7 Diagnostics and servicing

VEGACAP 98 • Relay (DPDT)

33760-EN-230510

If the resistance value is > 3 Ω, this can be due to corrosion on the 

thread or flange or the thread was covered e.g. with teflon tape.

Check the connection to the vessel. If there is no connection, you can 

connect a cable from the outer ground terminal to the vessel.

Keep in mind that coated flanges must always be connected via the 

ground terminal to the vessel.

Contact 7 against contact 1 (middle pin)

The resistor must be infinite (> 10 MΩ)

If the resistor is lower, then moisture can be penetrated or the com-

pensation capacitor or variable capacitor (phase) is defective.

Contact 3 (shielding) against contact 4

The resistor must be 1 MΩ.

In case of lower values, the electrode insulation is defective or mois-

ture is penetrated into the housing.
In case of higher values, there is a contacting error in the adapter 

plate or the resistor is defective.

No fault

If you cannot find a fault in the probe, then exchange the electronics 

module by a similar replacement electronics (if available).
If the fault is eliminated after inserting the new electronics module, 

then you have to carry out a fresh adjustment with the new electron-

ics module because electronics modules have certain manufacturing 

tolerances.
If the fault still exists or if no replacement electronics module is avail-

able, then you have to return the probe for repair.

Contact 3 (shielding) against contact 1 (middle pin)

The resistor must be 2 MΩ.

In case of lower values, the electrode insulation is defective or mois-

ture is penetrated into the housing.
In case of higher values, there is a contacting error in the adapter 

plate or the resistor is defective.

7.3  Exchanging the electronics module

If it is necessary to exchange the electronics module, you should use 

an electronics module type CAP E31R
Proceed as follows:

1.  Switch off voltage supply

2.  Loosen the four screws of the housing cover with a Phillips screw-

driver.

3.  Remove the housing cover
4.  Loosen the screws of the terminals with a Allen wrench.
5.  Pull the connection cables out of the terminals.
6.  Loosen the two screws with a Torx screwdriver.

Содержание VEGACAP 98

Страница 1: ...Operating Instructions Capacitive rod electrode for level detection VEGACAP 98 Relay DPDT Document ID 33760...

Страница 2: ...operation 7 3 3 Adjustment 7 3 4 Packaging transport and storage 8 4 Mounting 9 4 1 General instructions 9 4 2 Mounting instructions 10 5 Connecting to power supply 12 5 1 Preparing the connection 12...

Страница 3: ...s to the Docu ment ID By entering the Document ID on www vega com you will reach the document download Information note tip This symbol indicates helpful additional infor mation and tips for successfu...

Страница 4: ...ect mounting or adjustment Damage to property and persons or environmental contamination can result Also the protective characteristics of the instrument can be impaired 2 4 General safety instruction...

Страница 5: ...ly with the relevant requirements of the Canadian Electrical Code CEC Par I Canada 2 7 Safety instructions for Ex areas For applications in explosion proof areas Ex only devices with cor responding Ex...

Страница 6: ...the order specification The VEGACAP 98 consists of the components Process fitting with probe Housing with electronics Housing lid 1 2 3 Fig 1 VEGACAP 98 1 Housing lid 2 Housing with electronics 3 Pro...

Страница 7: ...ic constant of the product compared to air the capacitance increases as the probe is gradually covered The capacitance change is converted by the electronics module into a switching command VEGACAP 98...

Страница 8: ...be checked for completeness and possible transit damage immediately at receipt Ascertained transit damage or con cealed defects must be appropriately dealt with Up to the time of installation the pack...

Страница 9: ...ny position The instru ment must be mounted in such a way that the probe is at the height of the requested switching point Before beginning the welding work remove the electronics module from the sens...

Страница 10: ...move these plugs before electrical connection NPT thread In the case of instrument housings with self sealing NPT threads it is not possible to have the cable entries screwed in at the factory The fre...

Страница 11: ...11 4 Mounting VEGACAP 98 Relay DPDT 33760 EN 230510 Fig 4 Inflowing medium...

Страница 12: ...three wire cable without shielding If electromagnetic interference is expected which is above the test values of EN 61326 for industrial areas shielded cable should be used Make sure that the cable us...

Страница 13: ...old plating on the relay contact surface will be permanently damaged The contact is then no longer suitable for switching low voltage circuits Inductive loads also result from the connection to a PLC...

Страница 14: ...output will change if you set the mode switch 5 afterwards This could possibly trigger other con nected instruments or devices 6 2 Adjustment elements 3 4 5 6 1 2 Fig 6 Electronics module with relay...

Страница 15: ...mainly compensated As a default setting the electronics module is adjusted to the basic capacitance of the probe The relay output switching when the active tip is covered active tip 90 mm 3 5 in of t...

Страница 16: ...6 The probe is now ready for operation Sensitivity Standard very sensitive additional turns Dielectric constant 2 2 turns Dielectric constant 1 5 1 turn Tab 1 Number of additional turns for the potent...

Страница 17: ...760 EN 230510 Level Switching status Control lamp Mode B Dry run protection 5 3 4 8 6 7 Relay energized Mode B Dry run protection 5 3 4 8 6 7 Relay deener gized Failure of the sup ply voltage mode A B...

Страница 18: ...check the output signal In many cases the causes can be determined this way and the faults quickly rectified Depending on the reason for the fault and the measures taken the steps described in chapter...

Страница 19: ...odule Check the resistance between the marked plug connections See the follow ing instructions Electronics defective Press the mode switch A B If the instrument then changes the mode the instrument ma...

Страница 20: ...insulation A possible reason could be also a non insu lated electrode which is used in a conductive humid medium If the resistor is higher or if the connection is interrupted the reason is mostly a c...

Страница 21: ...exchange the electronics module by a similar replacement electronics if available If the fault is eliminated after inserting the new electronics module then you have to carry out a fresh adjustment w...

Страница 22: ...hten cable gland and check on tightness The seal ring must completely encircle the cable 15 Carry out a fresh adjustment See chapter Set up new adjust ment 16 Screw the housing lid back on The electro...

Страница 23: ...o voltage sup ply and carry out the listed steps in reverse order 8 2 Disposal Pass the instrument on to a specialised recycling company and do not use the municipal collecting points Remove any batte...

Страница 24: ...rocess fittings Pipe thread cylindrical DIN 3852 A G1 Weight Instrument weight 0 8 4 kg 0 18 8 82 lbs Rod weight 33 mm 1 3 in approx 560 g m 6 oz ft Sensor length L 150 2000 mm 5 91 78 74 ft Active ti...

Страница 25: ...onditions Ambient temperature on the housing 40 80 C 40 176 F Storage and transport temperature 40 80 C 40 176 F Process conditions Process pressure unpressurized Process temperature VEGACAP 98 of PP...

Страница 26: ...nical specifications depending on the version For that reason the associated approval documents of these instruments have to be carefully noted They are part of the delivery or can be downloaded by en...

Страница 27: ...nter www vega com Les lignes de produits VEGA sont globalement prot g es par des droits de propri t intellec tuelle Pour plus d informations on pourra se r f rer au site www vega com VEGA lineas de pr...

Страница 28: ...28 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 29: ...29 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 30: ...30 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 31: ...31 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 32: ...ing scope of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change withou...

Отзывы: