• Using the
" "
and
" "
keys,
choose
the desired regulation mode and press
" "
to confirm and move to the setting
of the next parameter.
Parameters for the chosen regulation type
(only for winter operation)
• In case of
"ON/OFF"
regulation type,
the only parameter to be set is the
differential. Field
(22)
will display the
writing
"dIF="
and on field
(16)
the
value currently set will flash. Press the
" "
and
" "
keys to increase or
decrease the value. The range varies from
0.1°C to 1°C.
• In case of
PROPORTIONAL
regulation type, the parameters to be set are:
-
regulation band
-
regulation period
Field
(22)
will display the writing
"bnd="
and on field
(16)
the value currently set
will flash. Press the
" "
and
" "
keys
to increase or decrease the value. The
range varies from 0.5°C to 5°C.
Once the band value is confirmed, field
(22)
will display the writing
"PEr="
and
on field
(16)
the value currently set will
flash. Press the
" "
and
" "
keys
to increase or decrease the value. It is
possible to choose between 10, 20 or 30
minutes.
For a wider description on how to operate the regulation type choice, please refer to
the chapter "REGULATION TYPE" on page 56.