T
he simulation of a measured value is used to check the outputs and
connected components
.
T
he simulation can be applied to the
percentage value
,
the lin
.
percentage value and the sensor value
.
N
ote
:
P
lease note that connected system parts
(
valves
,
pumps
,
motors
,
control systems
)
are in
fl
uenced by the simulation
,
thus unintentional
plant operating conditions can occur
.
T
he simulation is terminated
automatically after approxminately
10
minutes
.
à
C
arry out your settings via the appropriate keys and save with
[
OK
]
.
T
here are two reset modes
:
l
R
eset to default
:
with only a few exceptions
,
all settings will be
reset to default
.
E
xceptions are
:
H
ost name
,
IP
-
addr
.,
subnet
mask
,
time
,
language
.
l
R
eset on measurement loop
:
T
he settings of the selected
measurement loop will be set to default
.
T
he measurement loop is
deactivated and the
TAG
name reset to default
.
W
ith every
4
…
20
m
A
/
HART
sensor
,
the measured value can be
transmitted via analog current signal or digital
HART
signal
.
T
his is
regulated via the
HART
mode or the address
.
I
f a
HART
sensor is set
to address
0
,
the sensor is in the standard mode
.
H
ere the measured
value is transmitted digitally on the
4
…
20
m
A
cable
.
I
n mode
HART M
ultidrop
,
an address from
1
…
15
is assigned to the
sensor
.
B
y doing so
,
the current is
fi
x limited to
4
m
A
and the
measured value transmission is only made digitally
.
S
ervice
-
S
imulation
S
ervice
-
R
eset
S
ervice
-
S
ensor add
-
ress
26
VEGAMET
625
•
D
ouble channel
HART
signal conditioning instrument
6
S
etup with the integrated indicating and adjustment unit
28970
-
EN
-
110801