32
VEGAPULS 56K
0
2,4 m
3,8 m
2,4 m
3,8 m
10 m
0 m
20 m
14˚
22˚
100 %
50 %
Heat isolation
Mounting on a longer DIN-socket piece
>␣ 10␣ mm
Emission cone of a DN 250 horn antenna
Measuring
distance
Mounting and installation
Heat isolation
In case of process temperatures of more than
200
°
C an isolation on the rear of the flange is
necessary to separate the radiation heat from
the sensor electronics.
The best would be to include the sensor
isolation into the vessel isolation and isolate it
up to approx. to the first pipe segment.
4.2 Measurement of liquids
Sensor on DIN-socket piece
Most of the time the mounting of radar sensors
is made on short DIN-socket pieces. The
instrument flange is the reference pane of the
measuring range. The antenna should always
protrude out of the flange pipe.
Mounting on short DIN-socket piece
Reference pane
When the DIN-socket piece is longer, note that
the horn antenna must protrude at least 10 mm
out of the socket.
When mounting on dished end vessels the
antenna has to protrude at least 10 mm.
40
°
C
60
°
C
100
°
C 240
°
C
350
°
C
Vessel isolation
max. 350
°
C