background image

 
 
 
 
 
 
 
 
Mini-Spot 1-3T Systems 
Operating and Maintenance Instructions 
 
Cooling Operation 
Wall Mounted Thermostat 
 
A wall-mounted thermostat controls the cooling set point.  Upon a call for cooling, compressor 
contact and evaporator fan relay contacts close.  This will energize compressor and 
evaporator fan and condenser fan when applicable.  As temperature falls below the room set 
point, the compressor contacts and evaporator fan contacts will open de-energizing the 
system. 
 
Unit Mounted Thermostat 
 
A unit-mounted thermostat controls the set point.  Upon a call cooling, compressor contact 
relay closes. This will energize compressor and condenser fan when applicable.  As the 
temperature falls below the room set point the compressor contacts will open.   
 
Fan Operation 
 
Wall Mounted Thermostat 
 
The evaporator fan will operate in either auto or continuous mode, which is controlled by the 
thermostat sub-base.  In the auto on position, the evaporator fan will run continuously. 
 
Unit Mounted Thermostat 
 
On units with unit mounted thermostats, the evaporator fan relay is kept energized by factory 
installed jumper between terminals R & G. 
 
Humidification 
 
When the humidity drops below the set point on the wall mounted humidistat; the auxiliary fan 
relay is on if it was off. At the same time, the water solenoid is energized, supplying water to 
the evaporator pad When the humidity set point is reached the auxiliary relay and solenoid 
valve are de-energized.  
 

 
 
 
 
 
 
 
 

Содержание Mini-Spot 1-3T Systems

Страница 1: ...ssor and condenser fan when applicable As the temperature falls below the room set point the compressor contacts will open Fan Operation Wall Mounted Thermostat The evaporator fan will operate in eith...

Страница 2: ...to hangers raise unit several inches above the ceiling to allow placement of the grille into the ceiling grid After grille is in place lower unit just far enough for the frame to form an airtight seal...

Страница 3: ...s of a pressure activated switch mounted in the compressor section of the unit This control is factory adjusted but may be field adjusted if necessary I Motor Speed All 2 and 3 ton units are shipped w...

Страница 4: ...devices High and Low pressure switches are an integral part of the refrigeration system Should an unsafe high and or low pressure condition exist the appropriate safety device will trip Condensate ov...

Страница 5: ...Gas Line 1 1 2 1 5 8 7 8 3 1 5 8 7 8 1 Each circuit will have a liquid drain line and a hot gas line 2 The liquid line is an n oversized liquid line that runs between the condenser and receiver unit I...

Страница 6: ...tachment of use of any components accessories or devices other than those authorized by the manufacturer into onto or in conjunction with the air conditioner You should be aware that the use of unauth...

Страница 7: ...ondensing unit evaporator blower etc to make sure they are properly matched Remove shipping bracket under compressor if supplied With the thermostat in the Off position turn the power on to the furnac...

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Отзывы: