AC200 Frequency Inverter Maunal
21
F3.33
Curve 1 lower limit
corresponding setting
0.00%
~
100.00%
0.0%
●
0x321
F3.34
Curve 1 inflection point 1
input voltage
0.00V
~
10.00V
3.00V
●
0x322
F3.35
Curve 1 inflection point1
corresponding setting
0.00%
~
100.00%
30.00%
●
0x323
F3.36
Curve 1 inflection point 2
input voltage
0.00V
~
10.00V
6.00V
●
0x324
F3.37
Curve 1 inflection point2
corresponding setting
0.00%
~
100.00%
60.00%
●
0x325
F3.38
Curve 1 upper limit
0.00V
~
10.00V
10.0V
●
0x326
F3.39
Curve 1 upper limit
corresponding setting
0.00%
~
100.00%
100.00%
●
0x327
F3.40
Curve 2 lower limit
0.00V
~
10.00V
0.00V
●
0x328
F3.41
Curve 2 lower limit
corresponding setting
0.00%
~
100.00%
0.00%
●
0x329
F3.42
Curve 2 inflection point 1
input voltage
0.00V
~
10.00V
3.00V
●
0x32A
F3.43
Curve 2 inflection point1
corresponding setting
0.00%
~
100.00%
30.00%
●
0x32B
F3.44
Curve 2 inflection point 2
input voltage
0.00V
~
10.00V
6.00V
●
0x32C
F3.45
Curve 2 inflection point2
corresponding setting
0.00%
~
100.00%
60.00%
●
0x32D
F3.46
Curve 2 upper limit
0.00V
~
10.00V
10.00V
●
0x32E
F3.47
Curve 2 upper limit
corresponding setting
0.00%
~
100.00%
100.00%
●
0x32F
F3.48-F3.52
Reserved
0x330
F3.53
A0 output signal selection
LED “0” digit: AO1
0: 0V
~
10V
1: 4.00mA
~
20.00mA
2: 0.00mA
~
20.00mA
LED “00” digit: A02
0: 0V
~
10V
1: 4.00mA
~
20.00mA
2: 0.00mA
~
20.00mA
3: FM frequency pulse output
LED “000” digit: reserved
0000
●