English
- 36 -
Mithos Chronothermostat User Manual
• Activation delay setting between 15, 30 and 45 minutes (independent for every hour)
• Measured temperature scale: 0°C ÷ +50°C
• Measured and displayed temperature resolution: 0.1°C
• Temperature regulation range: 2.0°C ÷ +35°C
• Measurement update: every 20 seconds
• Measurement precision: ± 0.5°C
• Winter or summer or manual operation
• Optional display in °F
• Automatic change CET / DST
• Password protected keypad lock for installation in public places
• Wall mounting (or on 503 type box)
• Radio Frequency remote actuator control
• Operating temperature: 0 °C ÷ +50 °C
• Operating humidity: 20% ÷ 90% noncondensing
• Storage temperature -10°C ÷ +65°C
• Degree of protection: XXD
The preset temperature values (expressed in °C) are the following:
funct. winter
funct. summer
T1
5.0
OFF
T2
15.0
23.0
T3
18.0
25.0
T
MANUAL
20.0
24.0
Regulation of temperature levels is subjected to the following condition: T1 ≤ T2 ≤T3.
In summer mode, T1 cannot be set and corresponds to the air conditioning OFF.
■
REMOTE ACTUATOR
• For details about technical specifications refer to the remote actuator documentation
supplied with the instrument.