital input.
In particular, it is necessary to define:
– the status (open or closed)
– the delay: the time after which a certain time can be considered as an alarm.
The alarm syntaxes are:
SET ALARM CONTACT OPEN
[delay]
SET ALARM CONTACT CLOSED
[delay]
where:
[delay] numeric value that indicates after how many seconds of permanence in
open or closed status can be considered an alarm
SET ALARM CONTACT
restores the current configuration of the input alarm