6 Setup

VEGACAP 98 • Relay (DPDT)

33760-EN-230510

To adjust VEGACAP 98, loosen first of all the four screws on the up

-

per side of the instrument with a screwdriver and remove the housing 

cover. 

You can adapt the switching point to the solid with the potentiometer.

The electronics is adjustment free and an adaption is only necessry in 

exceptions. See " 

Exceptions

". 

With the mode switch you can change the switching condition of the 

relay. You can set the required mode (A - max. detection or overfill 

protection, B - min. detection or dry run protection).
We recommend connecting according to the idle current principle 

(relay contact deenergizes when the switching point is reached), 

because the relay always takes on the same (safe) state if a failure is 

detected or in case of mains failure.

Control lamp for indication of the switching status.

• 

Control lamp on = Relay deenergised

The measuring system is immediately ready for operation.

The switching point must no longer be set with VEGACAP 98. 
The probe has an active tip and a screen segment. Thanks to the 

screen segment, the so called standing capacitance, caused by the 

vessel after installation of the probe, is mainly compensated.
As a default setting, the electronics module is adjusted to the basic 

capacitance of the probe. The relay output switching when the active 

tip is covered (active tip: 90 mm / 3.5 in) of the electrode.
Changing dielectric values of the products, such as e.g. caused in 

mixing vessels are no problem for the switching accuracy within the 

active pin. The selection of the electrode length is hence very impor-

tant because the length of the electrode determines the switching 

point. This switching point cannot be shifted on the electrode.

In exceptions, e.g. in pipelines or if the probe is mounted very close to 

the vessel wall, it can happen ath the probe signals already overfilling 

(covering) in uncovered condition.
In this case, the switching point must be re-adjusted.

For adjustment, the vessel must not be filled and the switching point 

adjustment is also possible in dismounted condition.
A fresh adjustment is necessary in the following cases:

• 

in narrow space installation conditions with high standing capaci-

tance (e.g. in tubes etc.)

• 

after exchange of the electronics module

Proceed as follows for a fresh adjustment:
1.  Make sure that the probe is uncovered.
2.  Pierce the cover of the potentiometer (6) with a screwdriver.

Switching point adapta-

tion (6)

Mode adjustment (5)

Signal lamp (4)

Switching point adjust-

ment

Exceptions

Fresh adjustment

Содержание VEGACAP 98

Страница 1: ...Operating Instructions Capacitive rod electrode for level detection VEGACAP 98 Relay DPDT Document ID 33760...

Страница 2: ...operation 7 3 3 Adjustment 7 3 4 Packaging transport and storage 8 4 Mounting 9 4 1 General instructions 9 4 2 Mounting instructions 10 5 Connecting to power supply 12 5 1 Preparing the connection 12...

Страница 3: ...s to the Docu ment ID By entering the Document ID on www vega com you will reach the document download Information note tip This symbol indicates helpful additional infor mation and tips for successfu...

Страница 4: ...ect mounting or adjustment Damage to property and persons or environmental contamination can result Also the protective characteristics of the instrument can be impaired 2 4 General safety instruction...

Страница 5: ...ly with the relevant requirements of the Canadian Electrical Code CEC Par I Canada 2 7 Safety instructions for Ex areas For applications in explosion proof areas Ex only devices with cor responding Ex...

Страница 6: ...the order specification The VEGACAP 98 consists of the components Process fitting with probe Housing with electronics Housing lid 1 2 3 Fig 1 VEGACAP 98 1 Housing lid 2 Housing with electronics 3 Pro...

Страница 7: ...ic constant of the product compared to air the capacitance increases as the probe is gradually covered The capacitance change is converted by the electronics module into a switching command VEGACAP 98...

Страница 8: ...be checked for completeness and possible transit damage immediately at receipt Ascertained transit damage or con cealed defects must be appropriately dealt with Up to the time of installation the pack...

Страница 9: ...ny position The instru ment must be mounted in such a way that the probe is at the height of the requested switching point Before beginning the welding work remove the electronics module from the sens...

Страница 10: ...move these plugs before electrical connection NPT thread In the case of instrument housings with self sealing NPT threads it is not possible to have the cable entries screwed in at the factory The fre...

Страница 11: ...11 4 Mounting VEGACAP 98 Relay DPDT 33760 EN 230510 Fig 4 Inflowing medium...

Страница 12: ...three wire cable without shielding If electromagnetic interference is expected which is above the test values of EN 61326 for industrial areas shielded cable should be used Make sure that the cable us...

Страница 13: ...old plating on the relay contact surface will be permanently damaged The contact is then no longer suitable for switching low voltage circuits Inductive loads also result from the connection to a PLC...

Страница 14: ...output will change if you set the mode switch 5 afterwards This could possibly trigger other con nected instruments or devices 6 2 Adjustment elements 3 4 5 6 1 2 Fig 6 Electronics module with relay...

Страница 15: ...mainly compensated As a default setting the electronics module is adjusted to the basic capacitance of the probe The relay output switching when the active tip is covered active tip 90 mm 3 5 in of t...

Страница 16: ...6 The probe is now ready for operation Sensitivity Standard very sensitive additional turns Dielectric constant 2 2 turns Dielectric constant 1 5 1 turn Tab 1 Number of additional turns for the potent...

Страница 17: ...760 EN 230510 Level Switching status Control lamp Mode B Dry run protection 5 3 4 8 6 7 Relay energized Mode B Dry run protection 5 3 4 8 6 7 Relay deener gized Failure of the sup ply voltage mode A B...

Страница 18: ...check the output signal In many cases the causes can be determined this way and the faults quickly rectified Depending on the reason for the fault and the measures taken the steps described in chapter...

Страница 19: ...odule Check the resistance between the marked plug connections See the follow ing instructions Electronics defective Press the mode switch A B If the instrument then changes the mode the instrument ma...

Страница 20: ...insulation A possible reason could be also a non insu lated electrode which is used in a conductive humid medium If the resistor is higher or if the connection is interrupted the reason is mostly a c...

Страница 21: ...exchange the electronics module by a similar replacement electronics if available If the fault is eliminated after inserting the new electronics module then you have to carry out a fresh adjustment w...

Страница 22: ...hten cable gland and check on tightness The seal ring must completely encircle the cable 15 Carry out a fresh adjustment See chapter Set up new adjust ment 16 Screw the housing lid back on The electro...

Страница 23: ...o voltage sup ply and carry out the listed steps in reverse order 8 2 Disposal Pass the instrument on to a specialised recycling company and do not use the municipal collecting points Remove any batte...

Страница 24: ...rocess fittings Pipe thread cylindrical DIN 3852 A G1 Weight Instrument weight 0 8 4 kg 0 18 8 82 lbs Rod weight 33 mm 1 3 in approx 560 g m 6 oz ft Sensor length L 150 2000 mm 5 91 78 74 ft Active ti...

Страница 25: ...onditions Ambient temperature on the housing 40 80 C 40 176 F Storage and transport temperature 40 80 C 40 176 F Process conditions Process pressure unpressurized Process temperature VEGACAP 98 of PP...

Страница 26: ...nical specifications depending on the version For that reason the associated approval documents of these instruments have to be carefully noted They are part of the delivery or can be downloaded by en...

Страница 27: ...nter www vega com Les lignes de produits VEGA sont globalement prot g es par des droits de propri t intellec tuelle Pour plus d informations on pourra se r f rer au site www vega com VEGA lineas de pr...

Страница 28: ...28 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 29: ...29 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 30: ...30 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 31: ...31 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 32: ...ing scope of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change withou...

Отзывы: