AC200 Frequency Inverter Maunal
48
The REV Max
Frequency limit in
Torque Control
0x3007 or
0x2007
0
~
1000 is corresponding to 0.0%
~
100.0%
W/R
Communication Given
PID Setting
0x3008 or
0x2008
0
~
1000 is corresponding to 0.0%
~
100.0%
W/R
Communication Given
PID Feedback
0x3009 or
0x2009
0
~
1000 is corresponding to 0.0%
~
100.0%
W/R
Voltage Frequency
separation voltage
value setting
0x300A or
0x200A
0
~
1000 is corresponding to 0.0%
~
100.0%
W/R
Fault and pre- alarm
code reading
0x3010 or
0x2010
0-63 is the fault code
64- is the pre alarm code
R
Output terminal state
0x3010 or
0x2010
External borrowing inverter output terminal
BII0 -- Y
BIT1 -- TA1-TB1-TC1;
BIT2 -- TA2-TB2-TC2
R
AO1 output
0x3021 or
0x2021
0
~
10000 corresponds output 0V
~
10V,0mA
~
20mA
R
AO2 output
0x3022 or
0x2022
0
~
10000 corresponds output 0V
~
10V,0mA
~
20mA,0kHz
~
50kHz
R
Note: The other function code addresses refer to “Communication Address”of function code table. While using writing
command (06 H), if the highest digit of parameter function code address domain is 0, it only write in the RAM of inverter,
and on storage when power off; if the high half digit of parameter function code address is 1, it write in EEPROM, which
means power off storage.For instance,F0 parameter group:0X00XX (RAM);0X10XX(EEPROM)
●
List of fault code meanings for abnormal response information from salve machine:
Fault Code
Meanings
1
Order code fault
3
CRC checking fault
4
Illegal address
5
Illegal data
6
Unable to modify when running
8
Inverter busy
(
EEPROM is storing
)
9
Value over limit
10
Reserved parameters can’t be modify
11
Number of Bytes wrong when reading