Set-up
VEGALOG
VEGAMET
Rx
The most important adjustment steps
On the following pages you see a menu plan
for the HART
®
-handheld in conjunction with
VEGASON 51K … 53K sensors. The most
important adjustment steps are marked in the
menu plan with the letters A … E. When enter-
ing parameters first of all the key "ENTER“
must be pressed. The adjustment is thereby
saved in the handheld, but not in the sensor
itself.
After pressing "SEND“, a warning is dis-
played, which informs you that you are about
to modify the configuration and for that,
safety reasons, you should switch your sys-
tem over to manual operation.
After having pressed "ENTER“, press "SEND“
(here in the example for the min.-adjustment).
Press "OK“ and the adjustment will now be
transferred to the sensor. After a short time
you are asked to switch you system over
from manual to automatic operation. Confirm
with "OK“.
4.2
(5.2)
Generic: SENSOR
1 PV LRV
5.850 m
2 PV URV
0.300 m
HELP SEND HOME
Generic: SENSOR
PV URV
5.850 m
0.300
m
HELP DEL
ESC ENTER
Generic: SENSOR
WARN-Loop should be
removed from
automatic control
ABORT OK
Generic: SENSOR
NOTE- Loop may be re-
turned to automatic control
OK
Generic: SENSOR
1 PV LRV
5.850 m
2 PV URV
0.300 m
HELP
HOME
You see the actual carried out adjustment.