5 Connecting to power supply

VEGACAP 98 • Relay (DPDT)

33760-EN-230510

5  Connecting to power supply

5.1  Preparing the connection

Always keep in mind the following safety instructions:

Warning:

Connect only in the complete absence of line voltage.

• 

The electrical connection must only be carried out by trained, 

qualified personnel authorised by the plant operator.

• 

Always switch off power supply, before connecting or disconnect

-

ing the instrument.

Connect the voltage supply according to the following connection 

diagrams. The electronics module CAP E31R is designed in protec-

tion class I. To maintain this protection class, it is absolutely neces-

sary that the ground conductor be connected to the internal ground 

terminal. Take note of the general installation regulations.

The data for power supply are specified in chapter " 

Technical data

". 

The instrument is connected with standard three-wire cable without 

shielding. If electromagnetic interference is expected which is above 

the test values of EN 61326 for industrial areas, shielded cable should 

be used.
Make sure that the cable used has the required temperature resist-

ance and fire safety for max. occurring ambient temperature

Use cable with round cross-section. A cable outer diameter of 

5 … 9 mm (0.2 … 0.35 in) ensures the seal effect of the cable gland. 

If you are using cable with a different diameter or cross-section, 

exchange the seal or use a suitable cable gland.

Note:

When placing the housing cover, make sure that the inspection glass 

is above the signal lamp of the electronics module.

5.2  Wiring plan - single chamber housing

We recommend connecting VEGACAP 98 in such a way that the 

switching circuit is open when there is a level signal, line break or 

failure (safe state). 
The relays are always shown in non-operative condition.
The two relays (DPDT) work synchronously. Hence it is possible to 

control also e.g. a horn and a magnet valve.

Note safety instructions

Voltage supply

Connection cable

Wiring plan

Содержание VEGACAP 98

Страница 1: ...Operating Instructions Capacitive rod electrode for level detection VEGACAP 98 Relay DPDT Document ID 33760...

Страница 2: ...operation 7 3 3 Adjustment 7 3 4 Packaging transport and storage 8 4 Mounting 9 4 1 General instructions 9 4 2 Mounting instructions 10 5 Connecting to power supply 12 5 1 Preparing the connection 12...

Страница 3: ...s to the Docu ment ID By entering the Document ID on www vega com you will reach the document download Information note tip This symbol indicates helpful additional infor mation and tips for successfu...

Страница 4: ...ect mounting or adjustment Damage to property and persons or environmental contamination can result Also the protective characteristics of the instrument can be impaired 2 4 General safety instruction...

Страница 5: ...ly with the relevant requirements of the Canadian Electrical Code CEC Par I Canada 2 7 Safety instructions for Ex areas For applications in explosion proof areas Ex only devices with cor responding Ex...

Страница 6: ...the order specification The VEGACAP 98 consists of the components Process fitting with probe Housing with electronics Housing lid 1 2 3 Fig 1 VEGACAP 98 1 Housing lid 2 Housing with electronics 3 Pro...

Страница 7: ...ic constant of the product compared to air the capacitance increases as the probe is gradually covered The capacitance change is converted by the electronics module into a switching command VEGACAP 98...

Страница 8: ...be checked for completeness and possible transit damage immediately at receipt Ascertained transit damage or con cealed defects must be appropriately dealt with Up to the time of installation the pack...

Страница 9: ...ny position The instru ment must be mounted in such a way that the probe is at the height of the requested switching point Before beginning the welding work remove the electronics module from the sens...

Страница 10: ...move these plugs before electrical connection NPT thread In the case of instrument housings with self sealing NPT threads it is not possible to have the cable entries screwed in at the factory The fre...

Страница 11: ...11 4 Mounting VEGACAP 98 Relay DPDT 33760 EN 230510 Fig 4 Inflowing medium...

Страница 12: ...three wire cable without shielding If electromagnetic interference is expected which is above the test values of EN 61326 for industrial areas shielded cable should be used Make sure that the cable us...

Страница 13: ...old plating on the relay contact surface will be permanently damaged The contact is then no longer suitable for switching low voltage circuits Inductive loads also result from the connection to a PLC...

Страница 14: ...output will change if you set the mode switch 5 afterwards This could possibly trigger other con nected instruments or devices 6 2 Adjustment elements 3 4 5 6 1 2 Fig 6 Electronics module with relay...

Страница 15: ...mainly compensated As a default setting the electronics module is adjusted to the basic capacitance of the probe The relay output switching when the active tip is covered active tip 90 mm 3 5 in of t...

Страница 16: ...6 The probe is now ready for operation Sensitivity Standard very sensitive additional turns Dielectric constant 2 2 turns Dielectric constant 1 5 1 turn Tab 1 Number of additional turns for the potent...

Страница 17: ...760 EN 230510 Level Switching status Control lamp Mode B Dry run protection 5 3 4 8 6 7 Relay energized Mode B Dry run protection 5 3 4 8 6 7 Relay deener gized Failure of the sup ply voltage mode A B...

Страница 18: ...check the output signal In many cases the causes can be determined this way and the faults quickly rectified Depending on the reason for the fault and the measures taken the steps described in chapter...

Страница 19: ...odule Check the resistance between the marked plug connections See the follow ing instructions Electronics defective Press the mode switch A B If the instrument then changes the mode the instrument ma...

Страница 20: ...insulation A possible reason could be also a non insu lated electrode which is used in a conductive humid medium If the resistor is higher or if the connection is interrupted the reason is mostly a c...

Страница 21: ...exchange the electronics module by a similar replacement electronics if available If the fault is eliminated after inserting the new electronics module then you have to carry out a fresh adjustment w...

Страница 22: ...hten cable gland and check on tightness The seal ring must completely encircle the cable 15 Carry out a fresh adjustment See chapter Set up new adjust ment 16 Screw the housing lid back on The electro...

Страница 23: ...o voltage sup ply and carry out the listed steps in reverse order 8 2 Disposal Pass the instrument on to a specialised recycling company and do not use the municipal collecting points Remove any batte...

Страница 24: ...rocess fittings Pipe thread cylindrical DIN 3852 A G1 Weight Instrument weight 0 8 4 kg 0 18 8 82 lbs Rod weight 33 mm 1 3 in approx 560 g m 6 oz ft Sensor length L 150 2000 mm 5 91 78 74 ft Active ti...

Страница 25: ...onditions Ambient temperature on the housing 40 80 C 40 176 F Storage and transport temperature 40 80 C 40 176 F Process conditions Process pressure unpressurized Process temperature VEGACAP 98 of PP...

Страница 26: ...nical specifications depending on the version For that reason the associated approval documents of these instruments have to be carefully noted They are part of the delivery or can be downloaded by en...

Страница 27: ...nter www vega com Les lignes de produits VEGA sont globalement prot g es par des droits de propri t intellec tuelle Pour plus d informations on pourra se r f rer au site www vega com VEGA lineas de pr...

Страница 28: ...28 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 29: ...29 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 30: ...30 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 31: ...31 Notes VEGACAP 98 Relay DPDT 33760 EN 230510...

Страница 32: ...ing scope of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change withou...

Отзывы: