AC200 Frequency Inverter Maunal
40
FC.52
Swing frequency
amplitude
0.0%
~
100.0%
10.0%
●
0xC34
FC.53
Jump frequency amplitude
0.0%
~
50.0%
10.0%
●
0xC35
FC.54
Swing frequency rising
time
0.00s
~
650.00s
5.00s
●
0xC36
FC.55
Swing frequency falling
time
0.00s
~
650.00s
5.00s
●
0xC37
FC.56
Reserved
0xC38
Communication Control Function Parameter Group
NO.
Function description
Range of settings and definition
Factory
default
Feature
Address
Fd.00
Main-slave machine
selection
LED “0” digit: Modbus main-slave
selection
0: Slave machine
1: Main machine
LED “00” digit: reserved
LED “000” digit: reserved
LED “0000” digit: reserved
0000
〇
0xD00
Fd.01
485 communication
address
1
~
247
1
〇
0xD01
Fd.02
Communication baud rate
selection
LED “0” digit: 485 communication
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
LED “00” digit: reserved
LED “000” digit: reserved
LED “0000” digit: reserved
0003
〇
0xD02
Fd.03
Modbus data format
0: (N,8,1) format
1: (E,8,1) format
2: (O,8,1) format
3: (N,8,2) format
4: (E,8,2) format
5: (O,8,2) format
0
〇
0xD03
Fd.04
Communication ratio
setting
0.00
~
5.00
1.00
●
0xD04
Fd.05
Modbus communication
answer delay
0ms
~
500ms
0ms
●
0xD05
Fd.06
Modbus communication
overtime fault time
0.1s
~
100.0s
1.0s
●
0xD06